History
Records of solar collectors in the United States date to before 1900,Solar Evolution – The History of Solar EnergyMediterranean
Israel, Cyprus and Greece are the ''per capita'' leaders in the use of solar water heating systems supporting 30%–40% of homes. Flat plate solar systems were perfected and used on a large scale in Israel. In the 1950s a fuel shortage led the government to forbid heating water between 10 pm and 6 am. Levi Yissar built the first prototype Israeli solar water heater and in 1953 he launched the NerYah Company, Israel's first commercial manufacturer of solar water heating. Solar water heaters were used by 20% of the population by 1967. Following the energy crisis in the 1970s, in 1980 Israel required the installation of solar water heaters in all new homes (except high towers with insufficient roof area). As a result, Israel became the world leader in the use of solar energy ''per capita'' with 85% of households using solar thermal systems (3% of the primary national energy consumption), estimated to save the country of oil a year.Israeli Section of the International Solar Energy SocietyAsia
After 1960, systems were marketed in Japan. Australia has a variety of national and state and regulations for solar thermal starting with MRET in 1997. Solar water heating systems are popular in China, where basic models start at around 1,500 yuan (US$235), around 80% less than in Western countries for a given collector size. At least 30 million Chinese households have one. The popularity is due to efficient evacuated tubes that allow the heaters to function even under gray skies and at temperatures well below freezing.Design requirements
The type, complexity and size of a solar water heating system is mostly determined by: * Changes in ambient temperature and solar radiation between summer and winter * Changes in ambient temperature during the day-night cycle * Possibility of the potable water or collector fluid overheating or freezing The minimum requirements of the system are typically determined by the amount or temperature of hot water required during winter, when a system's output and incoming water temperature are typically at their lowest. The maximum output of the system is determined by the need to prevent the water in the system from becoming too hot.Freeze protection
Freeze protection measures prevent damage to the system due to the expansion of freezing transfer fluid. Drainback systems drain the transfer fluid from the system when the pump stops. Many indirect systems use antifreeze (e.g.,Overheat protection
When no hot water has been used for a day or two, the fluid in the collectors and storage can reach high temperatures in all non-"drainback" systems. When the storage tank in a "drainback" system reaches its desired temperature, the pumps stop, ending the heating process and thus preventing the storage tank from overheating. Some active systems deliberately cool the water in the storage tank by circulating hot water through the collector at times when there is little sunlight or at night, losing heat. This is most effective in direct or thermal store plumbing and is virtually ineffective in systems that use evacuated tube collectors, due to their superior insulation. Any collector type may still overheat. High pressure, sealed solar thermal systems ultimately rely on the operation of temperature and pressure relief valves. Low pressure, open vented heaters have simpler, more reliable safety controls, typically an open vent.Structure And Working
Simple designs include a simple glass-topped insulated box with a flat solar absorber made of dark-colored sheet metal, attached to copper heat exchanger pipes, or a set of metal tubes surrounded by an evacuated (near vacuum) glass cylinder. In industrial cases aHeat transfer
Direct
''Direct'' or ''open loop'' systems circulate potable water through the collectors. They are relatively cheap. Drawbacks include: * They offer little or no overheat protection unless they have a heat export pump. * They offer little or no freeze protection, unless the collectors are freeze-tolerant. * Collectors accumulate scale in hard water areas, unless an ion-exchange softener is used. The advent of freeze-tolerant designs expanded the market for SWH to colder climates. In freezing conditions, earlier models were damaged when the water turned to ice, rupturing one or more components.Indirect
''Indirect'' or ''closed loop'' systems use a heat exchanger to transfer heat from the "heat-transfer fluid" (HTF) fluid to the potable water. The most common HTF is an antifreeze/water mix that typically uses non-toxicPropulsion
Passive
''Passive'' systems rely on heat-driven convection or heat pipes to circulate the working fluid. Passive systems cost less and require low or no maintenance, but are less efficient. Overheating and freezing are major concerns.Active
