Stray voltage is the occurrence of
electrical potential between two objects that ideally should not have any voltage difference between them. Small voltages often exist between two
grounded objects in separate locations by the normal
current flow in the power system. Contact voltage is a better defined term when large voltage appear as a result of a fault. Contact voltage on the enclosure of electrical equipment can appear from a
fault in the electrical power system, such as a failure of insulation.
Terminology
The terminology, stray voltage may be used in any case of undesirable elevated electrical potential. More precise terminology gives an indication of the source of the voltage. Neutral to earth voltage (NEV) specifically refers to a difference in potential between a locally grounded object and the grounded return conductor, or
neutral, of an electrical system. The neutral is theoretically at 0 V potential, as any grounded object, but current flows on the neutral back to the source, somewhat elevating the neutral voltage. NEV is the product of current flowing on the neutral and the finite, non-zero
impedance of the neutral conductor between a given point and its source, often a distant
electrical substation. NEV differs from accidentally-energized objects because it is an unavoidable result of normal system operation, not an accident or a fault in materials or design.
Definitions
Official definition (draft)
In 2005, the
Institute of Electrical and Electronics Engineers
The Institute of Electrical and Electronics Engineers (IEEE) is an American 501(c)(3) public charity professional organization for electrical engineering, electronics engineering, and other related disciplines.
The IEEE has a corporate office ...
(IEEE) convened Working Group 1695 in an attempt to lay down definitions and guidelines for mitigating the various phenomena referred to as "stray voltage". The working group attempted to distinguish between the terms ''stray voltage'' and ''contact voltage'' as follows:
*Stray voltage is defined as "A voltage resulting from the normal delivery and/or use of electricity (usually smaller than 10 volts) that may be present between two conductive surfaces that can be simultaneously contacted by members of the general public and/or their animals. Stray voltage is caused by primary and/or secondary return current, and power system induced currents, as these currents flow through the impedance of the intended return pathway, its parallel conductive pathways, and conductive loops in close proximity to the power system. Stray voltage is not related to power system faults, and is generally not considered hazardous."
*Contact voltage is defined as "A voltage resulting from abnormal power system conditions that may be present between two conductive surfaces that can be simultaneously contacted by members of the general public and/or their animals. Contact voltage is caused by power system fault current as it flows through the impedance of available fault current pathways. Contact voltage is not related to normal system operation and can exist at levels that may be hazardous."
Working definition
In spite of the above definitions, the term ''stray voltage'' continues to be used by both utility workers and the general public for ''all'' occurrences of unwanted excess electricity. For example, at the annual "Jodie S. Lane Stray Voltage Detection, Mitigation & Prevention Conference", held at the Con Edison headquarters in New York City in April 2009, the presidents of most major utilities from throughout the United States and Canada continued to use ''stray voltage'' for all occurrences of unwanted excess electricity. The term ''contact voltage'' was used only once, possibly because "contact voltage" is generally the fault of the supply, network, or installation company. Few companies are willing to openly discuss their faults, let alone those that are seen as life-threatening. It would seem that ''stray voltage'' is now the common term for all unwanted voltage leakage because it categorises the fault as part of normal operation and so limits liability.
In New York City, a woman, Jodie S. Lane, was electrocuted in January 2004 by a five-foot by eight-foot metal road utility vault plate that was energized by an "improperly insulated wire." In the coverage of her death and the growing concern regarding the role of public utilities in electrical safety in the urban environment, both the media and the New York State regulatory agency used ''stray voltage'' for neutral-to-earth voltage (NEV), but conceded that the notoriety of the Lane incident had caused ''stray voltage'' to be a term that is well recognized by the public.
The regulator then used ''stray voltage'' to refer to any "voltage conditions on electric facilities that should not ordinarily exist. These conditions may be due to one or more factors, including, but not limited to, damaged cables, deteriorated, frayed or missing insulation, improper maintenance, or improper installation." In the same document, the commission accepted NEV to be a naturally occurring condition.
