A fire alarm system is a building system designed to detect, alert occupants, and alert emergency forces of the presence of
fire
Fire is the rapid oxidation of a fuel in the exothermic chemical process of combustion, releasing heat, light, and various reaction Product (chemistry), products.
Flames, the most visible portion of the fire, are produced in the combustion re ...
,
smoke
Smoke is an aerosol (a suspension of airborne particulates and gases) emitted when a material undergoes combustion or pyrolysis, together with the quantity of air that is entrained or otherwise mixed into the mass. It is commonly an unwante ...
,
carbon monoxide
Carbon monoxide (chemical formula CO) is a poisonous, flammable gas that is colorless, odorless, tasteless, and slightly less dense than air. Carbon monoxide consists of one carbon atom and one oxygen atom connected by a triple bond. It is the si ...
, or other fire-related emergencies. Fire alarm systems are required in most commercial buildings. They may include smoke detectors, heat detectors, and manual fire alarm activation devices (
pull stations). All components of a fire alarm system are connected to a
fire alarm control panel. Fire alarm control panels are usually found in an electrical or panel room. Fire alarm systems generally use visual and audio
signal
A signal is both the process and the result of transmission of data over some media accomplished by embedding some variation. Signals are important in multiple subject fields including signal processing, information theory and biology.
In ...
ization to warn the occupants of the building. Some fire alarm systems may also disable
elevators, which are unsafe to use during a fire under most circumstances.
Design
Fire alarm systems are designed after fire protection requirements in a location are established, which is usually done by referencing the minimum levels of security mandated by the appropriate model building code, insurance agencies, and other authorities. A fire alarm designer will detail specific components, arrangements, and interfaces necessary to accomplish these requirements. Equipment specifically manufactured for these purposes is selected, and standardized installation methods are anticipated during the design. There are several commonly referenced standards for fire protection requirements, including:
*
ISO
The International Organization for Standardization (ISO ; ; ) is an independent, non-governmental, international standard development organization composed of representatives from the national standards organizations of member countries.
Me ...
7240-14, the international standard for the design, installation, commissioning, and service of fire detection and fire alarm systems in and around a building. This standard was published in August 2013.
*
NFPA 72, ''The National Fire Alarm Code'', an established and widely used installation standard from the United States. In Canada, the
Underwriters' Laboratories of Canada or ULC provides fire system installation standards.
* TS 54 -14 is a technical specification (CEN/TS) for fire detection and fire alarm systems (Part 14: Guidelines for planning, design, installation, commissioning, use, and maintenance). Technical Committee CEN/TC72 has prepared this document as part of the
EN 54 series of standards. This standard was published in October 2018.
There are national codes in each European country for planning, design, installation, commissioning, use, and maintenance of fire detection systems with additional requirements that are mentioned on TS 54 -14:
* Germany,
VdS 2095
* Italy,
UNI 9795
* France,
NF S61-936
* Spain,
UNE 23007-14
* United Kingdom,
BS 5839 Part 1
Across
Oceania
Oceania ( , ) is a region, geographical region including Australasia, Melanesia, Micronesia, and Polynesia. Outside of the English-speaking world, Oceania is generally considered a continent, while Mainland Australia is regarded as its co ...
, the following standards outline the requirements, test methods, and performance criteria for fire detection control and indicating equipment utilised in building fire detection and fire alarm systems:
*
Australia
Australia, officially the Commonwealth of Australia, is a country comprising mainland Australia, the mainland of the Australia (continent), Australian continent, the island of Tasmania and list of islands of Australia, numerous smaller isl ...
AS 1603.4 (superseded), AS 4428.1 (superseded), and AS 7240.2:2018.
Parts
Fire alarm systems are composed of several distinct parts:
*
Fire alarm control panel (FACP), or fire alarm control unit (FACU): This component, the hub of the system, monitors inputs and system integrity, controls outputs, and transmits information.
* Remote annunciator: a device that connects directly to the panel; the annunciator's main purpose is to allow emergency personnel to view the system status and take command from outside the electrical room the panel is located in. Usually, annunciators are installed by the front door, the door the fire department responds by, or in a fire command center. Annunciators typically have the same
commands as those available from the panel's
LCD screen, although some annunciators allow for full system control.
* Primary power supply: Commonly, a commercial power utility supplies a non-switched 120 or 240-volt
alternating current
Alternating current (AC) is an electric current that periodically reverses direction and changes its magnitude continuously with time, in contrast to direct current (DC), which flows only in one direction. Alternating current is the form in w ...
source. A dedicated
branch circuit is connected to the fire alarm system and its constituents in non-residential applications. "Dedicated branch circuits" should not be confused with "Individual branch circuits" which supply energy to a single appliance.
