A residual-current device (RCD), residual-current circuit breaker (RCCB) or ground fault circuit interrupter (GFCI) is an electrical safety device that quickly breaks an
electrical circuit
An electrical network is an interconnection of electrical components (e.g., batteries, resistors, inductors, capacitors, switches, transistors) or a model of such an interconnection, consisting of electrical elements (e.g., voltage sources, ...
with
leakage current
In electronics, leakage is the gradual transfer of electrical energy across a boundary normally viewed as insulating, such as the spontaneous discharge of a charged capacitor, magnetic coupling of a transformer with other components, or flow of cu ...
to
ground. It is to protect equipment and to reduce the risk of serious harm from an ongoing
electric shock
Electrical injury is a physiological reaction caused by electric current passing through the body. The injury depends on the density of the current, tissue resistance and duration of contact. Very small currents may be imperceptible or produce ...
. Injury may still occur in some cases, for example if a human receives a brief shock before the electrical circuit is isolated, falls after receiving a shock, or if the person touches both conductors at the same time.
If the RCD device has additional
overcurrent protection
Power system protection is a branch of electrical power engineering that deals with the protection of electrical power systems from faults through the disconnection of faulted parts from the rest of the electrical network. The objective of a prot ...
integrated in the same device, it is referred to as
RCBO. An earth leakage circuit breaker may be a RCD, although an older type of voltage-operated
earth leakage circuit breaker
An earth-leakage circuit breaker (ELCB) is a safety device used in electrical installations with high Earth impedance to prevent shock. It detects small stray voltages on the metal enclosures of electrical equipment, and interrupts the circui ...
(ELCB) also exists.
These electrical wiring devices are designed to quickly and automatically isolate a circuit when it detects that the
electric current
An electric current is a stream of charged particles, such as electrons or ions, moving through an electrical conductor or space. It is measured as the net rate of flow of electric charge through a surface or into a control volume. The moving pa ...
is unbalanced between the supply and return conductors of a circuit. Any difference between the currents in these conductors indicates
leakage current
In electronics, leakage is the gradual transfer of electrical energy across a boundary normally viewed as insulating, such as the spontaneous discharge of a charged capacitor, magnetic coupling of a transformer with other components, or flow of cu ...
, which presents a shock hazard. Alternating 60 Hz current above 20
mA (0.020 amperes) through the human body is potentially sufficient to cause
cardiac arrest
Cardiac arrest is when the heart suddenly and unexpectedly stops beating. It is a medical emergency that, without immediate medical intervention, will result in sudden cardiac death within minutes. Cardiopulmonary resuscitation (CPR) and possib ...
or serious harm if it persists for more than a small fraction of a second. RCDs are designed to disconnect the conducting wires ("trip") quickly enough to potentially prevent serious injury to humans, and to prevent damage to electrical devices.
RCDs are testable and resettable devices—a test button safely creates a small leakage condition, and another button resets the conductors after a fault condition has been cleared. Some RCDs disconnect both the energized and return conductors upon a fault (double pole), while a single pole RCD only disconnects the energized conductor. If the fault has left the return wire "
floating" or not at its expected
ground potential
In an electrical system, a ground loop or earth loop occurs when two points of a circuit are intended to have the same ground reference potential but instead have a different potential between them. This is typically caused when enough curren ...
for any reason, then a single-pole RCD will leave this conductor still connected to the circuit when it detects the fault.
File:Residual current device 2pole.jpg, A two-pole, or double-pole, residual-current device. The test button and connect/disconnect switch are colored blue. A fault will trigger the switch to its down (off) position, which in this device would disconnect both conductors.
File:IEC TS 60479-1 electric shock graph.svg, Log-log graph of the effect of alternating current ''I'' of duration ''T'' passing from left hand to feet as defined in IEC
The International Electrotechnical Commission (IEC; in French: ''Commission électrotechnique internationale'') is an international standards organization that prepares and publishes international standards for all electrical, electronic and r ...
60479-1.
File:FISkizze.svg, 1: Electromagnet with help electronics
2: Current transformer secondary winding
3: Transformer core
4: Test push-button
L: Line conductor
N: Neutral conductor
Purpose and operation
RCDs are designed to disconnect the circuit if there is a leakage current.
In their first implementation in the 1950s, power companies used them to prevent electricity theft where consumers grounded returning circuits rather than connecting them to neutral to inhibit electrical meters from registering their power consumption.
The most common modern application is as a safety device to detect small leakage currents (typically 5–30mA) and disconnecting quickly enough (<30 milliseconds) to prevent device damage or
electrocution
Electrocution is death or severe injury caused by electric shock from electric current passing through the body. The word is derived from "electro" and "execution", but it is also used for accidental death.
The term "electrocution" was coined ...
.
They are an essential part of the automatic disconnection of supply (ADS), i.e. to switch off when a fault develops, rather than rely on human intervention, one of the essential tenets of modern electrical practice.
To reduce the risk of electrocution, RCDs should operate within 25–40 milliseconds with any leakage currents (through a person) of greater than 30mA, before electric shock can drive the heart into
ventricular fibrillation
Ventricular fibrillation (V-fib or VF) is an abnormal heart rhythm in which the ventricles of the heart quiver. It is due to disorganized electrical activity. Ventricular fibrillation results in cardiac arrest with loss of consciousness and no p ...
