Steiner Tunnel Test
   HOME

TheInfoList



OR:

The Steiner tunnel test is a widely used method of testing building interior wall and ceiling finishes for their ability to support and propagate fire, and for their tendency to emit smoke. The test was developed in 1944 by Al Steiner of Underwriters Laboratories, and has been incorporated as a reference into North American standards for materials testing as tests
ASTM ASTM International, formerly known as American Society for Testing and Materials, is an international standards organization that develops and publishes voluntary consensus technical standards for a wide range of materials, products, systems, an ...
E84, NFPA255, UL723 and ULCS102. These standards are in widespread use for the regulation and selection of materials for interior building construction throughout North America. The test may be carried out inside a dedicated, instrumented test apparatus. The test itself involves an assembly of the tested material, fabricated into an otherwise noncombustible horizontal box or tunnel as the tunnel's roof, in a section long and wide. The tunnel is as wide and long as the test specimen, and high. The apparatus is equipped with two gas burners providing a flame intensity of 89 kilowatts, and air and combustion products are moved through the tunnel by a ventilation system at a controlled velocity of per minute. The progress of the flame front across the test material is measured by visual observation, while the smoke emitted from the end of the test assembly is measured as a factor of optical density. A flame spread index (FSI) and a
smoke-developed index Smoke-developed index (abbreviated SDI) is a measure of the concentration of smoke a material emits as it burns. Like the Flame Spread Index, it is based on an arbitrary scale in which asbestos-cement board has a value of 0, and red oak wood has 10 ...
are calculated from these results. Both indices use an arbitrary scale in which
asbestos-cement Asbestos cement, genericized as fibro, fibrolite (short for "fibrous (or fibre) cement sheet") or AC sheet, is a building material in which asbestos fibres are used to reinforce thin rigid cement sheets. Although invented at the end of the 19t ...
board has a value of 0, and red oak wood has 100. The tunnel test does not measure the ignitability of materials, nor does it properly assess the behavior of thermoplastic materials which may tend to melt and drip from the assembly, or for materials with slow flame spread properties. It likewise does not give a true assessment of the smoke emanating from very thin materials. Other tests, such as the "critical radiant flux" test (ASTM E648/NFPA 253) are more suitable for establishing ignitability. The " methenamine pill test" (ASTM D 2859) is used to judge the ignitability of flooring carpet.


See also

* Flammability *
Fire test A fire test is a means of determining whether fire protection products meet minimum performance criteria as set out in a building code or other applicable legislation. Successful tests in laboratories holding national accreditation for testing and ...
*
Fire-safe polymers Fire-safe polymers are polymers that are resistant to degradation at high temperatures. There is need for fire-resistant polymers in the construction of small, enclosed spaces such as skyscrapers, boats, and airplane cabins.Zhang, H. ''Fire-Safe Po ...


References

{{Use dmy dates, date=March 2012 Fire test standards