Since then, the term had at least two very different definitions, which confused utilities, regulators, and the public. The term "stray voltage" is commonly used for all unwanted electrical leakage, by both the general public and many electrical utility professionals. Other more esoteric phenomenon that also result in elevated voltages on normally non-energized surfaces, are also referred to as “stray voltage.” Examples are voltage from
capacitive coupling
Capacitive coupling (electronics), coupling is the transfer of energy within an electrical network or between distant networks by means of displacement current between circuit(s) node (circuits) , nodes, induced by the electric field. This coup ...
, current induced by power lines,
EMF,
lightning
Lightning is a natural phenomenon consisting of electrostatic discharges occurring through the atmosphere between two electrically charged regions. One or both regions are within the atmosphere, with the second region sometimes occurring on ...
,
earth potential rise, and problems stemming from open (disconnected) neutrals.
Causes
Coupled voltages

Ungrounded metal objects close to
electric field
An electric field (sometimes called E-field) is a field (physics), physical field that surrounds electrically charged particles such as electrons. In classical electromagnetism, the electric field of a single charge (or group of charges) descri ...
sources such as neon signs or conductors carrying
alternating current
Alternating current (AC) is an electric current that periodically reverses direction and changes its magnitude continuously with time, in contrast to direct current (DC), which flows only in one direction. Alternating current is the form in w ...
s may have measurable voltage levels caused by
capacitive coupling
Capacitive coupling (electronics), coupling is the transfer of energy within an electrical network or between distant networks by means of displacement current between circuit(s) node (circuits) , nodes, induced by the electric field. This coup ...
. Since voltages detected by high-impedance instruments disappear or become greatly reduced when a low impedance is substituted, the effect is sometimes called phantom voltage (or ghost voltage). The term is often used by electricians, and might be seen, for example, when measuring the voltage at a lighting fixture after removing the bulb. It is common to measure phantom voltages of 50–90 V in testing the wiring of ordinary 120 V circuits with a high-impedance instrument. The voltage produced may read almost to the full supply voltage, but the
capacitance
Capacitance is the ability of an object to store electric charge. It is measured by the change in charge in response to a difference in electric potential, expressed as the ratio of those quantities. Commonly recognized are two closely related ...
or
mutual inductance between the wires of
building wiring systems is typically quite low and incapable of supplying significant amounts of
current.
However, in
overhead transmission work on or near high-voltage lines, safety rules require connecting a conductor to
earth ground during maintenance. That is since induced voltages and currents on a conductor may cause electrocution or serious injury.
Capacitive leakage through insulation
Alternating current is different from direct current in that the current can flow through what would ordinarily seem to be a physical barrier. In a
series circuit
Terminal (electronics), Two-terminal components and electrical networks can be connected in series or parallel. The resulting electrical network will have two terminals, and itself can participate in a series or parallel Topology (electrical ci ...
, a
capacitor
In electrical engineering, a capacitor is a device that stores electrical energy by accumulating electric charges on two closely spaced surfaces that are insulated from each other. The capacitor was originally known as the condenser, a term st ...
blocks direct current but passes alternating current.
In power transmission systems, one side of the circuit, known as the
neutral, is grounded to dissipate
static electricity
Static electricity is an imbalance of electric charges within or on the surface of a material. The charge remains until it can move away by an electric current or electrical discharge. The word "static" is used to differentiate it from electric ...
and to reduce hazardous voltages caused by insulation failure and other electrical faults.
Even a person is standing on an insulated surface may get a shock only by touching the ''hot'' wire because of the person's body being capacitively coupled to the ground upon which the person stands.
Induced voltages
Classical
electromagnetic induction
Electromagnetic or magnetic induction is the production of an electromotive force, electromotive force (emf) across an electrical conductor in a changing magnetic field.