, the most common cause of death through electric shock. By contrast, conventional circuit breakers or
fuses
Fuse or FUSE may refer to:
Devices
* Fuse (electrical), a device used in electrical systems to protect against excessive current
** Fuse (automotive), a class of fuses for vehicles
* Fuse (hydraulic), a device used in hydraulic systems to protec ...
only break the circuit when the total current is excessive (which may be thousands of times the leakage current an RCD responds to). A small leakage current, such as through a person, can be a very serious fault, but would probably not increase the total current enough for a fuse or overload circuit breaker to isolate the circuit, and not fast enough to save a life.
RCDs operate by measuring the current balance between two conductors using a differential
current transformer
A current transformer (CT) is a type of transformer that is used to reduce or multiply an alternating current (AC). It produces a current in its secondary which is proportional to the current in its primary.
Current transformers, along with volt ...
. This measures the difference between current flowing through the
live conductor and that returning through the
neutral conductor. If these do not sum to zero, there is a leakage of current to somewhere else (to earth/ground or to another circuit), and the device will open its contacts. Operation does not require a fault current to return through the
earth wire
In electrical engineering, ground or earth is a reference point in an electrical circuit from which voltages are measured, a common return path for electric current, or a direct physical connection to the Earth.
Electrical circuits may be connec ...
in the installation; the trip will operate just as well if the return path is through plumbing, contact with the ground or any other current path. Automatic disconnection and a measure of shock protection is therefore still provided even if the earth wiring of the installation is damaged or incomplete.
For an RCD used with
three-phase power
Three-phase electric power (abbreviated 3φ) is a common type of alternating current used in electricity generation, transmission, and distribution. It is a type of polyphase system employing three wires (or four including an optional neutral r ...
, all three live conductors and the neutral (if fitted) must pass through the current transformer.
Application
Electrical plugs with incorporated RCD are sometimes installed on appliances that might be considered to pose a particular safety hazard, for example long extension leads, which might be used outdoors, or garden equipment or hair dryers, which may be used near a bath or sink. Occasionally an in-line RCD may be used to serve a similar function to one in a plug. By putting the RCD in the extension lead, protection is provided at whatever outlet is used even if the building has old wiring, such as
knob and tube, or wiring that does not contain a grounding conductor. The in-line RCD can also have a lower tripping threshold than the building to further improve safety for a specific electrical device.
In North America, GFI receptacles can be used in cases where there is no grounding conductor, but they must be labeled as "no equipment ground". This is referenced in the National Electric Code section 406 (D) 2, however codes change and someone should always consult a licensed professional and their local building and safety departments. The code is An ungrounded GFI receptacle will trip using the built-in "test" button, but will not trip using a GFI test plug, because the plug tests by passing a small current from line to the non-existent ground. It is worth noting that despite this, only one GFCI receptacle at the beginning of each circuit is necessary to protect downstream receptacles. There does not appear to be a risk of using multiple GFI receptacles on the same circuit, though it is considered redundant.
In Europe, RCDs can fit on the same
DIN rail
A DIN rail is a metal rail of a standard type widely used for mounting circuit breakers and industrial control equipment inside equipment racks. These products are typically made from cold rolled carbon steel sheet with a zinc-plated or chroma ...
as the
miniature circuit breaker
A circuit breaker is an electrical safety device designed to protect an electrical circuit from damage caused by an overcurrent or short circuit. Its basic function is to interrupt current flow to protect equipment and to prevent the risk ...
s; much like in miniature circuit breakers, the busbar arrangements in
consumer unit
A consumer unit is a type of distribution board (a component of an electrical power system within which an electrical power feed provides supply to subsidiary circuits).
UK
The IET defines a consumer unit, also known as a consumer control ...
s and
distribution board
A distribution board (also known as panelboard, breaker panel, electric panel, DB board or DB box) is a component of an electricity supply system that divides an electrical power feed into subsidiary circuits while providing a protective fuse ...
s provides protection for anything downstream.
RCBO
A pure RCD will detect imbalance in the currents of the supply and return conductors of a circuit. But it cannot protect against overload or
short circuit
A short circuit (sometimes abbreviated to short or s/c) is an electrical circuit that allows a current to travel along an unintended path with no or very low electrical impedance. This results in an excessive current flowing through the circuit ...
like a fuse or a miniature circuit breaker (MCB) does (except for the special case of a short circuit from live to ground, not live to neutral).
However, a RCD and a MCB often come integrated in the same device, thus being able to detect both supply imbalance and overload current. Such a device is called
* RCBO (for residual-current circuit breaker with overcurrent protection) in Europe and Australia;
* GFCI breaker (for ground fault circuit interrupter) in USA and Canada;
Typical design
The diagram depicts the internal mechanism of a residual-current device (RCD). The device is designed to be wired in-line in an appliance power cord. It is rated to carry a maximal current of 13A and is designed to trip on a leakage current of 30mA. This is an active RCD; that is, it latches electrically and therefore trips on power failure, a useful feature for equipment that
could be dangerous on unexpected re-energisation. Some early RCDs were entirely electromechanical and relied on finely balanced sprung over-centre mechanisms driven directly from the current transformer. As these are hard to manufacture to the required accuracy and prone to drift in sensitivity both from pivot wear and lubricant dry-out, the electronically-amplified type with a more robust
solenoid
upright=1.20, An illustration of a solenoid
upright=1.20, Magnetic field created by a seven-loop solenoid (cross-sectional view) described using field lines
A solenoid () is a type of electromagnet formed by a helix, helical coil of wire whose ...
part as illustrated are now dominant.
