Cable insulation technologies
Like other power cables, high-voltage cables have the structural elements of one or more conductors, an insulation system, and a protective jacket. High-voltage cables differ from lower-voltage cables in that they have additional internal layers in the insulation system to control the electric field around the conductor. These additional layers are required at 2,000 volts and above between conductors. Without these semi-conducting layers, the cable will fail due to electrical stress within minutes. This technique was patented by Martin Hochstadter in 1916; the shield is sometimes called a Hochstadter shield and shielded cable used to be called H-Type Cable. Depending on the grounding scheme, the shields of a cable can be connected to the ground at one end or both ends of the cable. Splices in the middle of the cable can be also grounded depending on the length of the circuit and if a semiconducting jacket is employed on direct buried circuits. Since 1960 solid dielectric extruded cables have taken dominance in the distribution market. These medium voltage cables are generally insulated with EPR or XLPE polymeric insulation. EPR insulation is common on cables from 4 to 34kV. EPR is not commonly used over 35KV due to losses, however, it can be found in 69kV cables. XLPE is used at all voltage levels from the 600V class and up. Sometimes EAM insulation is marketed, however, market penetration remains fairly low. Solid, extruded insulation cables such as EPR and XLPE account for the majority of distribution and transmission cables produced today. However, the relative unreliability of early XLPE resulted in a slow adoption at transmission voltages. Cables of 330, 400, and 500 kV are commonly constructed using XLPE today, but this has occurred only in recent decades. An increasingly uncommon insulation type is PILC or paper insulation lead-covered cable. Some utilities still install this for distribution circuits as new construction or replacement. Sebastian Ziani de Ferranti was the first to demonstrate in 1887 that carefully dried and prepared kraft paper could form satisfactory cable insulation at 11,000 volts. Previously paper-insulated cable had only been applied for low-voltage telegraph and telephone circuits. An extruded lead sheath over the paper cable was required to ensure that the paper remained moisture-free. Mass-impregnated paper-insulated medium voltage cables were commercially practical by 1895. During World War II several varieties ofCable insulation components
High voltage is defined as any voltage over 1000 volts. Those of 2 to 33 kV are usually called ''medium voltage'' cables, those over 50 kV ''high voltage'' cables. Modern HV cables have a simple design consisting of a few parts: the conductor, the conductor shield, the insulation, the insulation shield, the metallic shield, and the jacket. Other layers can include water blocking tapes, ripcords, and armor wires. Copper or aluminum wires transports the current, see (1) in figure 1. (''For a detailed discussion on copper cables, see main article: Copper conductor.'') The insulation, insulation shield, and conductor shield are generally polymer-based with a few rare exceptions. Single conductor designs under 2000 KCM are generally concentric. The individual strands are often deformed during the stranding process to provide a smoother overall circumference. These are known are compact and compressed conductors. Compact offers a 10% reduction in conductor outer diameter while the compressed version only offers a 3% decrease. The selection of a compressed or compact conductor will often require a different connector during splicing. 2000 KCM and larger transmission cables often include a sectored style design to reduce skin effect losses. Utility power cables are often designed to run at up to 75C, 90C, and 105C conductor temperatures. This temperature is limited by the construction standard and jacket selection. The conductor shield is always permanently bonded to the EPR or XLPE cable insulation in the solid dielectric cable. The semi-conductive insulation shield can be bonded or removable depending on the desires of the purchaser. For voltages 69KV and up the insulation shield is generally bonded. A strippable insulation shield is purchased to reduce splicing time and skill. It can be argued that strippable Semicon can lead to fewer workmanship issues at medium voltage. With paper insulated cables the semiconducting layers consist of carbon-bearing or metalized tapes applied over the conductor and paper insulation. The function of these layers is to prevent air-filled cavities and suppress voltage stress between the metal conductors and the dielectric so that little electric discharges cannot arise and endanger the insulation material. The insulation shield is covered by a copper, aluminum, or lead "screen." The metallic shield or sheath serves as an earthed layer and will drain leakage currents. The shield's function is not to conduct faults but that functionality can be designed if desired. Some designs that could be used are copper tape, concentric copper wires, longitudinally corrugated shields, copper flat straps, or extruded lead sheath. The cable jacket is often polymeric. The function of the jacket is to provide mechanical protection as well as prevent moisture & chemical intrusion. Jackets can be semiconducting or non-conducting depending on soil conditions and desired grounding configuration. Semiconducting jackets can also be employed on cables to help with a jacket integrity test. Some types of jackets are LLDPE, HDPE, polypropylene, PVC (bottom end of the market), LSZH, etc.Quality
During the development of high voltage insulation, which has taken about half a century, two characteristics proved to be paramount. First, the introduction of the semiconducting layers. These layers must be absolutely smooth, without even protrusions as small as a fewHVDC cable
