A wide area synchronous grid (also called an "interconnection" in
North America
North America is a continent in the Northern Hemisphere, Northern and Western Hemisphere, Western hemispheres. North America is bordered to the north by the Arctic Ocean, to the east by the Atlantic Ocean, to the southeast by South Ameri ...
) is a
three-phase
Three-phase electric power (abbreviated 3ϕ) is a common type of alternating current (AC) used in electricity generation, Electric power transmission, transmission, and Electric power distribution, distribution. It is a type of polyphase system ...
electric
power grid
''Power Grid'' is the English-language version of the second edition of the multiplayer German-style board game ''Funkenschlag'', designed by Friedemann Friese and first released in 2004. ''Power Grid'' was released by Rio Grande Games.
I ...
that has regional scale or greater that operates at a synchronized
utility frequency
The utility frequency, (power) line frequency (American English) or mains frequency (British English) is the nominal frequency of the oscillations of alternating current (AC) in a wide area synchronous grid transmitted from a power station to t ...
and is electrically tied together during normal system conditions. Also known as ''synchronous zones'', the most powerful is the Northern Chinese State Grid with 1,700
gigawatts
The watt (symbol: W) is the unit of power or radiant flux in the International System of Units (SI), equal to 1 joule per second or 1 kg⋅m2⋅s−3. It is used to quantify the rate of energy transfer. The watt is named in honor o ...
(GW) of generation capacity, while the widest region served is that of the
IPS/UPS
The IPS/UPS (), also widely known as the Russian grid is a wide area synchronous transmission grid, the Russian Unified Power System (UPS; ) and the Integrated Power System (IPS; ) portion of the network being the national networks of Azerbaij ...
system serving most countries of the former Soviet Union. Synchronous grids with ample capacity facilitate
electricity trading across wide areas. In the
CESA system in 2008, over 350,000 megawatt hours were sold per day on the
European Energy Exchange
European Energy Exchange (EEX) AG is a central European electric power and related commodities exchange located in Leipzig, Germany. It develops, operates and connects secure, liquid and transparent markets for energy and related products, inc ...
(EEX).
Neighbouring interconnections with the same frequency and standards can be synchronized and directly connected to form a larger interconnection, or they may share power without synchronization via
high-voltage direct current
A high-voltage direct current (HVDC) electric power transmission system uses direct current (DC) for electric power transmission, in contrast with the more common alternating current (AC) transmission systems. Most HVDC links use voltages betwe ...
power transmission lines (DC ties),
solid-state transformers or
variable-frequency transformer
A variable-frequency transformer (VFT) is used to transmit electricity between two ( asynchronous or synchronous) alternating current frequency domains. The VFT is a relatively recent development. Most asynchronous grid inter-ties use high-voltage ...
s (VFTs), which permit a controlled flow of energy while also functionally isolating the independent AC frequencies of each side. Each of the interconnects in North America is synchronized at a nominal 60 Hz, while those of Europe run at 50 Hz.
The benefits of synchronous zones include pooling of generation, resulting in lower generation costs; pooling of load, resulting in significant equalizing effects; common provisioning of reserves, resulting in cheaper primary and secondary reserve power costs; opening of the market, resulting in possibility of long term contracts and short term power exchanges; and mutual assistance in the event of disturbances.
One disadvantage of a wide-area synchronous grid is that problems in one part can have repercussions across the whole grid.
Properties
Wide area synchronous networks improve reliability and permit the pooling of resources. Also, they can level out the load, which reduces the required generating capacity, allow more environmentally-friendly power to be employed; allow more diverse power generation schemes and permit economies of scale.

Wide area synchronous networks cannot be formed if the two networks to be linked are running at different frequencies or have significantly different standards. For example, in Japan, for historical reasons, the northern part of the country operates on 50 Hz, but the southern part uses 60 Hz. That makes it impossible to form a single synchronous network, which was problematic when the
Fukushima Daiichi plant melted down.
Also, even when the networks have compatible standards, failure modes can be problematic. Phase and current limitations can be reached, which can cause widespread outages. The issues are sometimes solved by adding HVDC links within the network to permit greater control during off-nominal events.