In the internal mechanism of an RCD, the incoming supply and the neutral conductors are connected to the terminals at (1), and the outgoing load conductors are connected to the terminals at (2). The earth conductor (not shown) is connected through from supply to load uninterrupted.
When the reset button (3) is pressed, the
contacts
Contact lenses, or simply contacts, are thin lenses placed directly on the surface of the eyes. Contact lenses are ocular prosthetic devices used by over 150 million people worldwide, and they can be worn to correct vision or for cosmetic ...
((4) and another, hidden behind (5)) close, allowing current to pass. The solenoid (5) keeps the contacts closed when the reset button is released.
The sense coil (6) is a
differential current transformer which surrounds (but is not electrically connected to) the live and neutral conductors. In normal operation, all the current down the live conductor returns up the neutral conductor. The currents in the two conductors are therefore equal and opposite and cancel each other out.
Any fault to earth (for example caused by a person touching a live component in the attached appliance) causes some of the current to take a different return path, which means that there is an imbalance (difference) in the current in the two conductors (single-phase case), or, more generally, a nonzero sum of currents from among various conductors (for example, three phase conductors and one neutral conductor).
This difference causes a current in the sense coil (6), which is picked up by the sense circuitry (7). The sense circuitry then removes power from the solenoid (5), and the contacts (4) are forced apart by a spring, cutting off the electricity supply to the appliance. A power failure will also remove power from the solenoid and cause the contacts to open, causing the safe trip-on-power-failure behaviour mentioned above.
The test button (8) allows the correct operation of the device to be verified by passing a small current through the orange test wire (9). This simulates a fault by creating an imbalance in the sense coil. If the RCD does not trip when this button is pressed, then the device must be replaced.
RCD with additional overcurrent protection circuitry (RCBO or GFCI breaker)
Residual-current and over-current protection may be combined in one device for installation into the service panel; this device is known as a GFCI (Ground-Fault Circuit Interrupter) breaker in the US and Canada, and as a RCBO (residual-current circuit breaker with over-current protection) in Europe and Australia. They are effectively a combination of a RCD and a MCB. In the US, GFCI breakers are more expensive than GFCI outlets.
As well as requiring both live and neutral inputs and outputs (or, full three-phase), many GFCI/RCBO devices require a functional earth (FE) connection. This serves to provide both EMC immunity and to reliably operate the device if the input-side neutral connection is lost but live and earth remain.
For reasons of space, many devices, especially in DIN rail format, use flying leads rather than screw terminals, especially for the neutral input and FE connections. Additionally, because of the small form factor, the output cables of some models (Eaton/MEM) are used to form the primary winding of the RCD part, and the outgoing circuit cables must be led through a specially dimensioned terminal tunnel with the current transformer part around it. This can lead to incorrect failed trip results when testing with meter probes from the screw heads of the terminals, rather than from the final circuit wiring.
Having one RCD feeding another is generally unnecessary, provided they have been wired properly. One exception is the case of a
TT earthing system
An earthing system (UK and IEC) or grounding system (US) connects specific parts of an electric power system with the ground, typically the Earth's conductive surface, for safety and functional purposes. The choice of earthing system can affect ...
, where the
earth loop impedance
In an electrical system, a ground loop or earth loop occurs when two points of a circuit are intended to have the same ground reference potential but instead have a different potential between them. This is typically caused when enough current ...
may be high, meaning that a ground fault might not cause sufficient current to trip an ordinary circuit breaker or fuse. In this case a special 100mA (or greater) trip current time-delayed RCD is installed, covering the whole installation, and then more sensitive RCDs should be installed downstream of it for sockets and other circuits that are considered high-risk.
RCD with additional arc fault protection circuitry
In addition to ground fault circuit interrupters (GFCIs),
arc-fault circuit interrupters (AFCI) are equally important as they offer added protection from potentially hazardous
arc-faults resulting from damage in branch circuit wiring as well as extensions to branches such as appliances and cord sets. By detecting hazardous arc-faults and responding by interrupting power, AFCIs helps reduce the likelihood of the home's electrical system being an ignition source of a fire. Dual function AFCI/GFCI devices offer both electrical fire prevention and shock prevention in one device making them a solution for many rooms in the home, especially when replacing an existing standard receptacle or existing ungrounded receptacle.
Common features and variations
Differences in disconnection actions
Major differences exist regarding the manner in which an RCD-unit will act to disconnect the power to a circuit or appliance.
There are four situations in which different types of RCD-units are used:
# At the consumer power distribution level, usually in conjunction with an RCBO resettable circuit breaker;
# Built into a wall socket;
# Plugged into a wall socket, which may be part of a power-extension cable; and
# Built into the cord of a portable appliance, such as those intended to be used in outdoor or wet areas.
The first three of those situations, relate largely to usage as part of a power-distribution system and are almost always of the 'passive' or 'latched' variety, whereas the fourth relates solely to specific appliances and are always of the 'active' or 'non-latching' variety. 'Active' means prevention of any 're-activation' of the power supply after any inadvertent form of power outage, as soon as the mains supply becomes re-established; 'latch' relates to a 'switch' inside the unit housing the RCD that remains as set following any form of power outage, but has to be reset manually after the detection of an error-condition.
In the fourth situation, it would be deemed to be highly undesirable, and probably very unsafe, for a connected appliance to automatically resume operation after a power disconnection, without having the operator in attendance – as such manual reactivation of the RCD is necessary.
