Ground loop (electricity)
   HOME

TheInfoList



OR:

In an electrical system, a ground loop or earth loop occurs when two points of a circuit are intended to have the same
ground Ground may refer to: Geology * Land, the surface of the Earth not covered by water * Soil, a mixture of clay, sand and organic matter present on the surface of the Earth Electricity * Ground (electricity), the reference point in an electrical c ...
reference potential but instead have a different potential between them. This is typically caused when enough current is flowing in the connection between the two ground points to produce a voltage drop and cause two points to be at different potentials. Current may be produced in a circular ground connection (ground loop) by
electromagnetic induction Electromagnetic or magnetic induction is the production of an electromotive force (emf) across an electrical conductor in a changing magnetic field. Michael Faraday is generally credited with the discovery of induction in 1831, and James Cle ...
. Ground loops are a major cause of
noise Noise is unwanted sound considered unpleasant, loud or disruptive to hearing. From a physics standpoint, there is no distinction between noise and desired sound, as both are vibrations through a medium, such as air or water. The difference aris ...
, hum, and interference in audio, video, and computer systems. Wiring practices that protect against ground loops include ensuring that all vulnerable signal circuits are referenced to one point as ground. The use of differential signaling can provide rejection of ground-induced interference. Removal of safety ground connections to equipment in an effort to eliminate ground loops also eliminates the protection the safety ground connection is intended to provide.


Description

A ground loop is caused by the interconnection of electrical equipment that results in multiple paths to ground, thereby forming closed conductive loops through the ground connections. A common example is two pieces of electrical equipment, A and B, each connected to a mains power outlet by a 3 conductor cable and plug containing a protective ground conductor for
safety Safety is the state of being "safe", the condition of being protected from harm or other danger. Safety can also refer to the control of recognized hazards in order to achieve an acceptable level of risk. Meanings There are two slightly di ...
. When signal cables are connected between A and B, the
shield A shield is a piece of personal armour held in the hand, which may or may not be strapped to the wrist or forearm. Shields are used to intercept specific attacks, whether from close-ranged weaponry or projectiles such as arrows, by means of ...
of the data cable is typically connected to the grounded equipment chassis of both A and B. This forms a closed loop through the ground conductors of the power cords, which are connected through the building wiring. In the vicinity of electric power wiring there will always be stray
magnetic field A magnetic field is a vector field that describes the magnetic influence on moving electric charges, electric currents, and magnetic materials. A moving charge in a magnetic field experiences a force perpendicular to its own velocity and to ...
s, particularly from utility lines oscillating at 50 or 60 
hertz The hertz (symbol: Hz) is the unit of frequency in the International System of Units (SI), equivalent to one event (or cycle) per second. The hertz is an SI derived unit whose expression in terms of SI base units is s−1, meaning that o ...
. These ambient
magnetic field A magnetic field is a vector field that describes the magnetic influence on moving electric charges, electric currents, and magnetic materials. A moving charge in a magnetic field experiences a force perpendicular to its own velocity and to ...
s passing through the ground loop will induce a current in the loop by
electromagnetic induction Electromagnetic or magnetic induction is the production of an electromotive force (emf) across an electrical conductor in a changing magnetic field. Michael Faraday is generally credited with the discovery of induction in 1831, and James Cle ...
. The ground loop acts as a single-turn secondary winding of a
transformer A transformer is a passive component that transfers electrical energy from one electrical circuit to another circuit, or multiple circuits. A varying current in any coil of the transformer produces a varying magnetic flux in the transformer' ...
, the primary being the summation of all current-carrying conductors nearby. The amount of current induced will depend on the magnitude and proximity of nearby currents. The presence of high-power equipment such as industrial motors or transformers can increase the interference. Since the conductors comprising the ground loop usually have very low resistance, often below one
ohm Ohm (symbol Ω) is a unit of electrical resistance named after Georg Ohm. Ohm or OHM may also refer to: People * Georg Ohm (1789–1854), German physicist and namesake of the term ''ohm'' * Germán Ohm (born 1936), Mexican boxer * Jörg Ohm (bor ...
, even weak magnetic fields can induce significant currents. Since the ground conductor of the signal cable linking the two pieces of equipment A and B is part of the signal path of the cable, the alternating ground current flowing through the cable can introduce electrical interference in the signal. The induced alternating current flowing through the resistance of the cable ground conductor will cause a small AC voltage drop across the cable ground. This is added to the signal applied to the input of the next stage. In
audio equipment Audio equipment refers to devices that reproduce, record, or process sound. This includes microphones, radio receivers, AV receivers, CD players, tape recorders, amplifiers, mixing consoles, effects units, headphones, and speakers. Audio ...
, the 50 or 60 Hz interference may be heard as a hum in the speakers. In a video system it may cause distortion or syncing problems. In computer cables it can cause slowdowns or failures of data transfer. Ground loops can also exist within the internal circuits of electronic equipment, as design flaws.


