Transient Recovery Voltage
   HOME

TheInfoList



OR:

A transient recovery voltage (TRV) for high-voltage
circuit breakers A circuit breaker is an electrical safety device designed to protect an electrical circuit from damage caused by an overcurrent or short circuit. Its basic function is to interrupt current flow to protect equipment and to prevent the risk ...
is the
voltage Voltage, also known as electric pressure, electric tension, or (electric) potential difference, is the difference in electric potential between two points. In a static electric field, it corresponds to the work needed per unit of charge to ...
that appears across the terminals after current interruption. It is a critical parameter for fault interruption by a high-voltage circuit breaker, its characteristics (amplitude, rate of rise) can lead either to a successful current interruption or to a failure (called reignition or restrike). The TRV is dependent on the characteristics of the system connected on both terminals of the circuit-breaker, and on the type of fault that this circuit breaker has to interrupt (single, double or three-phase faults, grounded or ungrounded fault ..). Characteristics of the system include: * type of neutral (effectively grounded, ungrounded, solidly grounded ..) * type of load (capacitive, inductive, resistive) * type of connection: cable connected, line connected.. The most severe TRV is applied on the first pole of a circuit-breaker that interrupts current (called the first-pole-to-clear in a three-phase system). The parameters of TRVs are defined in international standards such as IEC and
IEEE The Institute of Electrical and Electronics Engineers (IEEE) is a 501(c)(3) professional association for electronic engineering and electrical engineering (and associated disciplines) with its corporate office in New York City and its operat ...
(or
ANSI The American National Standards Institute (ANSI ) is a private non-profit organization that oversees the development of voluntary consensus standards for products, services, processes, systems, and personnel in the United States. The organi ...
).


Capacitive load

Typical cases of capacitive loads are unloaded lines and capacitor banks.


Inductive circuit


Terminal fault

A terminal fault is a fault that occurs at the circuit breaker terminals. The circuit breaker interrupts a short-circuit at current zero, at this instant the supply voltage is maximum and the recovery voltage tends to reach the supply voltage with a high frequency transient. The normalized value of the overshoot or amplitude factor is 1.4.


Short-line-fault

A short-line-fault is a fault that occurs on a line a few hundred meters to several kilometers down the line from the circuit breaker terminal. As shown on Figure 5, the TRV is characterized, in its initial part, by a steep rate-of-rise due to a high-frequency oscillation produced by travelling waves that travel on the line with positive and negative reflections at the circuit breaker terminal and at the fault point, respectively. The superposition of these travelling waves gives the voltage profiles on the line shown on Figures 6 to 14 with, on the horizontal axis, the circuit breaker terminal position on the left and the short-circuit point on the right. The voltage profile is given at different instants after current interruption, where TL is time needed for a wave to travel from the circuit breaker down the line and back to the circuit breaker terminal. Figure 15 shows, as function of time, the variation of voltage on the line-side terminal of the circuit breaker. The voltage variation is two times the initial voltage if losses are neglected, in reality it is approximately 1.6 times the initial voltage. The triangular waveshape of voltage on the line-side terminal, combined with a supply-side voltage variation at a lower frequency, produces the sawtooth variation of TRV shown on Figure 5. A short-line-fault TRV is characterized by a rate-of-rise that is proportional to the slope of current at the time of interruption and therefore to the amplitude of the short-circuit current : \frac = Z\,, where ''Z'' is the surge impedance of the line. The standardized value of ''Z'' is 450 Ω, it is equal to \sqrt (l/c)\,, where ''l'' and ''c'' are the line self-inductance and capacitance per unit length.


Out-of-phase condition


References

{{reflist *This article is a partial translation of the French version: Tension transitoire de rétablissement.


External links


''IEEE Switchgear Committee Tutorial 2008: Transient Recovery Voltages (TRV) for High Voltage Circuit Breakers, D. Dufournet''
on ewh.ieee.org
''TRV for High-voltage circuit breakers''
IEEE tutorial by R.Alexander & D.Dufournet, on ewh.ieee.org Electrical systems Electric power distribution