The difference between the modes of operation of the essentially two different types of RCD functionality is that the operation for power distribution purposes requires the internal latch to remain set within the RCD after any form of power disconnection caused by either the user turning the power off, or after any power outage; such arrangements are particularly applicable for connections to refrigerators and freezers.
Situation two is mostly installed just as described above, but some wall socket RCDs are available to fit the fourth situation, often by operating a switch on the fascia panel.
RCDs for the first and third situation are most commonly rated at 30mA and 40ms. For the fourth situation, there is generally a greater choice of ratings available – generally all lower than the other forms, but lower values often result in more nuisance tripping. Sometimes users apply protection in addition to one of the other forms, when they wish to override those with a lower rating. It may be wise to have a selection of type 4 RCDs available, because connections made under damp conditions or using lengthy power cables are more prone to trip-out when any of the lower ratings of RCD are used; ratings as low as 10mA are available.
Number of poles and pole terminology
The number of poles represents the number of conductors that are interrupted when a fault condition occurs. RCDs used on single-phase AC supplies (two current paths), such as domestic power, are usually one- or two-pole designs, also known as
single- and
double-pole. A single-pole RCD interrupts only the energized conductor, while a double-pole RCD interrupts both the energized and return conductors. (In a single-pole RCD, the return conductor is usually anticipated to be at
ground potential
In an electrical system, a ground loop or earth loop occurs when two points of a circuit are intended to have the same ground reference potential but instead have a different potential between them. This is typically caused when enough curren ...
at all times and therefore safe on its own).
RCDs with three or more poles can be used on three-phase AC supplies (three current paths) or to disconnect an earth conductor as well, with four-pole RCDs used to interrupt three-phase and neutral supplies. Specially designed RCDs can also be used with both AC and DC power distribution systems.
The following terms are sometimes used to describe the manner in which conductors are connected and disconnected by an RCD:
:* Single-pole or one-pole – the RCD will disconnect the energized wire only.
:* Double-pole or two-pole – the RCD will disconnect both the energized and return wires.
:* 1+N and 1P+N – non-standard terms used in the context of RCBOs, at times used differently by different manufacturers. Typically these terms may signify that the return (neutral) conductor is an isolating pole only, without a protective element (an unprotected but switched neutral), that the RCBO provides a conducting path and connectors for the return (neutral) conductor but this path remains uninterrupted when a fault occurs (sometimes known as "solid neutral"), or that both conductors are disconnected for some faults (such as RCD detected leakage) but only one conductor is disconnected for other faults (such as overload).
Sensitivity
RCD sensitivity is expressed as the rated residual operating current, noted ''I
Δn''. Preferred values have been defined by the IEC, thus making it possible to divide RCDs into three groups according to their ''I
Δn'' value:
* high sensitivity (HS): 5** – 10 – 30mA (for direct-contact or life injury protection),
* medium sensitivity (MS): 100 – 300 – 500 – 1000mA (for fire protection),
* low sensitivity (LS): 3 – 10 – 30A (typically for protection of machine).
The 5mA sensitivity is typical for GFCI outlets.
Break time (response speed)
There are two groups of devices. ''G'' (general use) ''instantaneous'' RCDs have no intentional time delay. They must never trip at one-half of the nominal current rating, but must trip within 200 milliseconds for rated current, and within 40 milliseconds at five times rated current. ''S'' (selective) or ''T'' (time-delayed) RCDs have a short time delay. They are typically used at the origin of an installation for fire protection to discriminate with ''G'' devices at the loads, and in circuits containing surge suppressors. They must not trip at one-half of rated current. They provide at least 130 milliseconds delay of tripping at rated current, 60 milliseconds at twice rated, and 50 milliseconds at five times rated. The maximum break time is 500ms at rated current, 200ms at twice rated, and 150ms at five times rated.
Programmable earth fault relays are available to allow co-ordinated installations to minimise outage. For example, a power distribution system might have a 300mA, 300ms device at the service entry of a building, feeding several 100mA ''S'' type at each sub-board, and 30mA ''G'' type for each final circuit. In this way, a failure of a device to detect the fault will eventually be cleared by a higher-level device, at the cost of interrupting more circuits.
Type (types of leakage current detected)
IEC Standard 60755 (''General requirements for residual current operated protective devices'') defines three types of RCD depending on the waveforms and frequency of the fault current.
* Type AC RCDs trip on sinusoidal residual current.
* Type A RCDs, in addition to Type AC, also respond to pulsating or continuous direct current of either polarity.
* Type B RCDs, in addition to Type A, also respond to steady DC, and higher frequency current, or for combinations of alternating and direct current as may be found from single-phase or multi-phase rectifying circuits, like all the switching power supplies used at home, or for example washing machines etc., equipped with DC motors.
The BEAMA RCD Handbook - Guide to the Selection and Application of RCDs summaries this as follows:
* Type AC RCDs trip on alternating sinusoidal residual current, suddenly applied or smoothly increasing.
* Type A RCDs trip on alternating sinusoidal residual current and on residual pulsating direct current, suddenly applied or smoothly increasing.
