Electrical safety testing is essential to make sure electrical products and electrical installations are safe. To meet this goal, governments and various technical bodies have developed electrical safety standards. All countries have their own electrical
safety standards Safety standards are standards designed to ensure the safety of products, activities and processes, etc. They may be advisory or compulsory and are normally laid down by an advisory or regulatory body that may be either voluntary or statutory. In ...
that must be complied with. To meet to these standards, electrical products and electrical installations must pass electrical safety tests. Some types of electrical safety tests include: *
dielectric withstand test A dielectric withstand test (or pressure test, high potential or hipot test) is an electrical test performed on a component or product to determine the effectiveness of its insulation. The test may be between mutually insulated sections of a part ...
(also called a hipot test) *insulation resistance test (IR test) *earth continuity test *leakage current test Electrical safety tests are described in IEC 60335, IEC 61010,
AS/NZS 3000 Electrical wiring is an electrical installation of cabling and associated devices such as switches, distribution boards, sockets, and light fittings in a structure. Wiring is subject to safety standards for design and installation. Allowable ...
, NFPA 70,
BS 7671 British Standard BS 7671 "Requirements for Electrical Installations. IET Wiring Regulations", informally called in the UK electrical community "The Regs", is the national standard in the United Kingdom for electrical installation and the safet ...
, and other national and international standards.\


Electrical Safety tests


Dielectric voltage withstand test

A dielectric voltage withstand test (also known as a hipot test) is done by applying a voltage higher than operating
voltage Voltage, also known as electric pressure, electric tension, or (electric) potential difference, is the difference in electric potential between two points. In a static electric field, it corresponds to the work needed per unit of charge to ...
to the device or installation under test. In this test, the electric insulation of a product or installation is put under a voltage stress much higher than its normal operating voltage. If the hipot test is done for
type testing Conformance testing — an element of conformity assessment, and also known as compliance testing, or type testing — is testing or other activities that determine whether a process, product, or service complies with the requirements of a specific ...
purposes, a much larger voltage may be applied.


Insulation resistance test (IR test)

An insulation resistance test (IR test) measures the
electrical resistance The electrical resistance of an object is a measure of its opposition to the flow of electric current. Its reciprocal quantity is , measuring the ease with which an electric current passes. Electrical resistance shares some conceptual paralle ...
of insulation by applying a voltage between two locations, and measuring the resultant current flow. Proper safety precautions must be taken when doing this test, such as exclusion zones, making sure no wires are exposed, and personal protective equipment is worn. To do this test, you need to have an insulation resistance tester, which may be a small hand held battery powered device, up to a larger luggage sized tool able to achieve higher test voltages. Variables to choose before starting an electrical resistance test is the test voltage, test duration, and test points. Acceptable values of insulation resistance vary depending on circuit purpose, industry, and country. Typically, standards will dictate acceptable values. An insulation resistance test can be used for simple go/no-go testing, or for periodic condition assessment, where routine insulation resistance tests are performed, with the results tracked over time. By tracking the insulation resistance of a circuit over time, preventative maintenance may be able to be planned before equipment failure. Insulation resistance is dependent on temperature and humidity variations, therefore the temperature and humidity should be recorded when testing and compensation applied to the measured value given. Many standards and safety agencies have specified the insulation resistance test as a required test for electrical installations and electrical products. This test may be referred to as "meggering', after the company Megger was one of the first companies to commercialize an insulation resistance test meter. These days, many other brands are widely available.


Earth Continuity Test

An earth continuity test checks if a metal part is connected to earth. The resistance of the connection to earth can also be measured.


Leakage Current Test

A leakage current test detects current that does not flow back through the circuit. This test may be used as part of testing GFCI or RCD operation.


Electrical Safety test categories

Visual inspection: A survey without touching anything, and looking at the electrical installation or product before starting any electrical testing. A visual inspection seeks to identify damaged insulation, disconnected wires, incorrect installation, and any other visual issues. Non-live testing Continuity test: a test to check the wiring is correct Earth continuity test: this test is to make sure the earthing system is properly connected Live testing Earth fault loop impedance testing: this test is to check that if a fault did occur, that the system meets requirements to cause a disconnection of the supply within the time limit specified by standards Insulation resistance testing Polarity test: a test to check that the connections are connected in the right sequence RCD testing: on modern electrical systems RCD's and RCBO's are regularly fitted, these devices react to electricity leaking from the circuit. Leakage may happen when a person touches live parts, which can cause electricity to passes through their body instead of the normal circuit return path.


UK specific information


Electrical Installation Condition Report

The competent person will then issue an Electrical Installation Condition Report (EICR), also known as Periodic Inspection and Testing Report (PIR), detailing any observed damage, deterioration, defects, dangerous conditions and any non-compliances with the current safety standard which might give rise to danger. If anything dangerous or potentially dangerous is found, the overall condition of the electrical installation will be declared to be 'unsatisfactory', meaning that remedial action is required without delay to remove the risks to those in the premises. A typical classification of faults found is: *C1 – Danger present. Risk of injury. Immediate remedial action required. *C2 – Potentially dangerous. Urgent remedial action required. *C3 – Improvement recommended. *FI – Further investigation required.


Means Of Protection (MOP)

The concept is that no one means of protection should be totally necessary to the device's safety, so that the failure of one should not make the device immediately dangerous. MOP is further divided into MOOP and MOPP.


Means Of Operator Protection (MOOP)

A concept introduced in the standard for medical electrical equipment IEC 60601-1.


Means of Patient Protection (MOPP)

Electrical safety standard set forward by standards organizations across the globe such as the American National Standards Institute (ANSI),
Canadian Standards Association The CSA Group (formerly the Canadian Standards Association; CSA) is a standards organization which develops standards in 57 areas. CSA publishes standards in print and electronic form, and provides training and advisory services. CSA is composed ...
, and European Commission in IEC60601-1. MOPP safety standards aim to set basic safety requirements for medical electrical equipment. "With hazardous voltages present in a system a robust and reliable approach to isolation is needed such that multiple and un-related insulation system failures would need to occur before an operator or patient is put at risk. To achieve this, two independent measures of protection are required or a single measure of physical isolation such as
creepage An electrical insulator is a material in which electric current does not flow freely. The atoms of the insulator have tightly bound electrons which cannot readily move. Other materials—semiconductors and conductors—conduct electric current ...
/clearance or solid insulation deemed equivalent." In addition to the insulation of the device being powered the additional main points the organizations have set forward with the implementation of the MOPP standards are: * Leakage current requirements. ** The maximum allowable patient leakage current is 500µA AC and 50µA DC in normal operation (normal condition, NC) and 1000µA AC or 100µA DC in single failure condition (SFC). * Requirements for the input stage. * Temperature measurement and requirements. * Printed circuit board (PCB) thickness requirements for multilayered boards. ** The distance for insulation thickness of 0.4 mm or three layers of insulation foil (Prepreg) are acceptable for reinforced insulation. * Dielectric testing. * Maximum output energy * Enclosure and mechanical fire requirements Example Example showing the differences between the isolation and creepage requirements for MOOP and MOPP.