Michael Faraday is generally credited with the discovery of induction in 1 ...
can occur when long conductors form an open
grounded loop under and parallel to transmission or distribution lines. In those cases, current is induced in the loop when a person makes contact with it and ground. Since this involves real current flow, it is potentially hazardous. This type of induced current occurs most often on long fences and distribution lines built under high-power
transmission lines.
Degraded insulation on power conductors
Stray voltage may leak via damaged or degraded insulation. Failing insulation is essentially a high impedance fault which will allow current to flow through any available path to ground, a condition which can cause shocks or fires if left unmitigated. This leakage can occur when there is damage caused by physical, thermal, or chemical stresses to insulation on power lines, especially but not limited to underground or underwater cables. Examples of this damage are swollen or cracked insulation from overheating, abrasions caused by digging or ground seizing, and corrosion damage from salt or oil exposure. Electrical leakage can occur also from moisture, salt, dust, and dirt buildup on open air insulators in overhead power distribution. If the leakage in these cases is severe enough, it can lead to a utility pole fire.
Leakage from single-wire earth return
The term "stray voltage" is used for the gradient (rate of change with respect to distance) of
electrical potential in the surface of the soil, associated with
single-wire earth return electricity distribution systems used in some rural locations. This gradient is low at points far away from the earth return connections, but increases near the ground rods where the metallic circuit enters the earth.
Neutral return currents through the ground
In
three phase
Three-phase electric power (abbreviated 3ϕ) is a common type of alternating current (AC) used in electricity generation, transmission, and distribution. It is a type of polyphase system employing three wires (or four including an optional n ...
four-wire ("wye") electrical power systems, when the load on the phases is not exactly equal, there is some current in the neutral conductor. Because both the primary and secondary of the distribution transformer are grounded, and the primary ground is grounded at more than one point, the earth forms a parallel return path for the neutral current, allowing part of the neutral current to continuously flow through the earth. This arrangement is partially responsible for stray voltage.
Stray voltage is a result of the design of a 4 wire distribution system and as such has existed as long as such systems have been used. Stray voltage became a problem for the dairy industry some time after electric milking machines were introduced, and large numbers of animals were simultaneously in contact with metal objects grounded to the electric distribution system and the earth. Numerous studies document the causes, physiological effects, and prevention, of stray voltage in the farm environment. Today, stray voltage on farms is regulated by state governments and controlled by the design of
equipotential planes in areas where livestock eat, drink or give milk. Commercially available neutral isolators also prevent elevated potentials on the utility system neutral from raising the voltage of farm neutral or ground wires.
Railway stray current
Typically a rail transit systems will have at least one of the rails as a return conductor for the traction current. This arrangement is common, based on economic considerations, since it does not require the installation of an additional return conductor. This rail is in contact with the earth at many places throughout its length. Since current will follow every parallel path between source and load, some part of the traction current will also flow through the earth. This is normally referred to as leakage current or stray current. The amount of leaking current depends on the conductance of the return tracks compared to the soil; and on the quality of the insulation between the tracks and soil. Where the railway uses
direct current
Direct current (DC) is one-directional electric current, flow of electric charge. An electrochemical cell is a prime example of DC power. Direct current may flow through a conductor (material), conductor such as a wire, but can also flow throug ...
, this stray current can cause damage to other buried metallic objects by
electrolysis
In chemistry and manufacturing, electrolysis is a technique that uses Direct current, direct electric current (DC) to drive an otherwise non-spontaneous chemical reaction. Electrolysis is commercially important as a stage in the separation of c ...
and accelerate corrosion of metal objects in contact with the soil.
Stray Voltage Effects
Electrolysis and corrosion
Dissimilar buried metals such as copper and steel can function as the poles of a
galvanic cell, using moist soil as the electrolyte. Stray direct currents in soil may counteract the anti-corrosion effect of a
cathodic protection system. Design of
high voltage direct current transmission systems must take care so that current flowing in the earth does not cause objectionable corrosion to buried objects such as pipelines.