Representative circuit

The circuit diagram illustrates a simple ground loop. Circuit 1 (left) and circuit 2 (right) share a common path to ground of resistance \scriptstyle R_G. Ideally, this ground conductor would have no resistance (\scriptstyle R_G = 0), yielding no voltage drop across it (\scriptstyle V_G = 0), keeping the connection point between the circuits at a constant ground potential. In that case, the output of circuit 2 is simply \scriptstyle V_\text = V_2. However, if this ground conductor has some resistance (\scriptstyle R_G > 0), then it forms a voltage divider with \scriptstyle R_1. As a result, if a current (\scriptstyle I_1) is flowing through \scriptstyle R_G from circuit 1, then a voltage drop across \scriptstyle R_G of \scriptstyle V_G\; =\; I_1 R_G occurs, causing the shared ground connection to no longer be at the actual ground potential. This voltage across the ground conductor is applied to circuit 2 and added to its output:V_\text = V_2 - V_G = V_2 - \fracV_1.\, Thus the two circuits are no longer isolated from each other and circuit 1 can introduce interference into the output of circuit 2. If circuit 2 is an audio system and circuit 1 has large AC currents flowing in it, the interference may be heard as a 50 or 60 Hz hum in the speakers. Also, both circuits have voltage \scriptstyle V_G on their grounded parts that may be exposed to contact, possibly presenting a
shock Shock may refer to: Common uses Collective noun *Shock, a historic commercial term for a group of 60, see English numerals#Special names * Stook, or shock of grain, stacked sheaves Healthcare * Shock (circulatory), circulatory medical emerge ...
hazard. This is true even if circuit 2 is turned off. Although ground loops occur most often in the ground conductors of electrical equipment, similar loops can occur wherever two or more circuits share a common current path, which can cause a similar problematic voltage drop along the conductor if enough current flows.


Common ground loops

A common type of ground loop is due to faulty interconnections between electronic components, such as laboratory or
recording studio A recording studio is a specialized facility for sound recording, mixing, and audio production of instrumental or vocal musical performances, spoken words, and other sounds. They range in size from a small in-home project studio large enou ...
equipment, or home component audio, video, and computer systems. This creates inadvertent closed loops in the ground wiring circuit, which can allow stray 50/60 Hz AC current to be induced and flow through the ground conductors of signal cables. The voltage drops in the ground system caused by these currents are added to the signal path, introducing noise and hum into the output. The loops can include the building's utility wiring ground system when more than one component is grounded through the protective earth (third wire) in their power cords.


Ground currents on signal cables

The symptoms of a ground loop, ground noise and hum in electrical equipment, are caused by current flowing in the ground or conductor of a cable. Fig. 1 shows a signal cable ''S'' linking two electronic components, including the typical line driver and receiver amplifiers ''(triangles)''. The cable has a ground or shield conductor which is connected to the chassis ground of each component. The driver amplifier in component 1 ''(left)'' applies signal ''V''1 between the signal and ground conductors of the cable. At the destination end ''(right)'', the signal and ground conductors are connected to a differential amplifier. This produces the signal input to component 2 by subtracting the shield voltage from the signal voltage to eliminate common-mode noise picked up by the cable V_2 = V_\text - V_\text \, If a current ''I'' from a separate source is flowing through the ground conductor, the resistance ''R'' of the conductor will create a voltage drop along the cable ground of ''IR'', so the destination end of the ground conductor will be at a different potential than the source end V_\text = V_\text - IR \, Since the differential amplifier has high impedance, little current flows in the signal wire, therefore there is no voltage drop across it: V_\text = V_\text \, The ground voltage appears to be in series with the signal voltage ''V''1 and adds to it V_2 = V_\text - (V_\text - IR)\, V_2 = V_1 + IR\, If ''I'' is an AC current this can result in noise added to the signal path in component 2.