As was discovered in the
2000–2001 California electricity crisis, there can be strong incentives among some market traders to create deliberate congestion and poor management of generation capacity on an interconnection network to inflate prices. Increasing transmission capacity and expanding the market by uniting with neighbouring synchronous networks make such manipulations more difficult.
Frequency
In a synchronous grid, all the generators naturally lock together electrically and run at the same
frequency
Frequency is the number of occurrences of a repeating event per unit of time. Frequency is an important parameter used in science and engineering to specify the rate of oscillatory and vibratory phenomena, such as mechanical vibrations, audio ...
, and stay very nearly in phase with each other. For rotating generators, a local
governor
A governor is an politician, administrative leader and head of a polity or Region#Political regions, political region, in some cases, such as governor-general, governors-general, as the head of a state's official representative. Depending on the ...
regulates the driving torque and helps maintain a more or less constant speed as loading changes.
Droop speed control ensures that multiple parallel generators share load changes in proportion to their rating. Generation and consumption must be balanced across the entire grid because energy is consumed as it is produced. Energy is stored in the immediate short term by the rotational kinetic energy of the generators.
Small deviations from the nominal system frequency are very important in regulating individual generators and assessing the equilibrium of the grid as a whole. When the grid is heavily loaded, the frequency slows, and governors adjust their generators so that more power is output (
droop speed control). When the grid is lightly loaded the grid frequency runs above the nominal frequency, and this is taken as an indication by
Automatic Generation Control
In an electric power system, automatic generation control (AGC) is a system for adjusting the power output of multiple generators at different power plants, in response to changes in the load. Since a power grid requires that generation and load ...
systems across the network that generators should reduce their output.
In addition, there's often central control, which can change the parameters of the AGC systems over timescales of a minute or longer to further adjust the regional network flows and the operating frequency of the grid.
Where neighbouring grids, operating at different frequencies, need to be interconnected, a frequency converter is required.
HVDC
A high-voltage direct current (HVDC) electric power transmission system uses direct current (DC) for electric power transmission, in contrast with the more common alternating current (AC) transmission systems. Most HVDC links use voltages betwe ...
interconnector
An interconnector (also known as a DC tie in the USA) is a structure which enables high-voltage DC electricity to flow between electrical grids, connecting separate AC networks, or linking synchronous grids. It may be formed of submarine power ...
s,
solid-state transformers or
variable-frequency transformer
A variable-frequency transformer (VFT) is used to transmit electricity between two ( asynchronous or synchronous) alternating current frequency domains. The VFT is a relatively recent development. Most asynchronous grid inter-ties use high-voltage ...
s links can connect two grids that operate at different frequencies or that are not maintaining synchronism.
Inertia
Inertia in a synchronous grid is stored energy that a grid has available which can provide extra power for up to a few seconds to maintain the grid frequency. Historically, this was provided only by the angular momentum of the generators, and gave the control circuits time to adjust their output to variations in loads, and sudden generator or distribution failures.
Inverters connected to HVDC usually have no inertia, but wind power can provide inertia, and solar and battery systems can provide
synthetic inertia.
Short circuit current
In short circuit situations, it's important for a grid to be able to provide sufficient current to keep the voltage and frequency reasonably stable until circuit breakers can resolve the fault. Many traditional generator systems had wires which could be overloaded for very short periods without damage, but inverters are not as able to deliver multiple times their rated load. The
short circuit ratio can be calculated for each point on the grid, and if it is found to be too low, for steps to be taken to increase it to be above 1, which is considered stable.
Timekeeping
For timekeeping purposes, over the course of a day the operating frequency will be varied so as to balance out deviations and to prevent line-operated clocks from gaining or losing significant time by ensuring there are 4.32 million on 50 Hz, and 5.184 million cycles on 60 Hz systems each day.
This can, rarely, lead to problems. In 2018
Kosovo
Kosovo, officially the Republic of Kosovo, is a landlocked country in Southeast Europe with International recognition of Kosovo, partial diplomatic recognition. It is bordered by Albania to the southwest, Montenegro to the west, Serbia to the ...
used more power than it generated due to a row with
Serbia
, image_flag = Flag of Serbia.svg
, national_motto =
, image_coat = Coat of arms of Serbia.svg
, national_anthem = ()
, image_map =
, map_caption = Location of Serbia (gree ...