''Active'' systems use one or more pumps to circulate water and/or heating fluid''.'' This permits a much wider range of system configurations. Pumped systems are more expensive to purchase and to operate. However, they operate at higher efficiency and can be more easily controlled. Active systems have controllers with features such as interaction with a backup electric or gas-driven water heater, calculation and logging of the energy saved, safety functions, remote access and informative displays.Passive direct systems
An ''integrated collector storage'' (ICS or batch heater) system uses a tank that acts as both storage and collector. Batch heaters are thin rectilinear tanks with a glass side facing the sun at noon. They are simple and less costly than plate and tube collectors, but they may require bracing if installed on a roof (to support lbs of water), suffer from significant heat loss at night since the side facing the sun is largely uninsulated and are only suitable in moderate climates. A ''convection heat storage unit'' (CHS) system is similar to an ICS system, except the storage tank and collector are physically separated and transfer between the two is driven by convection. CHS systems typically use standard flat-plate type or evacuated tube collectors. The storage tank must be located above the collectors for convection to work properly. The main benefit of CHS systems over ICS systems is that heat loss is largely avoided since the storage tank can be fully insulated. Since the panels are located below the storage tank, heat loss does not cause convection, as the cold water stays at the lowest part of the system.Active indirect systems
''Pressurized antifreeze'' systems use a mix of antifreeze (almost always low-toxic propylene glycol) and water mix for HTF in order to prevent freeze damage. Though effective at preventing freeze damage, antifreeze systems have drawbacks: * If the HTF gets too hot the glycol degrades into acid and then provides no freeze protection and begins to dissolve the solar loop's components. * Systems without drainback tanks must circulate the HTF – regardless of the temperature of the storage tank – to prevent the HTF from degrading. Excessive temperatures in the tank cause increased scale and sediment build-up, possible severe burns if a tempering valve is not installed, and if used for storage, possible thermostat failure. * The glycol/water HTF must be replaced every 3–8 years, depending on the temperatures it has experienced. * Some jurisdictions require more-expensive, double-walled heat exchangers even though propylene glycol is low-toxic. * Even though the HTF contains glycol to prevent freezing, it circulates hot water from the storage tank into the collectors at low temperatures (e.g. below ), causing substantial heat loss. A ''drainback system'' is an active indirect system where the HTF (usually pure water) circulates through the collector, driven by a pump. The collector piping is not pressurized and includes an open drainback reservoir that is contained in conditioned or semi-conditioned space. The HTF remains in the drainback reservoir unless the pump is operating and returns there (emptying the collector) when the pump is switched off. The collector system, including piping, must drain via gravity into the drainback tank. Drainback systems are not subject to freezing or overheating. The pump operates only when appropriate for heat collection, but not to protect the HTF, increasing efficiency and reducing pumping costs.Do-it-yourself (DIY)
Plans for solar water heating systems are available on the Internet. DIY SWH systems are usually cheaper than commercial ones, and they are used both in the developed and developing world.Comparison
Components
Collector
Solar thermal collectors capture and retain heat from the sun and use it to heat a liquid. Two important physical principles govern the technology of solar thermal collectors: * Any hot object ultimately returns to thermal equilibrium with its environment, due to heat loss fromFlat plate solar
Flat plate collectors are an extension of the idea to place a collector in an 'oven'-like box with glass directly facing the Sun. Most flat plate collectors have two horizontal pipes at the top and bottom, called headers, and many smaller vertical pipes connecting them, called risers. The risers are welded (or similarly connected) to thin absorber fins. Heat-transfer fluid (water or water/antifreeze mix) is pumped from the hot water storage tank or heat exchanger into the collectors' bottom header, and it travels up the risers, collecting heat from the absorber fins, and then exits the collector out of the top header. Serpentine flat plate collectors differ slightly from this "harp" design, and instead use a single pipe that travels up and down the collector. However, since they cannot be properly drained of water, serpentine flat plate collectors cannot be used in drainback systems. The type of glass used in flat plate collectors is almost always low-iron, tempered glass. Such glass can withstand significant hail without breaking, which is one of the reasons that flat-plate collectors are considered the most durable collector type. Unglazed or formed collectors are similar to flat-plate collectors, except they are not thermally insulated nor physically protected by a glass panel. Consequently, these types of collectors are much less efficient when water temperature exceeds ambient air temperatures. For pool heating applications, the water to be heated is often colder than the ambient roof temperature, at which point the lack of thermal insulation allows additional heat to be drawn from the surrounding environment.Evacuated tube