* Type F RCDs trip in the same conditions as Type A and in addition:
** for composite residual currents, whether suddenly applied or slowly rising intended for circuit supplied between phase and neutral or phase and earthed middle conductor;
** for residual pulsating direct currents superimposed on smooth direct current.
* Type B RCDs trip in the same conditions as Type F and in addition:
** for residual sinusoidal alternating currents up to 1kHz;
** for residual alternating currents superimposed on a smooth direct current;
** for residual pulsating direct currents superimposed on a smooth direct current;
** for residual pulsating rectified direct current which results from two or more phases;
** for residual smooth direct currents whether suddenly applied or slowly increased independent of polarity.
and notes that these designations have been introduced because some designs of type A and AC RCD can be disabled if a DC current is present that saturates the core of the detector.
Surge current resistance
The surge current refers to the peak current an RCD is designed to withstand using a test impulse of specified characteristics. The IEC 61008 and IEC 61009 standards require that RCDs withstand a 200A "ring wave" impulse. The standards also require RCDs classified as "selective" to withstand a 3000A impulse surge current of specified waveform.
Testing of correct operation
RCDs can be tested with a built-in test button to confirm functionality on a regular basis. RCDs may not operate correctly if wired improperly, so they are generally tested by the installer. By introducing a controlled fault current from live to earth, the operating time and wiring can be tested. Such a test may be performed on installation of the device and at any "downstream" outlet. (Upstream outlets are ''not'' protected.) To avoid needless tripping, only one RCD should be installed on any single circuit (excluding corded RCDs, such as bathroom small appliances).
Limitations
A residual-current circuit breaker cannot remove all risk of electric shock or fire. In particular, an RCD alone will not detect overload conditions, phase-to-neutral short circuits or phase-to-phase short circuits (see
three-phase electric power
Three-phase electric power (abbreviated 3φ) is a common type of alternating current used in electricity generation, transmission, and distribution. It is a type of polyphase system employing three wires (or four including an optional neutral ...
). Over-current protection (
fuse
Fuse or FUSE may refer to:
Devices
* Fuse (electrical), a device used in electrical systems to protect against excessive current
** Fuse (automotive), a class of fuses for vehicles
* Fuse (hydraulic), a device used in hydraulic systems to protect ...
s or
circuit breaker
A circuit breaker is an electrical safety device designed to protect an electrical circuit from damage caused by an overcurrent or short circuit. Its basic function is to interrupt current flow to protect equipment and to prevent the risk ...
s) must be provided. Circuit breakers that combine the functions of an RCD with overcurrent protection respond to both types of fault. These are known as RCBOs and are available in 2-, 3- and 4-pole configurations. RCBOs will typically have separate circuits for detecting current imbalance and for overload current but use a common interrupting mechanism.
An RCD helps to protect against electric shock when current flows through a person from a phase (live / line / hot) to earth. It cannot protect against electric shock when current flows through a person from phase to neutral or from phase to phase, for example where a finger touches both live and neutral contacts in a light fitting; a device cannot differentiate between current flow through an intended load from flow through a person, though the RCD may still trip if the person is in contact with the ground (earth), as some current may still pass through the persons finger and body to earth.
Whole installations on a single RCD, common in older installations in the UK, are prone to "nuisance" trips that can cause secondary safety problems with loss of lighting and defrosting of food. Frequently the trips are caused by deteriorating insulation on heater elements, such as water heaters and cooker elements or rings. Although regarded as a nuisance, the fault is with the deteriorated element and not the RCD: replacement of the offending element will resolve the problem, but replacing the RCD will not.
In the case of RCDs that need a power supply, a dangerous condition can arise if the neutral wire is broken or switched off on the supply side of the RCD, while the corresponding live wire remains uninterrupted. The tripping circuit needs power to work and does not trip when the power supply fails. Connected equipment will not work without a neutral, but the RCD cannot protect people from contact with the energized wire. For this reason circuit breakers must be installed in a way that ensures that the neutral wire cannot be switched off unless the live wire is also switched off at the same time. Where there is a requirement for switching off the neutral wire, two-pole breakers (or four-pole for 3-phase) must be used. To provide some protection with an interrupted neutral, some RCDs and RCBOs are equipped with an auxiliary connection wire that must be connected to the earth busbar of the distribution board. This either enables the device to detect the missing neutral of the supply, causing the device to trip, or provides an alternative supply path for the tripping circuitry, enabling it to continue to function normally in the absence of the supply neutral.
Related to this, a single-pole RCD/RCBO interrupts the energized conductor only, while a double-pole device interrupts both the energized and return conductors. Usually this is a standard and safe practice, since the return conductor is held at ground potential anyway. However, because of its design, a single-pole RCD will not isolate or disconnect all relevant wires in certain uncommon situations, for example where the return conductor is not being held, as expected, at ground potential, or where current leakage occurs between the return and earth conductors. In these cases, a double-pole RCD will offer protection, since the return conductor would also be disconnected.
History and nomenclature
The world's first high-sensitivity earth leakage protection system (i.e. a system capable of protecting people from the hazards of direct contact between a live conductor and earth), was a second-harmonic magnetic amplifier core-balance system, known as the magamp, developed in
South Africa
South Africa, officially the Republic of South Africa (RSA), is the southernmost country in Africa. It is bounded to the south by of coastline that stretch along the South Atlantic and Indian Oceans; to the north by the neighbouring countri ...
by
Henri Rubin
Henri is an Estonian, Finnish, French, German and Luxembourgish form of the masculine given name Henry.
People with this given name
; French noblemen
:'' See the 'List of rulers named Henry' for Kings of France named Henri.''
* Henri I de Montm ...