* Secondary (backup) power supplies: Sealed
lead-acid storage batteries or other emergency sources, including
generators, are used to supply energy during a primary power failure. The batteries can be either inside the bottom of the panel or inside a separate battery box installed near the panel.
* Initiating devices: These components act as
inputs to the fire alarm control unit and are manually or automatically activated. Examples include pull stations,
heat detectors, duct detectors, and
smoke detectors.
*
Fire alarm notification appliance: This component uses energy supplied from the fire alarm system or other stored energy source to inform the proximate persons of the need to take action, usually to
evacuate. This is done using a variety of audio and visual means, ranging from pulsing
incandescent lights, flashing
strobe light
A strobe light or stroboscopic lamp, commonly called a strobe, is a device used to produce regular flashes of light. It is one of a number of devices that can be used as a stroboscope. The word originated from the Ancient Greek ('), meaning ...
s,
horns,
sirens,
chimes,
bell
A bell /ˈbɛl/ () is a directly struck idiophone percussion instrument. Most bells have the shape of a hollow cup that when struck vibrates in a single strong strike tone, with its sides forming an efficient resonator. The strike may be m ...
s,
loudspeaker
A loudspeaker (commonly referred to as a speaker or, more fully, a speaker system) is a combination of one or more speaker drivers, an enclosure, and electrical connections (possibly including a crossover network). The speaker driver is an ...
s, or a combination of these devices.
* Building safety interfaces: This interface allows the fire alarm system to control aspects of the built environment, prepare the building for fire, and control the spread of smoke fumes by influencing air movement, lighting, process control, human transport, and availability of exits.
Initiating devices

Initiating devices used to activate a fire alarm system are either manually or automatically actuated devices. Manually actuated devices, also known as
fire alarm boxes, manual pull stations, or simply pull stations, break glass stations, and (in Europe) call points, are installed to be readily located (usually near the exits of a floor or building), identified, and operated. They are usually actuated using physical interaction, such as pulling a lever or breaking glass.
Automatically actuated devices can take many forms, and are intended to respond to any number of detectable physical changes associated with fire: convected thermal energy for a
heat detector, products of combustion for a
smoke detector,
radiant energy
In physics, and in particular as measured by radiometry, radiant energy is the energy of electromagnetic radiation, electromagnetic and gravitational radiation. As energy, its SI unit is the joule (J). The quantity of radiant energy may be calcul ...
for a
flame detector, combustion gases for a
fire gas detector, and operation of sprinklers for a water-flow detector. Automatic initiating devices may use
camera
A camera is an instrument used to capture and store images and videos, either digitally via an electronic image sensor, or chemically via a light-sensitive material such as photographic film. As a pivotal technology in the fields of photograp ...
s and computer algorithms to analyze and respond to the visible effects of fire and movement in applications inappropriate for or hostile to other detection methods.
Notification appliances
Alarms can take many forms, but are most often either motorized bells or wall-mountable sounders or horns. They can also be speaker strobes that sound an alarm, followed by a voice evacuation message for clearer instructions on what to do. Fire alarm sounders can be set to certain frequencies and different tones, either low, medium, or high, depending on the country and manufacturer of the device. Most fire alarm systems in Europe sound like a siren with alternating frequencies. Fire alarm electronic devices are known as horns in the United States and Canada and can be continuous or set to different codes. Fire alarm warning devices can also be set to different volume levels.
Notification appliances utilize audible, visible, tactile, textual or even olfactory stimuli (
odorizers)
[
] to alert the occupants of the need to evacuate or take action in the event of a fire or other emergency. Evacuation signals may consist of simple appliances that transmit uncoded information, coded appliances that transmit a predetermined pattern, and/or appliances that transmit audible and visible information such as live or prerecorded instructions and illuminated message displays. Some notification appliances are a combination of fire alarm and general
emergency notification appliances, allowing both types of emergency notifications from a single device. In addition to pre-recorded and predetermined messages and instructions, some systems also support the live broadcasting and recording of voice announcements to all or certain parts of the property or facility, including customized instructions for the situation for each area, such as by emergency or facility management personnel. Outdoor appliances (such as large-scale speaker/horn/strobe poles to effectively reach outdoor occupants over potentially larger distances or areas), lighting control, and dynamic exit signage may also be used in certain circumstances.
Emergency voice alarm communication systems
Some fire alarm systems utilize emergency voice alarm communication systems (EVAC) to provide prerecorded and manual voice messages. Voice alarm systems are typically used in high-rise buildings, arenas, and other large "defend-in-place" occupancies such as hospitals and detention facilities where total evacuation is difficult to achieve. Voice-based systems allow response personnel to conduct orderly evacuation and notify building occupants of changing event circumstances.