The stray currents from railways create or accelerate the electrolytic corrosion of metallic structures located in the proximity of the transit system. Metal pipes, cables and earthing grids laid in the ground near tracks may have a much shorter usable and safety functional life.
Persons
Small stray voltages may never be noticed and may be detected only by a
voltmeter
A voltmeter is an instrument used for measuring electric potential difference between two points in an electric circuit. It is connected in parallel. It usually has a high resistance so that it takes negligible current from the circuit.
A ...
. Larger stray voltages may have a range of effects, from barely perceptible to dangerous
electric shock
An electrical injury (electric injury) or electrical shock (electric shock) is damage sustained to the skin or internal organs on direct contact with an electric current.
The injury depends on the Current density, density of the current, tissu ...
s, or unintended electrical heating resulting in fires. Normally, metal electrical equipment cases are
bonded to ground to prevent a shock hazard if energized conductors accidentally contact the case. Where this bonding is not provided or has failed, a severe hazard of electric shock or
electrocution
Electrocution is death or severe injury caused by electric shock from electric current passing through the body. The word is derived from "electro" and "execution", but it is also used for accidental death.
The term "electrocution" was coined ...
is presented when circuit conductors contact the case.
In any situation where energized equipment is in intimate electrical contact with a person or animal (such as swimming pools, surgery, electric milking machines, car washes, laundries, and many others), particular attention must be paid to elimination of stray voltages. Dry intact skin has a higher
resistance than wet skin or a wound, so voltages that would otherwise be unnoticed become significant in a wet or surgical situation.
Potential differences between pool water and railings, or shower facilities and grounded drain pipes are common as a result of neutral to earth voltages (NEV). Potential differences can be a major nuisance, but are usually not life-threatening. However, a current carrying conductor with damaged insulation can result in contact voltage in unexpected places. Contact voltage energized metal parts can be very dangerous, and can lead to shock or electrocution. A contact voltage condition can arise spontaneously from mechanical, thermal, or chemical stress on insulation materials, or from unintentional damage from digging activity, freeze-frost seizing, corrosion and collapse of conduit, or even workmanship issues.
Contact voltage energizes objects which are normally safe – metal fences, metal telephone booths, metal street signs, etc. Anywhere buried electric wiring exists, a failure can occur in that wiring and create conditions that allow electricity to flow into the immediate surroundings. Some circuitry systems have protective devices such as circuit breakers or
Ground Fault Circuit Interrupters (GFCI), designed to isolate such a fault. However, in the absence of protective devices, a fault will go undetected until it either causes a failure or an energy discharge incident.
Farm animals
Stray voltage can have harmful effects on animal health and productivity. Some
dairy
A dairy is a place where milk is stored and where butter, cheese, and other dairy products are made, or a place where those products are sold. It may be a room, a building, or a larger establishment. In the United States, the word may also des ...
farmers have claimed damage to yields or stock caused by it.
Dr. Douglas J. Reinemann, Professor of Biological Systems Engineering at
University of Wisconsin–Madison
The University of Wisconsin–Madison (University of Wisconsin, Wisconsin, UW, UW–Madison, or simply Madison) is a public land-grant research university in Madison, Wisconsin, United States. It was founded in 1848 when Wisconsin achieved st ...
, reported on stray voltages on dairy farms in 2003. Investigation of stray voltage claims must also consider other animal health concerns.