. Electrical hazards were of great concern in South African
gold mine Gold Mine may refer to:
*Gold Mine (board game)
*Gold Mine (Long Beach), an arena
*"Gold Mine", a song by Joyner Lucas from the 2020 album '' ADHD''
See also
* ''Gold'' (1974 film), based on the novel ''Gold Mine'' by Wilbur Smith
*Gold mining
...
s, and Rubin, an engineer at the company C.J. Fuchs Electrical Industries of Alberton Johannesburg, initially developed a cold-cathode system in 1955 which operated at 525V and had a tripping sensitivity of 250mA. Prior to this, core balance earth leakage protection systems operated at sensitivities of about 10A.
The cold cathode system was installed in a number of gold mines and worked reliably. However, Rubin began working on a completely novel system with greatly improved sensitivity, and by early 1956, he had produced a prototype second-harmonic magnetic amplifier-type core balance system (South African Patent No. 2268/56 and Australian Patent No. 218360). The prototype magamp was rated at 220V, 60A and had an internally adjustable tripping sensitivity of 12.5–17.5mA. Very rapid tripping times were achieved through a novel design, and this combined with the high sensitivity was well within the safe current-time envelope for ventricular fibrillation determined by
Charles Dalziel Charles Dalziel (1904–1986) was a professor of electrical engineering and computer sciences
at UC Berkeley. According to volume 54 of UCB's Blue and Gold, Dalziel graduated with a Mechanics degree in 1927 and was from Santa Maria, CA. He was a mem ...
of the
University of California, Berkeley
The University of California, Berkeley (UC Berkeley, Berkeley, Cal, or California) is a public land-grant research university in Berkeley, California. Established in 1868 as the University of California, it is the state's first land-grant u ...
, USA, who had estimated electrical shock hazards in humans. This system, with its associated circuit breaker, included overcurrent and short-circuit protection. In addition, the original prototype was able to trip at a lower sensitivity in the presence of an interrupted neutral, thus protecting against an important cause of electrical fire.
Following the accidental electrocution of a woman in a domestic accident at the Stilfontein gold mining village near
Johannesburg
Johannesburg ( , , ; Zulu and xh, eGoli ), colloquially known as Jozi, Joburg, or "The City of Gold", is the largest city in South Africa, classified as a megacity, and is one of the 100 largest urban areas in the world. According to Demo ...
, a few hundred F.W.J. 20mA magamp earth leakage protection units were installed in the homes of the mining village during 1957 and 1958. F.W.J. Electrical Industries, which later changed its name to FW Electrical Industries, continued to manufacture 20mA single phase and three phase magamp units.
At the time that he worked on the magamp, Rubin also considered using
transistor
upright=1.4, gate (G), body (B), source (S) and drain (D) terminals. The gate is separated from the body by an insulating layer (pink).
A transistor is a semiconductor device used to Electronic amplifier, amplify or electronic switch, switch e ...
s in this application, but concluded that the early transistors then available were too unreliable. However, with the advent of improved transistors, the company that he worked for and other companies later produced transistorized versions of earth leakage protection.
In 1961, Dalziel, working with Rucker Manufacturing Co., developed a transistorized device for earth leakage protection which became known as a Ground Fault Circuit Interrupter (GFCI), sometimes colloquially shortened to Ground Fault Interrupter (GFI). This name for high-sensitivity earth leakage protection is still in common use in the U.S.A.
In the early 1970s most North American GFCI devices were of the circuit breaker type. GFCIs built into the outlet receptacle became commonplace beginning in the 1980s. The circuit breaker type, installed into a
distribution panel, suffered from accidental trips mainly caused by poor or inconsistent insulation on the wiring. False trips were frequent when insulation problems were compounded by long circuit lengths. So much current leaked along the length of the conductors' insulation that the breaker might trip with the slightest increase of current imbalance. The migration to outlet receptacle based protection in North American installations reduced the accidental trips and provided obvious verification that wet areas were under
electrical code {{Electrical Wiring Sidebar
An electrical code is a set of regulations for the design and installation of electrical wiring in a building.
The intention of a code is to provide standards to ensure electrical wiring systems that are safe for people ...
-required protection. European installations continue to use primarily RCDs installed at the distribution board, which provides protection in case of damage to fixed wiring; In Europe socket-based RCDs are primarily used for retrofitting.
Regulation and adoption
Regulations differ widely from country to country. A single RCD installed for an entire electrical installation provides protection against shock hazards to all circuits, however, any fault may cut all power to the premises. A solution is to create groups of circuits each with a RCD, or to use RCBO for each individual circuit.
Australia
In Australia, residual current devices have been mandatory on power circuits since 1991 and on light circuits since 2000.
A minimum of two RCDs is required per domestic installation. All socket outlets and lighting circuits are to be distributed over circuit RCDs. A maximum of three subcircuits only, may be connected to a single RCD.
Austria
Austria regulated residual current devices in the ÖVE E8001-1/A1:2013-11-01 norm (most recent revision). It has been required in private housing since 1980. The maximum activation time must not exceed 0.4 seconds. It needs to be installed on all circuits with power plugs with a maximum leakage current of 30mA and a maximum rated current of 16A.
Additional requirements are placed on circuits in wet areas, construction sites and commercial buildings.
Belgium
Belgian domestic installations are required to be equipped with a 300mA residual current device that protects all circuits. Furthermore, at least one 30mA residual current device is required that protects all circuits in "wet rooms" (e.g. bathroom, kitchen) as well as circuits that power certain "wet" appliances (washing machine, tumble dryer, dishwasher). Electrical underfloor heating is required to be protected by a 100mA RCD. These RCDs must be of type A.