Audible textual appliances can be employed as part of a fire alarm system that includes EVAC capabilities. High-reliability speakers notify the occupants of the need for action concerning a fire or other emergency. These speakers are employed in large facilities where general undirected evacuation is impracticable or undesirable. The signals from the speakers are used to direct the occupant's response. The fire alarm system automatically actuates speakers in a fire event. Following a pre-alert tone, selected groups of speakers may transmit one or more prerecorded messages directing the occupants to safety. These messages may be repeated in one or more languages. The system may be controlled from one or more locations within the building, known as "fire warden stations", or from a single location designated as the building's "fire command center". From these control locations, trained personnel activating and speaking into a dedicated microphone can suppress the replay of automated messages to initiate or relay real-time voice instructions.
In
highrise buildings, different evacuation messages may be played on each floor, depending on the location of the fire. The floor the fire is on along with ones above it may be told to evacuate while floors much lower may be asked to stand by.
In the United States
In the United States, fire alarm evacuation signals generally consist of a standardized audible tone, with visual notification in all public and common-use areas. Emergency signals are intended to be distinct and understandable to avoid confusion with other signals.
As per
NFPA 72, 18.4.2 (2010 Edition), Temporal Code 3 is the standard audible notification in a modern system. It consists of a repeated three-pulse cycle (0.5 s on, 0.5 s off, 0.5 s on, 0.5 s off, 0.5 s on, 1.5 s off). Voice evacuation is the second most common audible notification in modern systems. Legacy systems, typically found in older schools and buildings, have used continuous tones alongside other audible notifications.
In the United Kingdom
In the United Kingdom, fire alarm evacuation signals generally consist of a two-tone siren with visual notifications in all public and common-use areas. Some fire alarm devices can emit an alert signal, which is generally used in schools for lesson changes, the start of morning break, the end of morning break, the start of lunch break, the end of lunch break, and when the school day is over.
Emergency communication systems
New codes and standards introduced around 2010, especially the new UL Standard 2572, the US Department of Defense's UFC 4-021-01 Design and O&M Mass Notification Systems, and NFPA 72 2010 edition Chapter 24, have led fire alarm system manufacturers to expand their systems voice evacuation capabilities to support new requirements for mass notification. These expanded capabilities include support for multiple types of emergency messaging (i.e., inclement weather emergency, security alerts, amber alerts). The major requirement of a mass notification system is to provide prioritized messaging according to the local facilities' emergency response plan, and the fire alarm system must support the promotion and demotion of notifications based on this emergency response plan. In the United States,
emergency communication system
An emergency communication system (ECS) is any system (typically computer-based) that is organized for the primary purpose of supporting one-way and two-way communication of emergency information between both individuals and groups of individuals ...
s also have requirements for visible notification in coordination with any audible notification activities to meet the needs of the
Americans with Disabilities Act.
Mass notification system categories include the following:
* Tier 1 systems are in-building and provide the highest level of survivability
* Tier 2 systems are out of the building and provide the middle level of survivability
* Tier 3 systems are "At Your Side" and provide the lowest level of survivability
Mass notification systems often extend the notification appliances of a standard fire alarm system to include PC-based workstations, computers, mobile devices, text-based or display monitor-based digital signage, and a variety of remote notification options including
email
Electronic mail (usually shortened to email; alternatively hyphenated e-mail) is a method of transmitting and receiving Digital media, digital messages using electronics, electronic devices over a computer network. It was conceived in the ...
,
text message
Text messaging, or texting, is the act of composing and sending electronic messages, typically consisting of alphabetic and numeric characters, between two or more users of mobile phones, tablet computers, smartwatches, desktop computer, des ...
, RCS/other messaging protocols, phone calls, social media,
RSS feed, or
IVR-based telephone text-to-speech messaging. In some cases and locations, such as airports, localized cellular communication devices may also send wireless emergency alerts to cell phones in the area, and radio override may override other radio signals to play the emergency message and instructions to radios in range of the signal.
Residential systems
Residential fire alarm systems are commonplace. Typically, residential fire alarm systems are installed along with
security alarm
A security alarm is a system designed to detect intrusions, such as unauthorized entry, into a building or other areas, such as a home or school. Security alarms protect against burglary (theft) or property damage, as well as against intruders. ...
systems. In the United States, a residential fire alarm system is required in buildings where more than 12 smoke detectors are needed. Residential systems generally have fewer parts compared to commercial systems.