Sources of ground current

The diagrams in this section show a typical ground loop caused by a signal cable ''S'' connecting two grounded electronic components ''C1'' and ''C2''. The loop consists of the signal cable's ground conductor, which is connected through the components' metal chassis to the ground wires ''P'' in their power cords, which are plugged into outlet grounds which are connected through the building's utility ground wire system ''G''. Such loops in the ground path can cause currents in signal cable grounds by two main mechanisms: * Ground loop currents can be induced by stray AC
magnetic field A magnetic field is a vector field that describes the magnetic influence on moving electric charges, electric currents, and magnetic materials. A moving charge in a magnetic field experiences a force perpendicular to its own velocity and to ...
s ''(B, green)'' which are always present around AC electrical wiring. The ground loop constitutes a conductive wire loop which may have a large area of several square meters. According to
Faraday's law of induction Faraday's law of induction (briefly, Faraday's law) is a basic law of electromagnetism predicting how a magnetic field will interact with an electric circuit to produce an electromotive force (emf)—a phenomenon known as electromagnetic in ...
, any time-varying
magnetic flux In physics, specifically electromagnetism, the magnetic flux through a surface is the surface integral of the normal component of the magnetic field B over that surface. It is usually denoted or . The SI unit of magnetic flux is the weber ...
passing through the loop induces an
electromotive force In electromagnetism and electronics, electromotive force (also electromotance, abbreviated emf, denoted \mathcal or ) is an energy transfer to an electric circuit per unit of electric charge, measured in volts. Devices called electrical '' tran ...
(EMF) in the loop, causing a time varying current to flow. The loop acts like a
short circuit A short circuit (sometimes abbreviated to short or s/c) is an electrical circuit that allows a current to travel along an unintended path with no or very low electrical impedance. This results in an excessive current flowing through the circu ...
ed single-turn transformer winding; any AC
magnetic flux In physics, specifically electromagnetism, the magnetic flux through a surface is the surface integral of the normal component of the magnetic field B over that surface. It is usually denoted or . The SI unit of magnetic flux is the weber ...
from nearby transformers, electric motors, or just adjacent power wiring, will induce AC currents in the loop by induction. In general, the larger the area spanned by the loop and the larger the magnetic flux through it, the larger the induced currents will be. Since its resistance is typically very low, often less than 1
ohm Ohm (symbol Ω) is a unit of electrical resistance named after Georg Ohm. Ohm or OHM may also refer to: People * Georg Ohm (1789–1854), German physicist and namesake of the term ''ohm'' * Germán Ohm (born 1936), Mexican boxer * Jörg Ohm (bor ...
, the induced currents can be large. * Another less common source of ground loop currents, particularly in high-power equipment, is current leaking from the ''hot'' side of the power line into the ground system.This type is often called "common impedance coupling"
Ballou 2008 ''Handbook for Sound Engineers, 4th Ed.'', p. 1198-1200
/ref> In addition to resistive leakage, current can also be induced through low impedance capacitive or inductive coupling. The ground potential at different outlets may differ by as much as 10 to 20 volts due to voltage drops from these currents. The diagram shows leakage current from an appliance such as an electric motor ''A'' flowing through the building's ground system ''G'' to the neutral wire at the utility ground bonding point at the service panel. The ground loop between components ''C1'' and ''C2'' creates a second parallel path for the current. The current divides, with some passing through component ''C1'', the signal cable ''S'' ground conductor, ''C2'' and back through the outlet into the ground system ''G''. The AC voltage drop across the cable's ground conductor from this current introduces hum or interference into component ''C2''.