Evacuated tube collectors (ETC) are a way to reduce the heat loss, inherent in flat plates. Since heat loss due to convection cannot cross a vacuum, it forms an efficient isolation mechanism to keep heat inside the collector pipes. Since two flat glass sheets are generally not strong enough to withstand a vacuum, the vacuum is created between two concentric tubes. Typically, the water piping in an ETC is therefore surrounded by two concentric tubes of glass separated by a vacuum that admits heat from the sun (to heat the pipe) but that limits heat loss. The inner tube is coated with a thermal absorber. Vacuum life varies from collector to collector, from 5 years to 15 years. Flat plate collectors are generally more efficient than ETC in full sunshine conditions. However, the energy output of flat plate collectors is reduced slightly more than ETCs in cloudy or extremely cold conditions. Most ETCs are made out of annealed glass, which is susceptible toPump
PV pump
One way to power an active system is via aBubble pump
A bubble pump (also known as geyser pump) is suitable for flat panel as well as vacuum tube systems. In a bubble pump system, the closed HTF circuit is under reduced pressure, which causes the liquid to boil at low temperature as the sun heats it. The steam bubbles form a geyser, causing an upward flow. The bubbles are separated from the hot fluid and condensed at the highest point in the circuit, after which the fluid flows downward toward the heat exchanger caused by the difference in fluid levels. The HTF typically arrives at the heat exchanger at 70 °C and returns to the circulating pump at 50 °C. Pumping typically starts at about 50 °C and increases as the sun rises until equilibrium is reached.Controller
A ''differential controller'' senses temperature differences between water leaving the solar collector and the water in the storage tank near the heat exchanger. The controller starts the pump when the water in the collector is sufficiently about 8–10 °C warmer than the water in the tank, and stops it when the temperature difference reaches 3–5 °C. This ensures that stored water always gains heat when the pump operates and prevents the pump from excessive cycling on and off. (In direct systems the pump can be triggered with a difference around 4 °C because they have no heat exchanger.)Tank
The simplest collector is a water-filled metal tank in a sunny place. The sun heats the tank. This was how the first systems worked. This setup would be inefficient due to the equilibrium effect: as soon as heating of the tank and water begins, the heat gained is lost to the environment and this continues until the water in the tank reaches ambient temperature. The challenge is to limit the heat loss. * The storage tank can be situated lower than the collectors, allowing increased freedom in system design and allowing pre-existing storage tanks to be used. * The storage tank can be hidden from view. * The storage tank can be placed in conditioned or semi-conditioned space, reducing heat loss. * Drainback tanks can be used.Insulated tank
ICS or batch collectors reduce heat loss by thermally insulating the tank. This is achieved by encasing the tank in a glass-topped box that allows heat from the sun to reach the water tank. The other walls of the box are thermally insulated, reducing convection and radiation. The box can also have a reflective surface on the inside. This reflects heat lost from the tank back towards the tank. In a simple way one could consider an ICS solar water heater as a water tank that has been enclosed in a type of 'oven' that retains heat from the sun as well as heat of the water in the tank. Using a box does not eliminate heat loss from the tank to the environment, but it largely reduces this loss. Standard ICS collectors have a characteristic that strongly limits the efficiency of the collector: a small surface-to-volume ratio. Since the amount of heat that a tank can absorb from the sun is largely dependent on the surface of the tank directly exposed to the sun, it follows that the surface size defines the degree to which the water can be heated by the sun. Cylindrical objects such as the tank in an ICS collector have an inherently small surface-to-volume ratio. Collectors attempt to increase this ratio for efficient warming of the water. Variations on this basic design include collectors that combine smaller water containers and evacuated glass tube technology, a type of ICS system known as an Evacuated Tube Batch (ETB) collector.Applications
Evacuated tube