Brazil
Since NBR 5410 (1997) residual current devices and grounding are required for new construction or repair in wet areas, outdoor areas, interior outlets used for external appliances, or in areas where water is more probable like bathrooms and kitchens.
Denmark
Denmark requires 30mA RCDs on all circuits that are rated for less than 20 A (circuits at greater rating are mostly used for distribution). RCDs became mandatory in 1975 for new buildings, and then for all buildings in 2008.
France
According to the NF C15-100 regulation (1911 -> 2002), a general RCD not exceeding 100 to 300mA at the origin of the installation is mandatory. Moreover, in rooms where there is water, high power or sensitive equipment (bathrooms, kitchens, IT...), each socket outlet must be protected by an RCD not exceeding 30mA. The type of RCD required (A, AC, F) depends upon the type of the equipment that will be connected and the maximum power of the socket outlet. Minimal distances between electrical devices and water or the floor are described and mandatory.
Germany
Since 1 May 1984, RCDs are mandatory for all rooms with a bath tub or a shower. Since June 2007 Germany requires the use of RCDs with a trip current of no more than 30mA on sockets rated up to 32A which are for general use. (
DIN VDE 0100-410 Nr. 411.3.3).
It isn't allowed to use type "AC" RCDs since 1987, to be used to protect humans against electrical shocks.
It must be Type "A" or type "B".
India
According to Regulation 36 of the Electricity Regulations 1990
a) For a place of public entertainment, protection against earth leakage current must be provided by a residual current device of sensitivity not exceeding 10mA.
b) For a place where the floor is likely to be wet or where the wall or enclosure is of low electrical resistance, protection against earth leakage current must be provided by a residual current device of sensitivity not exceeding 10mA.
c) For an installation where hand-held equipment, apparatus or appliance is likely to be used, protection against earth leakage current must be provided by a residual current device of sensitivity not exceeding 30mA.
d) For an installation other than the installation in (a), (b) and (c), protection against earth leakage current must be provided by a residual current device of sensitivity not exceeding 100mA.
Italy
The Italian law (n. 46 March 1990) prescribes RCDs with no more than 30mA residual current (informally called "salvavita"—life saver, after early
BTicino
BTicino S.p.A. () is an Italian metalworking company that operates in the field of electrical low voltage equipment used for residential, employment and production. Bticino proposes solutions for the energy distribution, for the communication (i ...
models, or differential circuit breaker for the mode of operation) for all domestic installations to protect all the lines. The law was recently updated to mandate at least two separate RCDs for separate domestic circuits. Short-circuit and overload protection has been compulsory since 1968.
Malaysia
In the latest guidelines for electrical wiring in residential buildings (2008) handbook, the overall residential wiring need to be protected by a residual current device of sensitivity not exceeding 100mA. Additionally, all power sockets need to be protected by a residual current device of sensitivity not exceeding 30mA and all equipment in wet places (water heater, water pump) need to be protected by a residual current device of sensitivity not exceeding 10mA.
New Zealand
From January 2003, all new circuits originating at the switchboard supplying lighting or socket outlets (power points) in domestic buildings must have RCD protection. Residential facilities (such as boarding houses, hospitals, hotels and motels) will also require RCD protection for all new circuits originating at the switchboard supplying socket outlets. These RCDs will normally be located at the switchboard. They will provide protection for all electrical wiring and appliances plugged into the new circuits.
[''Residual current devices - ACC'']
by Ministry of Consumer Affairs’ Energy Safety Service
(''ACC Website'', December 2002 )
North America
In North America socket-outlets located in places where an easy path to ground exists—such as wet areas and rooms with uncovered concrete floors—must be protected by a GFCI. The US ''National Electrical Code'' has required devices in certain locations to be protected by GFCIs since the 1960s. Beginning with underwater swimming pool lights (1968) successive editions of the code have expanded the areas where GFCIs are required to include: construction sites (1974), bathrooms and outdoor areas (1975), garages (1978), areas near hot tubs or spas (1981), hotel bathrooms (1984), kitchen counter sockets (1987), crawl spaces and unfinished basements (1990), near wet bar sinks (1993), near laundry sinks (2005) and in laundry rooms (2014).
GFCIs are commonly available as an integral part of a socket or a circuit breaker installed in the distribution panelboard. GFCI sockets invariably have rectangular faces and accept so-called Decora face plates, and can be mixed with regular outlets or switches in a multi-gang box with standard cover plates. In both Canada and the US older two-wire, ungrounded
NEMA 1
NEMA connectors are power plugs and receptacles used for AC mains electricity in North America and other countries that use the standards set by the US National Electrical Manufacturers Association. NEMA wiring devices are made in current rat ...
sockets may be replaced with
NEMA 5
NEMA connectors are power plugs and receptacles used for AC mains electricity in North America and other countries that use the standards set by the US National Electrical Manufacturers Association. NEMA wiring devices are made in current ra ...
sockets protected by a GFCI (integral with the socket or with the corresponding circuit breaker) in lieu of rewiring the entire circuit with a grounding conductor. In such cases the sockets must be labeled "no equipment ground" and "GFCI protected"; GFCI manufacturers typically provide tags for the appropriate installation description.
GFCIs approved for protection against electric shock trip at 5mA within 25ms. A GFCI device which protects equipment (not people) is allowed to trip as high as 30mA of current; this is known as an Equipment Protective Device (EPD). RCDs with trip currents as high as 500mA are sometimes deployed in environments (such as computing centers) where a lower threshold would carry an unacceptable risk of accidental trips. These high-current RCDs serve for equipment and fire protection instead of protection against the risks of electrical shocks.