Solutions

The solution to ground loop noise is to break the ground loop, or otherwise prevent the current from flowing. Several approaches are available. * Group the cables involved in the ground loop into a bundle or
snake Snakes are elongated, limbless, carnivorous reptiles of the suborder Serpentes . Like all other squamates, snakes are ectothermic, amniote vertebrates covered in overlapping scales. Many species of snakes have skulls with several more ...
. The ground loop still exists, but the two sides of the loop are close together, so stray magnetic fields induce equal currents in both sides, which cancel out. * Create a break in the signal cable shield conductor. The break should be at the load end. This is often called ''ground lifting''. It is the simplest solution; it leaves the ground currents to flow through the other arm of the loop. Some sound system components have ground lifting switches at inputs, which disconnect the ground. One problem with this solution is if the other ground path to the component is removed, it will leave the component ungrounded and stray leakage currents may cause a very loud hum in the output, possibly damaging speakers. * Put a small resistor of about 10Ω in the cable shield conductor, at the load end. This is large enough to reduce magnetic-field-induced currents but small enough to keep the component grounded if the other ground path is removed. In high-frequency systems this solution leads to impedance mismatch and leakage of the signal onto the shield, where it can radiate to create RFI, or, symmetrically through the same mechanism, external signals or noise can be received by the shield and mixed into the desired signal. * Use a ground loop isolation transformer in the cable. This is considered the best solution, as it breaks the DC connection between components while passing the differential signal on the line. Even if one or both components are ungrounded, no noise will be introduced. The better isolation transformers have grounded shields between the two sets of windings. A transformer generally introduces some distortion in frequency response. A transformer designed specifically for the relevant frequency range must be used. Optoisolators can perform the same task for digital lines but introduce signal delay. * In circuits producing high-frequency noise such as computer components, ferrite bead chokes are placed around cables just before the termination to the next appliance (e.g., the computer). These present a high impedance only at high frequency, so they will effectively stop radio frequency and digital noise, but will have little effect on 50/60 Hz noise. * Reinforce the shield of the signal cable connecting C1 and C2 by connecting a thick copper conductor in parallel to the shield. This reduces the resistance of the shield and thus the amplitude of the unwanted signal. * A technique used in recording studios is to interconnect all the metal chassis with heavy conductors like copper strips, then connect to the building ground wire system at ''one'' point; this is referred to as ''star grounding'' or ''single-point grounding''. However, in home systems, multiple components are usually grounded through their 3-wire power cords, resulting in multipoint grounds. *
Battery Battery most often refers to: * Electric battery, a device that provides electrical power * Battery (crime), a crime involving unlawful physical contact Battery may also refer to: Energy source *Automotive battery, a device to provide power t ...
-powering one or more of the circuits can avoid a ground loop, because the entire device may be disconnected from mains power. A hazardous technique sometimes used by amateurs is to break the ''third wire'' ground conductor ''P'' in one of the component's power cords, by removing the ground pin on the plug, or using a cheater plug. This creates an electric shock hazard by leaving one of the components ungrounded.


Balanced lines

A more comprehensive solution is to use equipment that employs differential signaling. Ground noise can only get into the signal path in
single-ended signaling Single-ended signaling is the simplest and most commonly used method of transmitting electrical signals over wires. One wire carries a varying voltage that represents the signal, while the other wire is connected to a reference voltage, usually ...
, in which the ground or shield conductor serves as one side of the signal path. When the signal is sent as a differential signal along a pair of wires, neither of which are connected to ground, any noise from the ground system induced in the signal lines is a common-mode signal, identical in both wires. Since the line receiver at the destination end only responds to differential signals, a difference in voltage between the two lines, the common-mode noise is canceled out. Thus these systems are very immune to electrical noise, including ground noise. Professional and scientific equipment often uses differential signaling with
balanced line In telecommunications and professional audio, a balanced line or balanced signal pair is a circuit consisting of two conductors of the same type, both of which have equal electrical impedance, impedances along their lengths and equal impedances to ...
s.


History

The causes of ground loops have been thoroughly understood for more than half a century, and yet they are still a very common problem where multiple components are interconnected with cables. The underlying reason for this is an unavoidable conflict between the two different functions of a grounding system: reducing electronic noise and preventing electric shock. From a noise perspective, it is preferable to have ''single-point grounding'', with the system connected to the building ground wire at only one point. National electrical codes, however, often require all mains-powered components to have third-wire grounds; from a safety standpoint, it is preferable to have each mains component grounded. However, the multiple ground connections cause ground loops when the components are interconnected by signal cables. For this reason, in some large professional installations such as recording studios, it is sometimes the practice to provide two completely separate ground connections to equipment bays. One is the normal safety ground that connects to exposed metalwork, the other is a technical ground for cable screens and the like.