ETSCs can be more useful than other solar collectors during winter season. ETCs can be used for heating and cooling purposes in industries like pharmaceutical and drug, paper, leather and textile and also for residential houses, hospitals, nursing home, hotels, swimming pool etc. An ETC can operate at a range of temperatures from medium to high for solar hot water, swimming pool, air conditioning and solar cooker. ETCs higher operational temperature range (up to ) makes them suitable for industrial applications such as steam generation, heat engine and solar drying.Swimming pools
Floating pool covering systems and separate STCs are used for pool heating. Pool covering systems, whether solid sheets or floating disks, act as insulation and reduce heat loss. Much heat loss occurs through evaporation, and using a cover slows evaporation. STCs for nonpotable pool water use are often made of plastic. Pool water is mildly corrosive due to chlorine. Water is circulated through the panels using the existing pool filter or supplemental pump. In mild environments, unglazed plastic collectors are more efficient as a direct system. In cold or windy environments evacuated tubes or flat plates in an indirect configuration are used in conjunction with a heat exchanger. This reduces corrosion. A fairly simple differential temperature controller is used to direct the water to the panels or heat exchanger either by turning a valve or operating the pump. Once the pool water has reached the required temperature, a diverter valve is used to return water directly to the pool without heating. Many systems are configured as drainback systems where the water drains into the pool when the water pump is switched off. The collector panels are usually mounted on a nearby roof, or ground-mounted on a tilted rack. Due to the low temperature difference between the air and the water, the panels are often formed collectors or unglazed flat plate collectors. A simple rule-of-thumb for the required panel area needed is 50% of the pool's surface area. This is for areas where pools are used in the summer season only. Adding solar collectors to a conventional outdoor pool, in a cold climate, can typically extend the pool's comfortable usage by months and more if an insulating pool cover is used. When sized at 100% coverage most solar hot water systems are capable of heating a pool anywhere from as little as 4 °C for a wind-exposed pool, to as much as 10 °C for a wind-sheltered pool covered consistently with a solar pool blanket. An active solar energy system analysis program may be used to optimize the solar pool heating system before it is built.Energy production
The amount of heat delivered by a solar water heating system depends primarily on the amount of heat delivered by the sun at a particular place (Costs
In sunny, warm locations, where freeze protection is not necessary, an ICS (batch type) solar water heater can be cost effective. In higher latitudes, design requirements for cold weather add to system complexity and cost. This increases ''initial'' costs, but not life-cycle costs. The biggest single consideration is therefore the large initial financial outlay of solar water heating systems. Offsetting this expense can take years. The payback period is longer in temperate environments. Since solar energy is free, operating costs are small. At higher latitudes, solar heaters may be less effective due to lower insolation, possibly requiring larger and/or dual-heating systems. In some countries government incentives can be significant. Cost factors (positive and negative) include: * Price of solar water heater (more complex systems are more expensive) * Efficiency * Installation cost * Electricity used for pumping * Price of water heating fuel (e.g. gas or electricity) saved per kWh * Amount of water heating fuel used * Initial and/or recurring government subsidy * Maintenance cost (e.g. antifreeze or pump replacements) * Savings in maintenance of conventional (electric/gas/oil) water heating system Payback times can vary greatly due to regional sun, extra cost due to frost protection needs of collectors, household hot water use etc. For instance in central and southern Florida the payback period could easily be 7 years or less rather than the 12.6 years indicated on the chart for the United States. The payback period is shorter given greater insolation. However, even in temperate areas, solar water heating is cost effective. The payback period for photovoltaic systems has historically been much longer. Costs and payback period are shorter if no complementary/backup system is required. thus extending the payback period of such a system.Subsidies
Australia operates a system of Renewable Energy Credits, based on national renewable energy targets. The Toronto Solar Neighbourhoods Initiative offers subsidies for the purchase of solar water heating units.Energy footprint and life cycle assessment
Energy footprint
