HOME

TheInfoList



OR:

High-voltage transformer fire barriers, or transformer firewalls, transformer ballistic firewalls, transformer blast walls, are outdoor countermeasures against
cascading failure A cascading failure is a failure in a system of interconnected parts in which the failure of one or few parts leads to the failure of other parts, growing progressively as a result of positive feedback. This can occur when a single part fails, in ...
s in a national
electric grid An electrical grid is an interconnected network for electricity delivery from producers to consumers. Electrical grids vary in size and can cover whole countries or continents. It consists of:Kaplan, S. M. (2009). Smart Grid. Electrical Power ...
. The purpose of these barriers, like common fire barriers in building construction, is compartmentalisation of
transformer A transformer is a passive component that transfers electrical energy from one electrical circuit to another circuit, or multiple circuits. A varying current in any coil of the transformer produces a varying magnetic flux in the transformer' ...
fires, and compartmentalisation of transformer and bushing explosions―in which the fuel source of both fires and explosions is the
transformer oil Transformer oil or insulating oil is an oil that is stable at high temperatures and has excellent electrical insulating properties. It is used in oil-filled transformers (wet transformers), some types of high-voltage capacitors, fluorescent lamp b ...
. Without compartmentalisation, one ruptured transformer could start its neighbouring transformer on fire and thus create a
domino effect A domino effect or chain reaction is the cumulative effect generated when a particular event triggers a chain of similar events. This term is best known as a mechanical effect and is used as an analogy to a falling row of dominoes. It typically ...
that would affect the surrounding electric grid, particularly during peak times. High-voltage transformer fire barriers are typically located in electrical substations, but may also be attached to buildings, such as valve halls or manufacturing plants with large electrical distribution systems, such as pulp and paper mills. Outdoor transformer fire barriers that are attached at least on one side to a building are referred to as wing walls. At times, high-voltage transformers can be located immediately outside and sometimes inside of buildings, requiring higher fire-resistance ratings than other fire compartments in a building.


Voluntary recommendations by NFPA 850

The primary North American document that deals with outdoor high-voltage transformer fire barriers is NFPA 850. NFPA 850 outlines that outdoor oil-insulated transformers should be separated from adjacent structures and from each other by firewalls, spatial separation, or other approved means for the purpose of limiting the damage and potential spread of fire from a transformer failure.


Alternatives or enhancements to transformer fire barriers

The following may be used in place of or in addition to transformer fire barriers, depending on the design goals.


Automatic fire suppression systems

Fire protection water spray systems are used to cool a transformer to prevent damage if exposed to radiation heat transfer from a fire involving oil released from another transformer that has failed.


Transformer Fast Depressurization Systems (FDS)

Passive mechanical systems designed to depressurize the transformer a few milliseconds after the occurrence of an electrical fault. Those systems minimize the chance that a transformer tank will rupture given a minor fault but are not effective on major internal faults.


Alternatives to mineral-based transformer oil

Transformer oil Transformer oil or insulating oil is an oil that is stable at high temperatures and has excellent electrical insulating properties. It is used in oil-filled transformers (wet transformers), some types of high-voltage capacitors, fluorescent lamp b ...
is available in different levels of ignitability, including those approved by
FM Global FM Global is an American mutual insurance company based in Johnston, Rhode Island, United States, with offices worldwide, that specializes in loss prevention services primarily to large corporations throughout the world in the ''Highly Protecte ...

FM Data Sheet 5-4
indicates different levels of protection depending on the type of fluid used. Alternatives include, but are not limited to,
ester In chemistry, an ester is a compound derived from an oxoacid (organic or inorganic) in which at least one hydroxyl group () is replaced by an alkoxy group (), as in the substitution reaction of a carboxylic acid and an alcohol. Glycerides a ...
s and silicone oil.


See also

*
Arc fault An arc fault is a high power discharge of electricity between two or more conductors. This discharge generates heat, which can break down the wire's insulation and trigger an electrical fire. Arc faults can range in current from a few amps up to t ...
*
Cascading failure A cascading failure is a failure in a system of interconnected parts in which the failure of one or few parts leads to the failure of other parts, growing progressively as a result of positive feedback. This can occur when a single part fails, in ...
*
Countermeasure A countermeasure is a measure or action taken to counter or offset another one. As a general concept, it implies precision and is any technological or tactical solution or system designed to prevent an undesirable outcome in the process. The fi ...
*
Critical infrastructure protection Critical infrastructure protection (CIP) is a concept that relates to the preparedness and response to serious incidents that involve the critical infrastructure of a region or nation. The American Presidential directive PDD-63 of May 1998 set up ...
*
Electric grid security Electric grid security in the US refer to the activities that utilities, regulators, and other stakeholders play in securing the national electricity grid. The American electrical grid is going through one of the largest changes in its history, whic ...
*
Electrical power distribution Electric power distribution is the final stage in the delivery of electric power; it carries electricity from the transmission system to individual consumers. Distribution substations connect to the transmission system and lower the transmissi ...
* Fire test * Firewall (construction) *
North American Electric Reliability Corporation The North American Electric Reliability Corporation (NERC) is a nonprofit corporation based in Atlanta, Georgia, and formed on March 28, 2006, as the successor to the North American Electric Reliability Council (also known as NERC). The original ...
*
Passive fire protection Passive fire protection (PFP) is components or systems of a building or structure that slows or impedes the spread of the effects of fire or smoke without system activation, and usually without movement. Examples of passive systems include floo ...


References

{{Reflist Armour Electric power conversion Electric transformers Energy infrastructure Explosions Infrastructure Passive fire protection Security engineering