HOME

TheInfoList



OR:

IEC 61000-4-5 is an international standard by the
International Electrotechnical Commission The International Electrotechnical Commission (IEC; in French: ''Commission électrotechnique internationale'') is an international standards organization that prepares and publishes international standards for all electrical, electronic and r ...
on surge immunity. In an electrical installation, disruptive surges can appear on power and data lines. Their sources include abrupt load switching and faults in the power system, as well as induced
lightning Lightning is a naturally occurring electrostatic discharge during which two electric charge, electrically charged regions, both in the atmosphere or with one on the land, ground, temporarily neutralize themselves, causing the instantaneous ...
transients from an indirect lightning strike (direct lightning is out of scope in this standard). It necessitates the test of surge immunity in electrical or electronic equipment. IEC 61000-4-5 defines test set-up, procedures, and classification levels. In particular, it standardizes the required surge voltage and current waveforms for laboratory testing, with the "1.2/50-8/20 μs" impulse being the most frequently used surge waveform. Although this standard is designed for testing equipment as a whole at system level, not for individual protection devices, in practice this surge waveform is often also used for rating Transient Voltage Suppressors (TVS), Gas Discharge Tubes (GDT), Metal Oxide Varistors (MOV), and other surge protection devices. The current version is Third Edition (2014), amended in 2017.


Test Setup

Two major components are defined in this standard: two types of Combination Wave Generators (CWG) and various Coupling/Decoupling Networks (CDN) depending on the test level and type. First, a Combination Wave Generator is a standardized
impulse generator An impulse generator is an electrical apparatus which produces very short high-voltage or high-current surges. Such devices can be classified into two types: impulse voltage generators and impulse current generators. High impulse voltages are us ...
(sometimes also referred to as a lightning surge generator), it's used for producing simulated, standard voltage and current surges under laboratory conditions. Subsequently, the surge is transmitted into a port of the Device-Under-Test (DUT) via a coupling network. Finally, to prevent surges from reaching other devices via the power system during the test, a decoupling network is also inserted between the power line and the DUT.


Surge Waveforms

The Combination Wave Generator is required to have an output floating from ground, and be capable of generating both positive and negative impulses. Its repetition rate should be at least one impulse per 60 seconds. The surge is defined by the Combination Wave Generator's open-circuit voltage and short-circuit current waveforms, characterized by front time, duration, and peak values. With an open circuit output, the surge voltage is a double exponential pulse in the form of k(e^-e^). With a short circuit output, the surge current waveform is a
damped sine wave Damping is an influence within or upon an oscillatory system that has the effect of reducing or preventing its oscillation. In physical systems, damping is produced by processes that dissipate the energy stored in the oscillation. Examples incl ...
. The ratio between the peak open-circuit voltage and the peak short-circuit current is 2, giving an effective
output impedance The output impedance of an electrical network is the measure of the opposition to current flow (impedance), both static ( resistance) and dynamic ( reactance), into the load network being connected that is ''internal'' to the electrical source. The ...
of 2 Ω. Usually, the voltage waveform has a 1.2 μs front time and a 50 μs duration, and the current waveform has a 8 μs front time and 20 μs duration. This is the most commonly used surge waveform for most applications, often referred to as a "1.2/50-8/20 μs" surge. Alternatively, for outdoor telecommunication networks that experience a higher surge level, the standard also defines a more energetic generator with a 10/700 μs voltage waveform and a 5/320 μs current waveform. Front time and duration are not measured directly, but as virtual parameters derived from measurements. For open-circuit voltage, front time is defined to be 1.67 times the 30%-90%
rise time In electronics, when describing a voltage or current step function, rise time is the time taken by a signal to change from a specified low value to a specified high value. These values may be expressed as ratiosSee for example , and . or, equivalen ...
, duration is defined as the time interval between the 50% point of its rising edge and the 50% point of its falling edge. For short-circuit current, front time is defined to be 1.25 times the 10%-90% rise time, duration is defined as 1.18 times time interval between the 50% point of its rising edge and the 50% point of its falling edge. At the output of the generator, a 30% undershoot below zero is allowed. There's no overshoot or overshoot limit at the output of the Coupling Network.


Comparison with different standards


IEC 60060-1

It's worth noting that both "1.2/50 μs" voltage and "8/20 μs" current impulses are classic waveforms with a well-established history of use in high-voltage testing for electric power transmission. Thus, these waveforms are also defined by IEC 60060-1 "High-Voltage Test Techniques" and other standards in this context. In fact, the waveform definitions in IEC 61000-4-5 were originally based on IEC 60060-1. Nevertheless, there are important differences. In traditional high-voltage testing, voltage and current impulses are tested separately, not in combination. The "1.2/50 μs" generator is designed for insulation testing, and produces a high-voltage, low-current impulse into a high-impedance load. The output current of this generator is on the milliampere scale. The "8/20 μs" generator is designed for
surge arrester A 'surge protector'' (or spike suppressor, surge suppressor, surge diverter, surge protection device (SPD) or transient voltage surge suppressor (TVSS) is an appliance or device intended to protect electrical devices from voltage spikes in alt ...
testing, and produces a high-current surge into a low-impedance load. On the other hand, modern electronic devices can be high and low-impedance loads simultaneously due to non-linear devices, protection circuits, and arcing in a dielectric breakdown. As a result, it motivated the creation of the Combination Wave Generator with the ability to generate a high-voltage, high-current output during the same surge. In addition, both standards have different waveform tolerances and other technical requirements. Thus, IEC 61000-4-5 is not to be confused with IEC 60060-1 and other high-voltage tests that also use a "1.2/50 μs" or "8/20 μs" impulse.


