Spurious trip level
   HOME

TheInfoList



OR:

Spurious trip level (STL) is defined as a discrete level for specifying the spurious trip requirements of safety functions to be allocated to safety systems. An STL of 1 means that this safety function has the highest level of spurious trips. The higher the STL level the lower the number of spurious trips caused by the safety system. There is no limit to the number of spurious trip levels. Safety functions and systems are installed to protect people, the environment and for asset protection. A safety function should only activate when a dangerous situation occurs. A safety function that activates without the presence of a dangerous situation (e.g., due to an internal failure) causes economic loss. The spurious trip level concept represents the probability that safety function causes a spurious (unscheduled) trip. The STL is a metric that is used to specify the performance level of a safety function in terms of the spurious trips it potentially causes. Typical safety systems that benefit from an STL level are defined in standards like
IEC 61508 IEC 61508 is an international standard published by the International Electrotechnical Commission consisting of methods on how to apply, design, deploy and maintain automatic protection systems called safety-related systems. It is titled ''Functio ...
IEC 61511 IEC standard 61511 is a technical standard which sets out practices in the engineering of systems that ensure the safety of an industrial process through the use of instrumentation. Such systems are referred to as ''Safety Instrumented Systems''. ...
, IEC 62061, ISA S84, EN 50204EN 50204 - Electrical apparatus for the detection and measurement of combustible or toxic gases or vapours or of oxygen. Requirements on the functional safety of fixed gas detection systems and so on. An STL provides end-users of safety functions with a measurable attribute that helps them define the desired availability of their safety functions. An STL can be specified for a complete safety loop or for individual devices. For end-users there is always a potential conflict between the cost of safety solutions and the loss of profitability caused by spurious trips of these safety solutions. The STL concept helps the end-users to end this conflict in a way that safety solutions provide both the desired safety and the desired process availability.


STL determination

The spurious trip level represents asset loss due to an internal failure of the safety function. The more financial damage the safety function can cause due to a spurious trip the higher the STL level of the safety function should be. Each company needs to decide for themselves which level of financial loss they can or are willing to take. This actually depends on many different factors including the financial strength of the company, the insurance policy they have, the cost of process shutdown and startup, and so on. All these factors are unique to each company. The table below shows an example of how a company can calibrate its spurious trip levels.


STL levels

The STL level achieved by a safety function is determined by the probability of fail safe (PFS) of this safety function. The PFS value is determined by internal failures of the safety system that cause the safety function to be executed without a demand from the process. The table below demonstrates the PFS value and spurious trip reduction values of each STL level.


STL vs SIL

Today standards only define the
safety integrity level Safety integrity level (SIL) is defined as the relative level of risk-reduction provided by a safety function, or to specify a target level of risk reduction. In simple terms, SIL is a measurement of performance required for a safety instrumented ...
(SIL) for safety functions. Standards do not define STL levels because they do in first instance not represent safety but economic loss. Despite this the STL is also a safety attribute, specially for safety functions in the process, oil & gas, chemical and nuclear industry. In those industries an undesired shutdown of the process leads to dangerous situation as the plant needs to be started up again. Startup and shutdown of a process plant are considered the two most dangerous operational modes of the plant and should be limited to the absolute minimum. In practice the STL and SIL concepts complement each other. Both factors are attributes of the same safety function. The STL level is determined by the average PFS value of the safety function. The SIL level is determined by the average probability of failure on demand. PFD value of the safety function. The STL level expresses the probability of spurious trips by the safety function, i.e., the safety function is executed without a demand from the process. The SIL level expresses the probability that the safety function does not work upon demand from the process. Both parameters are important to end-users in order to achieve safety and asset protection. {, class="wikitable" , - ! Description ! Spurious Trip Level ! Safety Integrity Level , - , Calculated via , Average PFS , Average PFD , - , Represents , Process availability , Safety availability , - , Expressed as ... , STL , SIL , - , Number of levels ... , Unlimited , 1 through 4 In order to calculate the PFS or PFD value of a safety loop it is necessary to have a reliability model and reliability data for each component in the safety loop. The best reliability model to use is a Markov model (see Andrey Markov). Typical data required are: * Lambda safe detected * Lambda safe undetected * Lambda dangerous detected * Lambda dangerous undetected * Repair rate * Proof test coverage * Proof test interval * Common cause factors


See also

*
Safety integrity level Safety integrity level (SIL) is defined as the relative level of risk-reduction provided by a safety function, or to specify a target level of risk reduction. In simple terms, SIL is a measurement of performance required for a safety instrumented ...


Notes


External links


Spurious Trip Level analysis and certificationIEC Functional safety zoneIEC What is functional safety?Overview of IEC 61508

SIL and Functional Safety in a Nutshell
- eBook introducing SIL and Functional Safety Safety Risk management Safety engineering