In low frequency audio and instrumentation systems

If, for example, a domestic HiFi system has a grounded turntable and a grounded preamplifier connected by a thin screened cable (or cables, in a stereo system) using phono connectors, the cross-section of copper in the cable screen(s) is likely to be less than that of the protective ground conductors for the turntable and the preamplifier. So, when a current is induced in the loop, there will be a voltage drop along the signal ground return. This is directly additive to the wanted signal and will result in objectionable hum. For instance, if a current I of 1 mA at the local power frequency is induced in the ground loop, and the resistance R of the screen of the signal cable is 100 mΩ, the voltage drop will be V = I \cdot R = 100 µV. This is a significant fraction of the output voltage of a
moving coil A magnetic cartridge, more commonly called a phonograph cartridge or phono cartridge or (colloquially) a pickup, is an electromechanical transducer that is used to play records on a turntable. The cartridge contains a removable or permanentl ...
pickup cartridge, and imposes an objectionable hum on the cartridge output. In a more complex situation, such as
sound reinforcement system A sound reinforcement system is the combination of microphones, signal processors, amplifiers, and loudspeakers in enclosures all controlled by a mixing console that makes live or pre-recorded sounds louder and may also distribute those sou ...
s, public address systems, music instrument amplifiers,
recording studio A recording studio is a specialized facility for sound recording, mixing, and audio production of instrumental or vocal musical performances, spoken words, and other sounds. They range in size from a small in-home project studio large enou ...
and broadcast studio equipment, there are many signal sources in mains-powered equipment feeding many inputs on other equipment and interconnection may result in hum problems. Attempting to cure these problems by removing the protective ground conductor creates a
shock hazard Electrical injury is a physiological reaction caused by electric current passing through the body. The injury depends on the density of the current, tissue resistance and duration of contact. Very small currents may be imperceptible or produce a ...
. Solving hum problems must be done in the signal interconnections, and this is done in two main ways, which may be combined.


Isolation

Isolation is the quickest, quietest and most foolproof method of resolving hum problems. The signal is isolated by a small transformer, such that the source and destination equipment each retain their own protective ground connections, but there is no through connection from one to the other in the signal path. By transformer isolating all unbalanced connections, we can connect unbalanced connections with balanced connections and thus fix the hum problem. In analog applications such as audio, the physical limitations of the transformers cause some signal degradation, by limiting bandwidth and adding some distortion.


Balanced interconnection

Balanced connections see the spurious noise due to ground loop current as common-mode interference while the signal is differential, enabling them to be separated at the destination by circuits having a high
common-mode rejection ratio In electronics, the common mode rejection ratio (CMRR) of a differential amplifier (or other device) is a metric used to quantify the ability of the device to reject common-mode signals, i.e. those that appear simultaneously and in-phase on bot ...
. This rejection can be accomplished with transformers or semiconductor output drivers and line receivers. With the increasing trend towards digital processing and transmission of audio signals, the full range of isolation by small pulse transformers, optocouplers or fibre optics become more useful. Standard protocols such as S/PDIF, AES3 or TOSLINK are available in relatively inexpensive equipment and allow full isolation, so ground loops need not arise, especially when connecting between audio systems and computers. In instrumentation systems, the use of differential inputs with high common-mode rejection ratio, to minimize the effects of induced AC signals on the parameter to be measured, is widespread. It may also be possible to introduce narrow notch filters at the power frequency and its lower harmonics; however, this can not be done in audio systems due to the objectionable audible effects on the wanted signal.


In analog video systems

In analog video, mains hum can be seen as hum bars (bands of slightly different brightness) scrolling vertically up the screen. These are frequently seen with video projectors where the display device has its case grounded via a 3-prong plug, and the other components have a floating ground connected to the CATV coax. In this situation the video cable is grounded at the projector end to the home electrical system, and at the other end to the cable TV's ground, inducing a current through the cable which distorts the picture. This problem can not be solved by a simple isolating transformer in the video feed, as the video signal has a net DC component, which varies. The isolation must be put in the CATV RF feed instead. The internal design of the CATV box should have provided for this. Ground loop issues with television coaxial cable can affect any connected audio devices such as a receiver. Even if all of the audio and video equipment in, for example, a home theatre system is plugged into the same power outlet, and thus all share the same ground, the coaxial cable entering the TV is sometimes grounded by the cable company to a different point than that of the house's electrical ground creating a ground loop, and causing undesirable mains hum in the system's speakers. Again, this problem is due entirely to incorrect design of the equipment.