, leading to the phase in the whole
synchronous grid of Continental Europe
The Continental Europe Synchronous Area (CESA), formerly known as the UCTE grid, is one of the largest synchronous electrical grids in the world, primarily operating in Europe. It is interconnected as a single phase-locked mains frequency el ...
lagging behind what it should have been. The frequency dropped to 49.996 Hz. Over time, this caused
synchronous electric clocks to become six minutes slow until the disagreement was resolved.
Deployed networks
Historically, on the
North American power transmission grid the Eastern and Western Interconnections were directly connected, and was at the time largest synchronous grid in the world, but this was found to be unstable, and they are now only DC interconnected.
Planned
*
Unified Smart Grid unification of the US interconnections into a single grid with
smart grid
The smart grid is an enhancement of the 20th century electrical grid, using two-way communications and distributed so-called intelligent devices. Two-way flows of electricity and information could improve the delivery network. Research is main ...
features.
*
SuperSmart Grid a similar mega grid proposal linking UCTE, IPS/UPS, and Mediterranean grid.
*
ASEAN Power Grid plan to connect all ASEAN Grids. The first step is connecting all mainland ASEAN countries with Sumatra, Java, and Singapore Grid, then Borneo Island and Philippines.
DC interconnectors
Interconnectors such as
High-voltage direct current
A high-voltage direct current (HVDC) electric power transmission system uses direct current (DC) for electric power transmission, in contrast with the more common alternating current (AC) transmission systems. Most HVDC links use voltages betwe ...
lines,
solid-state transformers or
variable-frequency transformer
A variable-frequency transformer (VFT) is used to transmit electricity between two ( asynchronous or synchronous) alternating current frequency domains. The VFT is a relatively recent development. Most asynchronous grid inter-ties use high-voltage ...
s can be used to connect two alternating current interconnection networks which are not necessarily synchronized with each other. This provides the benefit of interconnection without the need to synchronize an even wider area. For example, compare the wide area synchronous grid map of Europe (in the introduction) with the map of HVDC lines (here to the right). Solid state transformers have larger losses than conventional transformers, but DC lines lack reactive impedance and overall HVDC lines have lower losses sending power over long distances within a synchronous grid, or between them.
Planned non-synchronous connections
The
Tres Amigas SuperStation aims to enable energy transfers and trading between the
Eastern Interconnection
The Eastern Interconnection is one of the two major alternating current, alternating-current (AC) electrical grids in the North American power transmission grid. The other major wide area synchronous grid, interconnection is the Western Inter ...
and
Western Interconnection
The Western Interconnection is a wide area synchronous grid and one of the two major alternating current, alternating current (AC) power grids in the North American power transmission grid. The other major wide area synchronous grid is the East ...
using 30GW
HVDC
A high-voltage direct current (HVDC) electric power transmission system uses direct current (DC) for electric power transmission, in contrast with the more common alternating current (AC) transmission systems. Most HVDC links use voltages betwe ...
Interconnectors.
See also
*
High-voltage direct current
A high-voltage direct current (HVDC) electric power transmission system uses direct current (DC) for electric power transmission, in contrast with the more common alternating current (AC) transmission systems. Most HVDC links use voltages betwe ...
(HVDC)
*
Super grid
A super grid or supergrid is a wide-area transmission grid (electricity), network, generally trans-continental or multinational, that is intended to make possible the trade of high volumes of electricity across great distances. It is sometimes a ...
*
European super grid
*
Microgrid
A microgrid is a local electrical grid with defined electrical boundaries, acting as a single and controllable entity. It is able to operate in grid-connected and off-grid modes.
*
Smart grid
The smart grid is an enhancement of the 20th century electrical grid, using two-way communications and distributed so-called intelligent devices. Two-way flows of electricity and information could improve the delivery network. Research is main ...
*
Unified Smart Grid
*
SuperSmart Grid
*
Tres Amigas SuperStation
References
External links
A Wide Area Synchronized Frequency Measurement System