Building safety interfaces
Various equipment may be connected to a fire alarm system to facilitate evacuation or to control a fire, directly or indirectly:
* Magnetic smoke door holders and retainers are wall-mounted
solenoids or
electromagnet
An electromagnet is a type of magnet in which the magnetic field is produced by an electric current. Electromagnets usually consist of wire (likely copper) wound into a electromagnetic coil, coil. A current through the wire creates a magnetic ...
s controlled by a fire alarm system or detection component that magnetically secures spring-loaded self-closing smoke-tight
doors in the open position. The device
demagnetizes to allow automatic closure of the door on command from the fire control or upon failure of the power source, interconnection, or controlling element. Stored energy in the form of a spring or gravity can then close the door to restrict the passage of smoke from one space to another in order to facilitate evacuation and firefighting efforts. Electromagnetic fire door holders may also be hard-wired into the fire panel, radio-controlled, triggered by
radio wave
Radio waves (formerly called Hertzian waves) are a type of electromagnetic radiation with the lowest frequencies and the longest wavelengths in the electromagnetic spectrum, typically with frequencies below 300 gigahertz (GHz) and wavelengths g ...
s from a central controller connected to a fire panel, or acoustic, which learns the sound of the fire alarm and releases the door upon hearing this exact sound.
* Duct-mounted smoke detectors may be mounted in such a manner as to sample the airflow through
ductwork and other
plenums fabricated explicitly for the transport of environmental air into
conditioned spaces. As part of the fire alarm system, these detectors may be connected to the fan motor control circuits in order to stop air movement, close
dampers and generally prevent the recirculation of toxic smoke and fumes from fire in occupied spaces.
* Automatic initiating devices associated with
elevator operation are used for emergency elevator functions, such as the recall of associated elevator cab(s). The recall will cause the elevator cabs to return to the ground level for use by
fire service response teams and to ensure that cabs do not return to the floor of fire incidence, as well as preventing people from becoming trapped in the elevators. Phases of operation include primary recall (typically the ground level), alternate/secondary recall (typically a floor adjacent to the ground level—used when the fire alarm initiation occurred on the primary level), illumination of the "fire hat" indicator when an alarm occurs in the elevator hoistway or associated control room, and in some cases shunt trip (disconnect) of elevator power (generally used where the control room or hoistway is protected by
fire sprinkler
A fire sprinkler or sprinkler head is the component of a fire sprinkler system that discharges water when the effects of a fire have been detected, such as when a predetermined temperature has been exceeded. Fire sprinklers are extensively used ...
s).
* Audio
public address racks can be interfaced with a fire alarm system by adding a signaling control relay module to either the rack's power supply unit or the main amplifier driving the rack. The purpose of the fire alarm system interface is usually to "mute" the
background music
Background music (British English: piped music) is a mode of musical performance in which the music is not intended to be a primary focus of potential listeners, but its content, character, and volume level are deliberately chosen to affect behav ...
in case of an emergency.
British fire alarm system categories
In the United Kingdom, fire alarm systems in non-domestic premises are generally designed and installed in accordance with the guidance given in
BS 5839 Part 1. There are many types of fire alarm systems, each suited to different building types and applications. A fire alarm system can vary dramatically in price and complexity, from a single panel with a detector and sounder in a small commercial property to an addressable fire alarm system in a multi-occupancy building.
BS 5839 Part 1 categorizes fire alarm systems as:
* "M" manual systems (no automatic fire detectors, so the building is fitted with call points and sounders).
* "L" automatic systems intended for the protection of life.
* "P" automatic systems intended for the protection of property.
Categories for automatic systems are further subdivided into L1 to L5 and P1 to P2.
Zoning
An important consideration when designing fire alarms is that of individual "zones". The following recommendations are found in
BS 5839 Part 1:
* A single zone should not exceed in floor space.
* Where addressable systems are in place, two faults should not remove protection from an area greater than .
* A building may be viewed as a single zone if the floor space is less than .
* Where the floor space exceeds then all zones should be restricted to a single floor level.
* Stairwells, lift shafts or other vertical shafts (nonstop risers) within a single fire compartment should be considered as one or more separate zones.
* The maximum distance traveled within a zone to locate the fire should not exceed .
The NFPA recommends placing a list for reference near the fire alarm control panel showing the devices contained in each zone.
See also
*
Fire Safety Equivalency System
*
Multiple-alarm fire
*
National Fire Protection Association
The National Fire Protection Association (NFPA) is a U.S.-based international nonprofit organization devoted to eliminating death, injury, property damage, and economic loss due to fire, electrical, and related hazards. , the NFPA claims to have 5 ...
*
Smoke detector
*
Fire drill
*
False alarm
*
EN 54 – European Standard for Fire detection
*
Emergency population warning
An emergency population warning, or public warning system is a method where by local, regional, or national authorities can contact or notify members of the public to warn them of an impending emergency. These warnings may be necessary for a numbe ...
- a way to warn people through audible and visual devices when people are in harm's way.