Legal proceedings in Wisconsin
In 2003, the
Wisconsin Supreme Court
The Wisconsin Supreme Court is the Supreme court, highest and final court of appeals in the state judicial system of the U.S. state of Wisconsin. In addition to hearing appeals of lower Wisconsin court decisions, the Wisconsin Supreme Court also ...
upheld a
judgement of $1.2 million against the Wisconsin electrical utility
WEPCO in ''Hoffman''
v. ''Wisconsin Electric Power Company''. The Hoffman family, dairy farmers near
New London, had sued WEPCO after several years of declining production. WEPCO had measured on the farm currents because of stray voltage <1
mA, the "level of concern" set by the
Public Service Commission of Wisconsin, but the court ruled on procedural grounds that the utility could be found negligent under
common law
Common law (also known as judicial precedent, judge-made law, or case law) is the body of law primarily developed through judicial decisions rather than statutes. Although common law may incorporate certain statutes, it is largely based on prece ...
even though they met the state standard. The Hoffmans had presented, the court said, a viable alternative theory that stray voltage had caused them economic harm.
In 2017, a jury sided with farmers Paul and Lyn Halderson for a $4.5 million settlement against
Xcel Energy. The Haldersons claimed stray voltage from high voltage power lines hurt their 1,000 cow herd and lowered milk production. The jury found that Xcel subsidiary –
Northern States Power Company – was "negligent with respect to the delivery of electrical service." The jury awarded $4.09 million for economic damages and another $409,000 for "inconvenience, annoyance and loss of use and enjoyment" of property.
Public concerns about stray voltage
In metropolitan areas, stray voltage issues became a concern in the 1990s. Many of these areas have large amounts of aging underground and aboveground electrical distribution equipment in crowded public spaces. Even a low rate of insulation failures or current leakage can result in hazardous exposure to the general public.
Consolidated Edison
Consolidated Edison, Inc., commonly known as Con Edison (stylized as conEdison) or ConEd, is one of the largest investor-owned energy companies in the United States, with approximately $12 billion in annual revenues as of 2017, and over $62 ...
in
New York City
New York, often called New York City (NYC), is the most populous city in the United States, located at the southern tip of New York State on one of the world's largest natural harbors. The city comprises five boroughs, each coextensive w ...
has had frequent incidents of stray voltage,
including the electrocution death of Jodie S. Lane in 2004, while walking her dog in
Manhattan
Manhattan ( ) is the most densely populated and geographically smallest of the Boroughs of New York City, five boroughs of New York City. Coextensive with New York County, Manhattan is the County statistics of the United States#Smallest, larg ...
.
In 2009, the Jodie S. Lane Public Safety Foundation
announced a publicly accessible website with maps showing thousands of reported stray voltage locations in New York City. In addition, the Foundation sponsors the "Jodie S. Lane Stray Voltage Detection, Mitigation & Prevention Conference", an annual meeting attended by power utilities and regulators from around the country to discuss stray voltage detection programs. The Foundation also initiated and advocates regular mobile scanning by utility companies for stray voltage hazards.
In Boston,
NSTAR Electric (formerly
Boston Edison) has also had problems with hazardous stray voltages, which have killed several dogs during the 1990s.
As a result, the
City of Boston government started a program to detect, report on, and repair stray voltage hazards.
Toronto Hydro pulled all employees off regular duty on the weekend of January 30, 2009 to deal with ongoing stray voltage problems in the city. This came after as many as five children were shocked though none suffered serious injury. The stray voltage problem had claimed the lives of two dogs in the previous few months.
In March 2013, Californian Simona Wilson won a $4 million lawsuit against her power company after stray voltage from an
electrical substation near her house repeatedly shocked her and members of her family whenever they were in the shower.
Woman Shocked in Shower by Stray Voltage Wins $4 Million Lawsuit
Yahoo News, 21 Mar 2013. Retrieved 22 Mar 2013.
The United States Social Security Administration, Administrative Law Judge, Edward Bergtholdt, in an August 17, 2000 decision awarded Michael Gunner permanent disability from exposure to stray voltage.
Stray/contact voltage detection
Stray voltage is generally discovered during routine electrical work, or as a result of a customer complaint or shock incident. A growing number of utilities in urban areas now conduct routine periodic and systematic active tests for stray voltage (or more specifically, contact voltage) for public safety reasons. Some incipient electrical faults may also be discovered during routine work or inspection programs which are not specifically focused on stray voltage.