The source of electricity in an active SWH system determines the extent to which a system contributes to atmospheric carbon during operation. Active solar thermal systems that use mains electricity to pump the fluid through the panels are called 'low carbon solar'. In most systems the pumping reduces the energy savings by about 8% and the carbon savings of the solar by about 20%. However, low power pumps operate with 1-20W. Assuming a solar collector panel delivering 4 kWh/day and a pump running intermittently from mains electricity for a total of 6 hours during a 12-hour sunny day, the potentially negative effect of such a pump can be reduced to about 3% of the heat produced. However, PV-powered active solar thermal systems typically use a 5–30 W PV panel and a small, low powerLife cycle energy assessment
Recognised standards can be used to deliver robust and quantitative life cycle assessments (LCA). LCA considers the financial and environmental costs of acquisition of raw materials, manufacturing, transport, using, servicing and disposal of the equipment. Elements include: * Financial costs and gains * Energy consumption * CO2 and other emissions In terms of energy consumption, some 60% goes into the tank, with 30% towards the collector (thermosiphon flat plate in this case). In Italy, some 11 giga-joules of electricity are used in producing SWH equipment, with about 35% goes toward the tank, with another 35% towards the collector. The main energy-related impact is emissions. The energy used in manufacturing is recovered within the first 2–3 years of use (in southern Europe). By contrast the energy payback time in the UK is reported as only 2 years. This figure was for a direct system, retrofitted to an existing water store, PV pumped, freeze tolerant and of 2.8 sqm aperture. For comparison, a PV installation took around 5 years to reach energy payback, according to the same comparative study. In terms of CO2 emissions, a large fraction of the emissions saved is dependent on the degree to which gas or electricity is used to supplement the sun. Using the Eco-indicator 99 points system as a yardstick (i.e. the yearly environmental load of an average European inhabitant) in Greece, a purely gas-driven system may have fewer emissions than a solar system. This calculation assumes that the solar system produces about half of the hot water requirements of a household. But because methane (CH4) emissions from the natural gas fuel cycle dwarf the greenhouse impact of CO2, the netSystem specification and installation
* Most SWH installations require backup heating. * The amount of hot water consumed each day must be replaced and heated. In a solar-only system, consuming a high fraction of the water in the reservoir implies significant reservoir temperature variations. The larger the reservoir the smaller the daily temperature variation. * SWH systems offer significant scale economies in collector and tank costs. Thus the most economically efficient scale meets 100% of the heating needs of the application. * Direct systems (and some indirect systems using heat exchangers) can be retrofitted to existing stores. * Equipment components must be insulated to achieve full system benefits. The installation of efficient insulation significantly reduces heat loss. * The most efficient PV pumps start slowly in low light levels, so they may cause a small amount of unwanted circulation while the collector is cold. The controller must prevent stored hot water from this cooling effect. * Evacuated tube collector arrays can be adjusted by removing/adding tubes or their heat pipes, allowing customization during/after installation. * Above 45 degrees latitude, roof mounted sun-facing collectors tend to outproduce wall-mounted collectors. However, arrays of wall-mounted steep collectors can sometimes produce more useful energy because gains in used energy in winter can offset the loss of unused (excess) energy in summer.Standards
Europe
*EN 806: Specifications for installations inside buildings conveying water for human consumption. General. *EN 1717: Protection against pollution of potable water in water installations and general requirements of devices to prevent pollution by backflow. * EN 60335: Specification for safety of household and similar electrical appliances. (2–21) * UNE 94002:2005 Thermal solar systems for domestic hot water production. Calculation method for heat demand.United States
*OG-300: OG-300 Certification of Solar Water Heating Systems.Canada
Australia
*Renewable Energy (Electricity) Act 2000 *Renewable Energy (Electricity) (Large-scale Generation Shortfall Charge) Act 2000 *Renewable Energy (Electricity) (Small-scale Technology Shortfall Charge) Act 2010 *Renewable Energy (Electricity) Regulations 2001 *Renewable Energy (Electricity) Regulations 2001 - STC Calculation Methodology for Solar Water Heaters and air source heat pump Water Heaters *Renewable Energy (Electricity) Amendment (Transitional Provision) Regulations 2010 *Renewable Energy (Electricity) Amendment (Transitional Provisions) Regulations 2009 All relevant participants of the Large-scale Renewable Energy Target and Small-scale Renewable Energy Scheme must comply with the above Acts.Worldwide use
European Union
See also
* Concentrating solar power * Passive solar * Renewable energy commercialization * Renewable heat * Renewable Energy Certificate (United States) *References
External links