In digital and RF systems

In digital systems, which commonly transmit data serially (
RS-232 In telecommunications, RS-232 or Recommended Standard 232 is a standard originally introduced in 1960 for serial communication transmission of data. It formally defines signals connecting between a ''DTE'' ('' data terminal equipment'') suc ...
, RS-485, USB,
FireWire IEEE 1394 is an interface standard for a serial bus for high-speed communications and isochronous real-time data transfer. It was developed in the late 1980s and early 1990s by Apple in cooperation with a number of companies, primarily Sony an ...
,
DVI Digital Visual Interface (DVI) is a video display interface developed by the Digital Display Working Group (DDWG). The digital interface is used to connect a video source, such as a video display controller, to a display device, such as a comp ...
,
HDMI High-Definition Multimedia Interface (HDMI) is a proprietary audio/video interface for transmitting uncompressed video data and compressed or uncompressed digital audio data from an HDMI-compliant source device, such as a display controlle ...
etc.) the signal voltage is often much larger than induced power frequency AC on the connecting cable screens, but different problems arise. Of those protocols listed, only RS-232 is single-ended with ground return, but it is a large signal, typically + and - 12V, all the others being differential. Simplistically, the big problem with the differential protocols is that with slightly mismatched capacitance from the hot and cold wires to ground, or slightly mismatched hot and cold voltage swings or edge timing, the currents in the hot and cold wires will be unequal, and also a voltage will be coupled onto the signal screen, which will cause a circulating current at signal frequency and its harmonics, extending up to possibly many GHz. The difference in signal current magnitudes between the hot and cold conductors will try to flow from, for example, item A's protective ground conductor back to a common ground in the building, and back along item B's protective ground conductor. This may involve a large loop area and cause significant radiation, violating EMC regulations and causing interference to other equipment. As a result of the reciprocity theorem the same loop will act as a receiver of high-frequency noise and this will be coupled back into the signal circuits, with the potential to cause serious signal corruption and data loss. On a video link, for example, this may cause visible noise on the display device or complete non-operation. In a data application. such as between a computer and its network storage, this may cause very serious data loss. The "cure" for these problems is different from that for low frequency and audio ground loop problems. For example, in the case of Ethernet
10BASE-T 1 (one, unit, unity) is a number representing a single or the only entity. 1 is also a numerical digit and represents a single unit of counting or measurement. For example, a line segment of ''unit length'' is a line segment of length 1 ...
,
100BASE-TX In computer networking, Fast Ethernet physical layers carry traffic at the nominal rate of 100 Mbit/s. The prior Ethernet speed was 10 Mbit/s. Of the Fast Ethernet physical layers, 100BASE-TX is by far the most common. Fast Ether ...
and
1000BASE-T In computer networking, Gigabit Ethernet (GbE or 1 GigE) is the term applied to transmitting Ethernet frames at a rate of a gigabit per second. The most popular variant, 1000BASE-T, is defined by the IEEE 802.3ab standard. It came into use ...
, where the data streams are Manchester encoded to avoid any DC content, the ground loop(s) which would occur in most installations are avoided by using signal isolating transformers, often incorporated into the body of the fixed
RJ45 A modular connector is a type of electrical connector for cords and cables of electronic devices and appliances, such as in computer networking, telecommunication equipment, and audio headsets. Modular connectors were originally developed fo ...
jack. Many of the other protocols break the ground loop at data baud rate frequency by fitting small ferrite cores around the connecting cables near each end, and/or just inside the equipment boundary. These form a
common-mode choke In electronics, a choke is an inductor used to block higher-frequency alternating currents while passing direct current (DC) and lower-frequencies alternating current (AC) in an electrical circuit. A choke usually consists of a coil of insulated ...
which inhibits unbalanced current flow, without affecting the differential signal. This technique is equally valid for coaxial interconnects, and many
camcorder A camcorder is a self-contained portable electronic device with video and recording as its primary function. It is typically equipped with an articulating screen mounted on the left side, a belt to facilitate holding on the right side, hot-sw ...
s have ferrite cores fitted to some of their auxiliary cables such as DC charging and external audio input, to break the high-frequency current flow if the user inadvertently creates a ground loop when connecting external equipment.
Coaxial cable Coaxial cable, or coax (pronounced ) is a type of electrical cable consisting of an inner conductor surrounded by a concentric conducting shield, with the two separated by a dielectric ( insulating material); many coaxial cables also have a p ...
s used at radio frequencies may be wound several times through a ferrite core to add a useful amount of common-mode inductance. This limits the flow of unwanted common-mode current along the cable shield. Where no power need be transmitted, only digital data, the use of
fiber optics An optical fiber, or optical fibre in Commonwealth English, is a flexible, transparent fiber made by drawing glass (silica) or plastic to a diameter slightly thicker than that of a human hair. Optical fibers are used most often as a means t ...
can remove many ground loop problems, and sometimes safety problems too, but there are practical limitations. However, optical isolators or
optocouplers An opto-isolator (also called an optocoupler, photocoupler, or optical isolator) is an electronic component that transfers electrical signals between two isolated circuits by using light. Opto-isolators prevent high voltages from affecting the ...
are frequently used to provide ground loop isolation, and often safety isolation and the prevention of fault propagation.


