Fire damper
   HOME

TheInfoList



OR:

Fire dampers are
passive fire protection Passive fire protection (PFP) is components or systems of a building or structure that slows or impedes the spread of the effects of fire or smoke without system activation, and usually without movement. Examples of passive systems include floor- ...
products used in heating, ventilation, and
air conditioning Air conditioning, often abbreviated as A/C or AC, is the process of removing heat from an enclosed space to achieve a more comfortable interior environment (sometimes referred to as 'comfort cooling') and in some cases also strictly controlling ...
(HVAC) ducts to prevent the spread of fire inside the ductwork through fire-resistance rated walls and floors. Fire/smoke dampers are similar to fire dampers in fire resistance rating, and also prevent the spread of smoke inside the ducts. When a rise in temperature occurs, the fire damper closes, usually activated by a thermal element which melts at temperatures higher than ambient but low enough to indicate the presence of a fire, allowing springs to close the damper blades. Fire dampers can also close following receipt of an electrical signal from a fire alarm system utilising detectors remote from the damper, indicating the sensing of heat or smoke in the building occupied spaces or in the HVAC duct system. Regulations and
fire test A fire test is a means of determining whether fire protection products meet minimum performance criteria as set out in a building code or other applicable legislation. Successful tests in laboratories holding national accreditation for testing and ...
regimes vary from one country to another, which can result in different designs and applications.


Fire dampers for ducts


Mechanical dampers

Image:Deutsche_fsk_nicht_ami_bloedsinn.png, German fire damper in underground parking of a commercial building. Image:Fire and smoke dampers 1 of 3.jpg, North American fire dampers, ready for installation in Durasteel fire-resistance rated
pressurisation ductwork Pressurisation duct work is a passive fire protection system. It is used to supply fresh air to any area of refuge, designated emergency evacuation or egress route. Purpose The purpose of pressurisation ductwork is to maintain positive pressur ...
. Image:Fire and smoke dampers 2 of 3.jpg, Side view of
North America North America is a continent in the Northern Hemisphere and almost entirely within the Western Hemisphere. It is bordered to the north by the Arctic Ocean, to the east by the Atlantic Ocean, to the southeast by South America and the Car ...
n fire damper, showing the closing mechanism that shuts the interior blades. Image:FireDamper.png, European fire damper with interior fire-resisting board. Image:Fire damper clusterf.jpg, Fire damper in oversized hole in a 2-hour rated
concrete Concrete is a composite material composed of fine and coarse aggregate bonded together with a fluid cement (cement paste) that hardens (cures) over time. Concrete is the second-most-used substance in the world after water, and is the most wi ...
slab.
Mechanical dampers obstruct the cross-sectional area of a HVAC duct in the event of a fire either by means of a pivoting a fire-resistant board in Europe, or steel shutters in North America. Maintenance includes the function of the damper and removal of obstructions that may impair proper function.


Intumescent dampers

Image:Square_intumescent_damper.jpg, Intumescent damper insert. Openings in the unit swell shut as a result of intumescence in case of fire or heat exposure. Image:Round_intumescent_damper.jpg, Round intumescent damper insert. Intumescent dampers swell shut due to intumescence in the event of a fire. Unlike mechanical dampers, it is a physical/chemical reaction that causes closure. Cleaning and an age assessment are periodically performed. The annulus of an intumescent damper is closed eliminating smoke migration. Also, intumescent fire dampers can be qualified to ASTM E2912. or ISO 10294-5:2005 Fire dampers for air distribution systems—Part 5: Intumescent fire dampers. The purpose of some intumescent fire dampers is to prevent entry of airborne burning embers into buildings as a result of Wildlife Urban Interface Fires (WUI).US Fire Administration Page on its Wildland Urban Interface (WUI) toolkit
/ref>


Air transfer dampers

Air transfer fire dampers (ATFD) are not protected by ductwork and must therefore be installed and manufactured to standards and tests that take into account room fire exposures. Air transfer fire dampers are passive such as intumescent types or mechanical types. They are designed for fire resistance, direct flame resistance in the open state or for smoke resistance or for combinations. Some designs are for exterior use, some are for hygienic zone use and some are for Ex-zone applications. Depending on regional regulation, they are either tested to the same exposure as wall and floor building elements or tested slightly different such as for cable or pipe penetrations. In Europe, Sm or Sa classifications can be obtained for cold smoke resistance or cold and hot smoke resistance respectively. In the US, listing can be issued for use in wildfire exposure. Contrary to dampers in ducts the closing time of ATFDs are crucial to avoid fire passing during the open state. For applications where direct flame penetration is not allowed through openings that are normally in open state, ATFDs must pass adequate standards. In the US, ASTM E2912 verify direct flame resistance in the open state and ASTM E119 for closed state. Air transfer fire dampers for walls or floors are usually designed for flush installation and comes in multiple sizes. Dampers are listed for vertical or horizontal installation or both and for one- or two-way fire exposure. Performance may be fire rated resistance as the compartment they serve, with or without smoke resistance. In Europe, the harmonized ETAG 026 Part 4 apply to classification of ATFDs. Image:Air transfer element.JPG, Fire element for air transfer dampers for walls Image:Air transfer damper mounted in wall.jpg, Air transfer damper mounted in wall Air transfer fire dampers for doors are designed and tested for use in the lower part of door leaves and cannot be installed elsewhere or higher. In Europe, the fire door test EN 14600 and EN 1634-1 applies. Air transfer fire dampers in facades are vents applied in wall, eave soffit, gable or foundation. In the US, these are used to protect from exterior fire exposure from neighboring structure or via window-, arson- and wildfire (ASTM E2912 plus ASTM E119) or against wildfire only (ASTM E2886). In Europe, air transfer grilles for walls can be applied externally once a national assessment of suitability for the application in regards of embers, direct flame impingement, environmental impacts etc. has been done. Ventilating cavity fire barriers is a type of air transfer fire damper used in cavities or voids in constructions with natural ventilation, typically inside air gaps behind cladding. These are often subject to sudden direct flame impingement. In the US, ASTM E2912 cover testing, combined with E119 where required. A method to verify performance in the open state, similar to E2912, is being assessed in Europe by CEN. Image:Cavity vent transparent.png, Cavity barrier with instant fire stop Image:Mounted cavity barrier.JPG, Cavity barrier invisible behind cladding Dampers for ducts applied as air transfer dampers: Allowances exist for use of duct dampers as air transfer fire dampers. Since these typically will be too hot, and even allow penetration of flames to the unexposed side during fire, they must be modified and classified for such application. To achieve this they are tested with a grid on either side to prevent combustibles to be stored too close to hot parts or flaming. Some jurisdictions prescribe a general grid for use in front of listed duct dampers, which are not listed for use without ductwork.