IEC 61000-4-5 Ed. 2 and Ed. 3

When a Coupling Network is used, past experience has shown inconsistent waveforms between different generators. Thus, an important change in IEC 61000-4-5 Ed. 3 is that a Combination Wave Generator must be verified only with a 18 μF capacitor attached at the output. This causes a significant impact to the short-circuit current waveform. If the generator is to be designed without the coupling capacitor in mind, the output would no longer be standard compliant. Third Edition also simplified waveform definitions. The earlier standard contained two definitions of "1.2/50-8/20 μs" waveform parameters, based on either IEC 60060-1 or IEC 60469-1, and two definitions of "10/700-5/320 μs" waveform parameters, based on either IEC 60060-1 or ITU-T K series. Ed. 3 removed references to these standards and gives standalone definitions. Especially, front time has been redefined in terms of rise time, rather than a time interval from an extrapolated "virtual origin" using IEC 60060-1's approach. This allows one to use the built-in measurement feature on an oscilloscope, simplifying test procedures. For practical purposes, the differences between both definitions are negligible. However, because the new definition was created using IEC 60060-1 as its basis, a generator calibrated according to IEC 60469-1's definitions may no longer be standard compliant.


Circuit Analysis


1.2/50-8/20 μs Generator

The Combination Wave Generator is essentially a capacitor discharge circuit. Initially, the switch is open, a high voltage source charges the energy-storage capacitor C_c through a current-limiting resistor R_c. The switch is then closed to deliver an impulse to the load through a
pulse-forming network A pulse-forming network (PFN) is an electric circuit that accumulates electrical energy over a comparatively long time, and then releases the stored energy in the form of a relatively square pulse of comparatively brief duration for various pulse ...
, which consists of a rise time shaping inductor L_r, two impulse duration shaping resistors R_ and R_, and an impedance matching resistor R_m. The standard does not specify component values or practical circuits, any suitable design that conforms to the standard requirements can be used. A complete
circuit analysis A network, in the context of electrical engineering and electronics, is a collection of interconnected components. Network analysis is the process of finding the voltages across, and the currents through, all network components. There are many t ...
of the ideal surge generator, including design equations and component values, is available in the presentation ''Introduction To Voltage Surge Immunity Testing'' by Hesterman et, al. An updated derivation for the Third Edition is given in the paper ''Elementary and ideal equivalent circuit model of the 1,2/50-8/20 μs combination wave generator'' by Carobbi et, al.


Design Equations

The following design equations are derived by Carobbi et, al. In these equations, the charging voltage is E, and the components are C = C_c, R_1 = R_, R_2 = R_, R_ = R_, and L = L_r.


= Open-Circuit Voltage

= For open-circuit voltage, its
Laplace transform In mathematics, the Laplace transform, named after its discoverer Pierre-Simon Laplace (), is an integral transform In mathematics, an integral transform maps a function from its original function space into another function space via integra ...
is: Where: Thus, open-circuit voltage is a double exponential waveform: The voltage reaches its peak value at: And the peak voltage is:


= Short-Circuit Current

= When the output is shorted, note that the last resistor R_3 (R_ in the schematic) is effectively removed. For short-circuit current, its
Laplace transform In mathematics, the Laplace transform, named after its discoverer Pierre-Simon Laplace (), is an integral transform In mathematics, an integral transform maps a function from its original function space into another function space via integra ...
is: Where: Thus, short-circuit current is a
damped sine wave Damping is an influence within or upon an oscillatory system that has the effect of reducing or preventing its oscillation. In physical systems, damping is produced by processes that dissipate the energy stored in the oscillation. Examples incl ...
(from an underdamped RLC circuit): The current reaches its peak value at: And the peak current is:


= Solution

= Ignore the amplitude in , it becomes: By substituting x = \alpha t: The ratio \frac should be selected to make y(x)'s waveform have a duration over front-time ratio of 50/1.2 \approx 41.7. By numerically evaluating y(x)'s waveform (including its front time and duration) while varying this ratio, the solution is found to be \frac = 168. Next, \alpha and \beta are computed by numerically varying \alpha until 's waveform has a front time of 1.2 μs. The solution is \alpha^ = 68.2 μs. Therefore, \beta^ = 0.4 μs. Ignore the amplitude in , it becomes: By substituting z = \omega_0 t: The value Q should be selected to make y'(z)'s waveform have a duration over front time ratio of 20/8 = 2.5. By numerically evaluating y'(z)'s waveform (including its front time and duration) while varying Q, the solution is found to be Q = 1.46. Next, \omega_0 is computed by varying it numerically until 's waveform has a duration of 20 μs. With the correct duration, front time is also automatically satisfied. The solution is \frac = f_0 = 20.03\text. Once \alpha, \beta, \omega_0 and Q are solved, the circuit component values can be obtained, R_3 is derived first. Note that the effective output impedance is (by dividing by ): And can be rearranged as: Set output impedance R = 2 Ω, the solution is R_3 = 26.1 Ω. Finally, the closed-form solution of other component values is: The solution is C = 5.93 μF, L = 10.9 μH, R_1 = 20.2 Ω, and R_2 = 0.814 Ω. Output peak voltage is slightly lower than the charging voltage. To scale the voltage, use the amplitude in and set E = 1, this yields \frac = 0.943. Thus, the capacitor charging voltage is \frac = 1.06 times the output peak voltage. Note that this solution doesn't consider the coupling capacitor, and also has an undershoot of e^ = 0.34. The solution to both problems are discussed in the following sections.


Coupling Capacitor

An extra 18 μF series coupling capacitor has almost no effect on the open-circuit voltage, but affects short-circuit current significantly. Carobbi et, al. suggested the following iterative, trial-and-error design procedure to take the effect of the series coupling capacitor into account. First, without considering the capacitor, the original circuit analysis is reused, and circuit components values are obtained through a numerical solver. Next, the capacitor is added and the change of short-circuit waveform is noted. Then, the target waveform parameters for the numerical solver are "pre-distorted", obtaining a new set of component values (by changing front time, duration, and effective output impedance). For example, if the peak current becomes too low, component values are recalculated for a higher peak current by adjusting the effective output impedance target. These steps are repeated until the desired waveform is obtained. The result given here is accurate within 1.5% after two iterations, more iterations are required for higher accuracy.


Results

Both sources showed that it's not possible to exactly meet the waveform requirements without violating the 30% short-circuit current overshoot limit. Nevertheless, Hesterman, et. al. presented an approximate solution by adjusting the waveform parameters within tolerance. The derivation by Carobbi et, al. ignored the undershoot requirement, pointing out that a practical circuit may reduce overshoot to even practically zero in some cases if an unidirectional switch is used. Also, IEC 61000-4-5 states that there's no overshoot or undershoot requirement at the output of a coupling network. These solutions are only valid for an ideal generator, suitable for circuit simulation. It can be used as a starting point of practical generator design, but component values have to be adjusted further due to switch non-idealities. In an ideal circuit, open-circuit voltage rise time is governed by the time constant \frac, but a practical switch may cause rise time degradation. Further, due to the use of different switch types, a real generator may produce either a bidirectional impulse with undershoot, or an unidirectional impulse without undershoot. An ideal circuit model cannot predict these non-linear effects, and should not be treated as a complete circuit model of practical generators.


10/700-5/320 μs Generator

A different Combination Wave Generator is used for the 10/700-5/320 μs surge.


Test Levels

The following table shows the peak open-circuit voltage and short-circuit current of the Combination Wave Generator. The full current is not always actually applied to the DUT. Depending on the test setup and port type, an additional resistor may be used as a part of the coupling network to reduce the peak surge current into the DUT, raising the output impedance to 12 Ω or 42 Ω.


See also

*
IEC 61000-4-2 IEC 61000-4-2 is the International Electrotechnical Commission's immunity standard on electrostatic discharge (ESD). The publication is one of the basic EMC standards of the IEC 61000–4 series. The European equivalent of the standard is called ...
*
IEC 61000-4-4 IEC 61000-4-4 is the International_Electrotechnical_Commission, International Electrotechnical Commission's immunity standard based on electrical fast transient (EFT) / burst Transient (oscillation), transients. This publication is part of the grea ...
*
Surge protection A 'surge protector'' (or spike suppressor, surge suppressor, surge diverter, surge protection device (SPD) or transient voltage surge suppressor (TVSS) is an appliance or device intended to protect electrical devices from voltage spikes in alt ...
*
List of common EMC test standards The following list outlines a number of electromagnetic compatibility (EMC) standards which are known at the time of writing to be either available or have been made available for public comment. These standards attempt to standardize product E ...
*
List of IEC standards This is an incomplete list of standards published by the International Electrotechnical Commission (IEC). The numbers of older IEC standards were converted in 1997 by adding 60000; for example IEC 27 became IEC 60027. IEC standards often have m ...
*
List of EN standards European Standards (abbreviated EN, from the German name ("European Norm")) are technical standards drafted and maintained by CEN (European Committee for Standardization), CENELEC (European Committee for Electrotechnical Standardization) and ETSI ...


References


External links


IEC Webstore
*{{IEC, 61000-4-5
STMicroelectronics' Application note ''AN4275 IEC 61000-4-5 standard overview''
Electromagnetic compatibility #61000-4-5