Internal ground loops in equipment

Typically these are caused by poor design. Where there is mixed-signal technology on a
printed circuit board A printed circuit board (PCB; also printed wiring board or PWB) is a medium used in electrical and electronic engineering to connect electronic components to one another in a controlled manner. It takes the form of a laminated sandwich str ...
(PCB), e.g. analog, digital and possibly RF, it is usually necessary for a highly skilled engineer to specify the layout of where the grounds are to be interconnected. Typically the digital section will have its own
ground plane In electrical engineering, a ground plane is an electrically conductive surface, usually connected to electrical ground. The term has two different meanings in separate areas of electrical engineering. *In antenna theory, a ground plane is a ...
to obtain the necessary low inductance grounding and avoid ground bounce which can cause severe digital malfunction. But digital ground current must not pass through the analog grounding system, where voltage drop due to the finite ground impedance would cause noise to be injected into the analog circuits. Phase lock loop circuits are particularly vulnerable because the VCO loop filter circuit is working with sub-microvolt signals when the loop is locked, and any disturbance will cause frequency jitter and possible loss of lock. Generally, the analog and digital parts of the circuit are in separate areas of the PCB, with their own ground planes, and these are tied together at a carefully chosen star point. Where analog-to-digital converters (ADCs) are in use, the star point may have to be at or very close to the ground terminals of the ADC(s). Differential signal transmission, optical or transformer isolation, or fibre optic links, are also used in PCBs in extreme cases.


In circuit design

Ground and ground loops are also important in circuit design. In many circuits, large currents may exist through the ground plane, leading to voltage differences of the ground reference in different parts of the circuit, leading to hum and other problems. Several techniques should be used to avoid ground loops, and otherwise, guarantee good grounding: * The external shield, and the shields of all connectors, should be connected. ** If the power supply design is non-isolated, this external
chassis ground A chassis ground is a link between different metallic parts of a machine to ensure an electrical connection between them. Examples include electronic instruments and motor vehicles. Usages ; Electronics : Most electronic systems have their circuit ...
should be connected to the ground plane of the PCB at only one point; this avoids large current through the ground plane of the PCB. ** If the design is an isolated power supply, this external ground should be connected to the ground plane of the PCB via a high voltage capacitor, such as 2200 pF at 2 kV. ** If the connectors are mounted on the PCB, the outer perimeter of the PCB should contain a strip of copper connecting to the shields of the connectors. There should be a break in copper between this strip, and the main ground plane of the circuit. The two should be connected at only one point. This way, if there is a large current between connector shields, it will not pass through the ground plane of the circuit. * A star topology should be used for ground distribution, avoiding loops. * High-power devices should be placed closest to the power supply, while low-power devices can be placed farther from it. * Signals, wherever possible, should be differential. * Isolated power supplies require careful checking for parasitic, component, or internal PCB power plane capacitance that can allow AC present on input power or connectors to pass into the ground plane, or to any other internal signal. The AC might find a path back to its source via an I/O signal. While it can never be eliminated, it should be minimized as much as possible. The acceptable amount is implied by the design.