Fire damper inspections and maintenance

In the US, the
Joint Commission The Joint Commission is a United States-based nonprofit tax-exempt 501(c) organization that accredits more than 22,000 US health care organizations and programs. The international branch accredits medical services from around the world. A majori ...
, State Fire Marshals and Other Authorities Having Jurisdiction (AHJ's), require some Fire and Smoke Dampers to be tested at specified intervals. Similarly, European authorities mandate maintenance and repairs of fire dampers also, as part of approvals or listings issued following successful testing of fire damper assemblies.


See also

*
Blast damper A blast damper is used to protect occupants and equipment of a structure against overpressures resultant of an explosion. The blast dampers normally protect air inlets and exhaust penetrations in an otherwise hardened structure. Blast dampers are ...
*
HVAC Heating, ventilation, and air conditioning (HVAC) is the use of various technologies to control the temperature, humidity, and purity of the air in an enclosed space. Its goal is to provide thermal comfort and acceptable indoor air quality. HV ...
*
Passive fire protection Passive fire protection (PFP) is components or systems of a building or structure that slows or impedes the spread of the effects of fire or smoke without system activation, and usually without movement. Examples of passive systems include floor- ...
*
Active fire protection Active fire protection (AFP) is an integral part of fire protection. AFP is characterized by items and/or systems, which require a certain amount of motion and response in order to work, contrary to passive fire protection. Categories of active fi ...
*
Fire test A fire test is a means of determining whether fire protection products meet minimum performance criteria as set out in a building code or other applicable legislation. Successful tests in laboratories holding national accreditation for testing and ...
*
Listing and approval use and compliance Listing and approval use and compliance is the practice of installing and operating safety-related products and materials in accordance with to minimum performance conformance testing requirements. The conformance could be for a certification lis ...
*
Sheet metal Sheet metal is metal formed into thin, flat pieces, usually by an industrial process. Sheet metal is one of the fundamental forms used in metalworking, and it can be cut and bent into a variety of shapes. Thicknesses can vary significantly; ex ...
*
Uniform Mechanical Code The Uniform Mechanical Code (UMC) is a model code developed by the International Association of Plumbing and Mechanical Officials (IAPMO) to govern the installation, inspection and maintenance of HVAC (heating, ventilating and air-conditioning) ...


References


External links


NFPA Xchange site on comparison of UL555(S) versus DIN4102 qualified fire dampers, including video linkUL fire damper guidelineAbstract on UL555s Standard for Smoke DampersUL Marking and Application Guide for Dampers
* ttp://www.astm.org/Standards/E2912.htm ASTM E2912 Standard Test Method for Fire Test of Non-Mechanical Fire Dampers Used in Vented Constructionbr>ASTM E2886 Access Portal: Standard Test Method for Evaluating the Ability of Exterior Vents to Resist the Entry of Embers and Direct Flame ImpingementNFPA 80 Access Portal: Standard for Fire Doors and Other Opening ProtectivesNFPA 90A Access: Standard for the Installation of Air-Conditioning and Ventilating SystemsNFPA 105 Access: Standard for the Installation of Smoke Door Assemblies and Other Opening ProtectivesSMACNA - Fire, Smoke, and Radiation Damper Installation Guide for HVAC (for purchase)14600 Access Portal: Doorsets and openable windows with fire resisting and/or smoke control characteristics - Requirements and classificationEN 1634-1 Access Portal: Fire resistance and smoke control tests for door and shutter assemblies, openable windows and elements of building hardware - Part 1: Fire resistance test for door and shutter assemblies and openable windowsAbstract DIN EN 15650:2010-09 Ventilation for buildings - Fire dampers; German version EN 15650:2010Abstract DIN EN 15882-2:2010-11 Extended application of results from fire resistance tests for service installations - Part 2 - Dampers; German version prEN 15882-2:2010Excerpt Scheuermann, Praxishandbuch Brandschutz (Practice Handbook Fire Protection, Paragraph 5.5.4 Fire Dampers), 2008Access to DIN EN 1366-2:1999-10 (replaces DIN4102 Part 6) Fire resistance tests on service installations - Part 2: Fire dampers; German version EN 1366-2:1999
* ttp://www.iso.org/iso/home/store/catalogue_tc/catalogue_detail.htm?csnumber=37675 Abstract ISO 10294-5:2005 Fire dampers for air distribution systems -- Part 5: Intumescent fire dampers Heating, ventilation, and air conditioning Passive fire protection Active fire protection {{HVAC