In the United States the
American Boat and Yacht Council
The American Boat and Yacht Council is a non-profit organization which sets standards for the safe construction and maintenance of boats in the United States. It is a standards development member of the American National Standards Institute. Founde ...
requires both GFCIs for outlets and Equipment Leakage Circuit Interrupters (ELCI) for the entire boat. The difference is GFCIs trip on 5mA of current whereas ELCIs trip on 30mA after up to 100ms. The greater values are intended to provide protection while minimizing nuisance trips.
Norway
In Norway, it has been required in all new homes since 2002, and on all new sockets since 2006. This applies to 32A sockets and below. The RCD must trigger after a maximum 0.4 seconds for 230V circuits, or 0.2 seconds for 400V circuits.
South Africa
South Africa mandated the use of Earth Leakage Protection devices in residential environments (e.g. houses, flats, hotels, etc.) from October 1974, with regulations being refined in 1975 and 1976.
Devices need to be installed in new premises and when repairs are carried out. Protection is required for power outlets and lighting, with the exception of emergency lighting that should not be interrupted. The standard device used in South Africa is indeed a hybrid of ELPD and RCCB.
Taiwan
Taiwan requires circuits of receptacles in washrooms, balconies, and receptacles in kitchen no more than 1.8 metres from the sink the use of earth leakage circuit breakers. This requirement also apply to circuit of water heater in washrooms and circuits that involves devices in water, lights on metal frames, public drinking fountains and so on. In principle, ELCBs should be installed on branch circuits, with trip current no more than 30mA within 0.1 second according to Taiwanese law.
Turkey
Turkey requires the use of RCDs with no more than 30mA and 300mA in all new homes since 2004. This rule was introduced in RG-16/06/2004-25494.
United Kingdom
The current (18th) edition of the
IEE Electrical Wiring Regulations requires that all socket outlets in most installations have RCD protection, though there are exemptions. Non armoured cables buried in walls must also be RCD protected (again with some specific exemptions). Provision of RCD protection for circuits present in bathrooms and shower rooms reduces the requirement for supplementary bonding in those locations. Two RCDs may be used to cover the installation, with upstairs and downstairs lighting and power circuits spread across both RCDs. When one RCD trips, power is maintained to at least one lighting and power circuit. Other arrangements, such as the use of RCBOs, may be employed to meet the regulations. The new requirements for RCDs do not affect most existing installations unless they are rewired, the distribution board is changed, a new circuit is installed, or alterations are made such as additional socket outlets or new cables buried in walls.
RCDs used for shock protection must be of the 'immediate' operation type (not time-delayed) and must have a residual current sensitivity of no greater than 30mA.
If spurious tripping would cause a greater problem than the risk of the electrical accident the RCD is supposed to prevent (examples might be a supply to a critical factory process, or to life support equipment), RCDs may be omitted, providing affected circuits are clearly labelled and the balance of risks considered; this may include the provision of alternative safety measures.
The previous edition of the regulations required use of RCDs for socket outlets that were liable to be used by outdoor appliances. Normal practice in domestic installations was to use a single RCD to cover all the circuits requiring RCD protection (typically sockets and showers) but to have some circuits (typically lighting) not RCD protected.
This was to avoid a potentially dangerous loss of lighting should the RCD trip. Protection arrangements for other circuits varied. To implement this arrangement it was common to install a
consumer unit
A consumer unit is a type of distribution board (a component of an electrical power system within which an electrical power feed provides supply to subsidiary circuits).
UK
The IET defines a consumer unit, also known as a consumer control ...
incorporating an RCD in what is known as a split load configuration, where one group of circuit breakers is supplied direct from the main switch (or time delay RCD in the case of a
TT earth) and a second group of circuits is supplied via the RCD. This arrangement had the recognised problems that cumulative earth leakage currents from the normal operation of many items of equipment could cause spurious tripping of the RCD, and that tripping of the RCD would disconnect power from all the protected circuits.
See also
*
Domestic AC power plugs and sockets
AC power plugs and sockets connect electric equipment to the alternating current (AC) mains electricity power supply in buildings and at other sites. Electrical plugs and sockets differ from one another in voltage and current rating, shape, si ...
*
Electrical injury
Electrical injury is a physiological reaction caused by electric current passing through the body. The injury depends on the density of the current, tissue resistance and duration of contact. Very small currents may be imperceptible or produce a ...
*
Insulation monitoring device An insulation monitoring device monitors the ungrounded system between an active phase conductor and earth. It is intended to give an alert (light and sound) or disconnect the power supply when the resistance between the two conductors drops below ...
*
Protective relay
In electrical engineering, a protective relay is a relay device designed to trip a circuit breaker when a fault is detected. The first protective relays were electromagnetic devices, relying on coils operating on moving parts to provide detecti ...
*
Arc-fault circuit interrupter
An arc-fault circuit interrupter (AFCI) or arc-fault detection device (AFDD) is a circuit breaker that breaks the circuit when it detects the electric arcs that are a signature of loose connections in home wiring. Loose connections, which can dev ...
*
Isolation transformer
An isolation transformer is a transformer used to transfer electrical power from a source of alternating current (AC) power to some equipment or device while isolating the powered device from the power source, usually for safety reasons or to re ...