A high-voltage cable for high-voltage direct current (HVDC) transmission has the same construction as the AC cable shown in figure 1. The physics and the test requirements are different. In this case the smoothness of the semiconducting layers (2) and (4) is of utmost importance. Cleanliness of the insulation remains imperative. Many HVDC cables are used for DC submarine connections, because at distances over approximately 100 km AC can no longer be used. As of 2021 the longest submarine cable today is the North Sea Link cable between Norway and the UK which is long.Cable terminals
Terminals of high-voltage cables must manage theCable joints
Connecting two high-voltage cables with one another poses two main problems. First, the outer conducting layers in both cables must be terminated without causing a field concentration, as with the making of a cable terminal. Secondly, a field-free space must be created where the cut-down cable insulation and the connector of the two conductors safely can be accommodated. These problems were solved by NKF inHand-taped joints
Hand taped joints are the old-school method of splicing and terminating cable. The construction of these joints involves taking several types of tape and manually building up appropriate stress relief. Some of the tapes involved could be rubber tapes, semiconducting tapes, friction tapes, varnished cambric tapes, etc. This splicing method is incredibly labor and time-intensive. It requires measuring the diameter and length of the layers being built up. Often the tapes must be half-lapped and pulled tight to prevent the formation of windows or voids in the resulting splice. Waterproofing hand taped splicing is very difficult.Pre-molded joints
Pre-molded joints are injection molded bodies created in two or more stages. Due to automation, the faraday cage will have a precise geometry and placement not achievable in taped joints. Pre-molded joints come in many different body sizes that much be matched up to the cable Semicon's outside diameter. A tight joint interface is required to ensure waterproofing. These joints are often pushed on and can cause soft tissue injuries among craftsmen.Heat shrink joints
Heat shrink joints consist of many different heat shrink tubes: insulating and conducting. These kits are less labor-intensive than taping but more than pre-molded. There can be concerns about having an open flame in a manhole or building vault. There can also be workmanship concerns with using a torch as the tubes must be fully recovered without scorching and any mastics used must flow into the voids and eliminate any air. Sufficient time and heat must be given. There are also a high number of components that must be placed in the correct order and position relative to the center of the joint.Cold shrink joints
Cold shrink is the newest family of joints. The idea is a polymer tube is formed at the correct diameter for the cable. It is then expanded over a form and placed onto a hold-out tube at the factory. Then ready for installation the joint is very easily slipped over the cable end. After the connector is installed the splicer simply needs to center the joint body and then release the holdout. The tube will automatically recover to the original size. The only complication is cold shrink has a shelf life of approximately 2–3 years. After that time period, the rubber will form memory and not recover down to the intended size. This can lead to joint failure if not installed before the recommended date. From a utility perspective, this makes it difficult to keep track of stock or retain emergency spares for critical customers. Cold shrink is the more rapidly growing area of distribution splices and is thought to have the fewest workmanship issues with the quickest install times.X-ray cable
X-ray cables Kreuger 1991 Vol. 1, pp. 65, 133 are used in lengths of several meters to connect the HV source with an X-ray tube or any other HV device in scientific equipment. They transmit small currents, in the order of milliamperes at DC voltages of 30 to 200 kV, or sometimes higher. The cables are flexible, with rubber or otherTesting of high-voltage cables
There are different causes for faulty cable insulation when considering solid dielectric or paper insulation. Hence, there are various test and measurement methods to prove fully functional cables or to detect faulty ones. While paper cables are primarily tested with DC insulation resistance tests the most common test for solid dielectric cable systems is the partial discharge test. One needs to distinguish between cable testing and cable diagnosis. While cable testing methods result in a go/no go statement cable diagnosis methods allow judgment of the cable's current condition. With some tests, it is even possible to locate the position of the defect in the insulation before failure. In some cases, electrical treeing (water trees) can be detected by tan delta measurement. Interpretation of measurement results can in some cases yield the possibility to distinguish between new, strongly water treed cable. Unfortunately, there are many other issues that can erroneously present themselves as high tangent delta, and the vast majority of solid dielectric defects can not be detected with this method. Damage to the insulation and electrical treeing may be detected and located by partial discharge measurement. Data collected during the measurement procedure are compared to measurement values of the same cable gathered during the acceptance test. This allows a simple and quick classification of the dielectric condition of the tested cable. Just like with tangent delta, this method has many caveats, but with good adherence to factory test standards, field results can be very reliable.See also