Equipment used to detect stray voltage varies, but common devices are electrical tester pens or electric field detectors, with follow-up testing using a low-impedance voltmeter. Electrical tester pens are hand-held devices which detect a potential difference between the user's hand and the object being tested. They generally indicate on contact with an energized object, if the potential difference is above the sensitivity threshold of the device. Reliability of the test can be affected if the user is at an elevated potential him/herself, or if the user is not making firm contact with a bare hand on the reference terminal of the tester.
Capacitive coupling
Capacitive coupling (electronics), coupling is the transfer of energy within an electrical network or between distant networks by means of displacement current between circuit(s) node (circuits) , nodes, induced by the electric field. This coup ...
is the mechanism used by electrical tester pen devices. Because the capacitance between an object and a current source is typically small, only very small currents can flow from the energized source to the coupled object. High-impedance digital or analog voltmeters may measure elevated voltages from non-energized objects from the coupling and in effect provide a misleading reading. For that reason, high-impedance voltage measurements of normally non-energized objects must be verified.
Verification of a voltage reading is performed using a ''low-impedance'' voltmeter, which usually has a shunt resistor load bridging the voltmeter terminals. Since very little current can flow from a coupled surface through the small shunt or meter resistance, capacitively coupled voltages will collapse to zero, indicating a harmless "false alarm". By contrast, if an object being tested is in contact with a current source, or coupled by a very large capacitance (possible but unlikely in this context), the voltage will drop only slightly as dictated by Ohm's law
Ohm's law states that the electric current through a Electrical conductor, conductor between two Node (circuits), points is directly Proportionality (mathematics), proportional to the voltage across the two points. Introducing the constant of ...
. In this latter case, real power is being delivered, indicating a potentially hazardous situation.
Electric field detectors detect the electric field strength relative to the user's body or mounting platform. By sensing electric field
An electric field (sometimes called E-field) is a field (physics), physical field that surrounds electrically charged particles such as electrons. In classical electromagnetism, the electric field of a single charge (or group of charges) descri ...
gradients at a distance, they can detect energized objects without making direct contact, making these instruments useful for scanning or screening large areas for potential electrical hazards. A low electric field reading also provides a definitive indication that no objects are energized within a tested area. Electric field detectors respond to all field sources, and any positive indications must be verified with a low-impedance voltmeter to eliminate false positives. Electric field proximity sensing also has other industrial applications from manufacturing to building security.
Since stray voltage cannot be seen, smelled, or heard, there is no easy way for the public to know when a dangerous condition exists. Periodic testing is an important precaution, but it is possible that a dangerous condition can develop without warning.
See also
* Disturbance voltage
* Earth potential rise
* Earthing system
*Electrical bonding
Electricity is the set of physical phenomena associated with the presence and motion of matter possessing an electric charge. Electricity is related to magnetism, both being part of the phenomenon of electromagnetism, as described by Maxwe ...
*Gas leak
A gas leak refers to a leak of natural gas or another gaseous product from a pipeline or other containment into any area where the gas should not be present. Gas leaks can be hazardous to health as well as the environment. Even a small leak into ...
* Neutral and ground
* Shaft voltage
References
External links
University of Wisconsin–Madison Report on Stray Voltage
'Electrified Cover Safeguard' website
'Stray voltage' website
from the '' LaCrosse Tribune'', including their award-winning coverage
Self-Help Guide: Stray Voltage Detection
Wisconsin Farm Electric Council (2/1997), well written, for farmer-consumers, at
Stray Voltage portal
Wisconsin Public Service Stray Voltage site
(technical)
Pacific Gas and Electric Power Quality Bulletin No. 2, "Stray Voltage"
(10/2004)
First conference about "Stray currents in our environment" - November 29, 2007, Ester Technopole Limoges, France
Stray voltage description and mitigation
{{DEFAULTSORT:Stray Voltage
Electrical parameters