Geo-thermal Heating And Cooling
   HOME

TheInfoList



OR:

A ground source heat pump (also geothermal heat pump) is a heating/cooling system for buildings that uses a type of heat pump to transfer heat to or from the ground, taking advantage of the relative constancy of temperatures of the earth through the seasons. Ground source heat pumps (GSHPs) – or geothermal heat pumps (GHP) as they are commonly termed in North America – are among the most energy-efficient technologies for providing
HVAC Heating, ventilation, and air conditioning (HVAC) is the use of various technologies to control the temperature, humidity, and purity of the air in an enclosed space. Its goal is to provide thermal comfort and acceptable indoor air quality. HV ...
and
water heating Water heating is a heat transfer process that uses an energy source to heat water above its initial temperature. Typical domestic uses of hot water include cooking, cleaning, bathing, and space heating. In industry, hot water and water heated t ...
, using far less energy than can be achieved by burning a fuel in a boiler/furnace or by use of resistive
electric heater Electric heating is a process in which electrical energy is converted directly to heat energy at around 100% efficiency, using rather cheap devices. Common applications include space heating, cooking, water heating and industrial processes. A ...
s. Efficiency is given as a coefficient of performance (CoP) which is typically in the range 3 – 6, meaning that the devices provide 3 – 6 units of heat for each unit of electricity used. Setup costs are higher than for other heating systems due to the requirement to install ground loops over large areas or drill bore holes, and for this reason air source heat pumps are often used instead.


Thermal properties of the ground

Ground-source heat pumps take advantage of the difference between the ambient temperature and the temperature at various depths in the ground. The thermal properties of the ground near the surfaceKalogirou, Soteris & Florides, Georgios. (2004). Measurements of Ground Temperature at Various Depths, conference paper 3rd International Conference on Sustainable Energy Technologies, Nottingham, UK, https://www.researchgate.net/publication/30500372_Measurements_of_Ground_Temperature_at_Various_Depths https://ktisis.cut.ac.cy/bitstream/10488/870/3/C55-PRT020-SET3.pdfWilliams G. and Gold L. Canadian Building Digest 180m 1976. National Research Council of Canada, Institute for Research in Construction. https://nrc-publications.canada.ca/eng/view/ft/?id=386ddf88-fe8d-45dd-aabb-0a55be826f3f, can be described as follows: * In the surface layer to a depth of about 1 metre, the temperature is very sensitive to sunlight and weather, * In the shallow layer to a depth of about 8-20 metres depending on soil type, the thermal mass of the ground causes temperature variation to decrease exponentially with depth until it is close to the local annual average air temperature; it also lags behind the surface temperature, so that the peak temperature is about 6 months after the surface peak temperature * Below that, in the deeper layer, the temperature is effectively constant, rising about 0.025 °C per metre according to the geothermal gradient. The "penetration depth" is defined as the depth at which the temperature variable is less than 0.01 of the variation at the surface, and this depends on the type of soil:


History

The heat pump was described by Lord Kelvin in 1853 and developed by Peter Ritter von Rittinger in 1855. Heinrich Zoelly had patented the idea of using it to draw heat from the ground in 1912. After experimenting with a freezer, Robert C. Webber built the first direct exchange ground source heat pump in the late 1940s; sources disagree, however, as to the exact timeline of his invention The first successful commercial project was installed in the Commonwealth Building (Portland, Oregon) in 1948, and has been designated a National Historic Mechanical Engineering Landmark by ASME. Professor Carl Nielsen of Ohio State University built the first residential open loop version in his home in 1948. As a result of the
1973 oil crisis The 1973 oil crisis or first oil crisis began in October 1973 when the members of the Organization of Arab Petroleum Exporting Countries (OAPEC), led by Saudi Arabia, proclaimed an oil embargo. The embargo was targeted at nations that had supp ...
, ground source heat pumps became popular in Sweden and have been growing slowly in worldwide acceptance since then. Open loop systems dominated the market until the development of polybutylene pipe in 1979 made closed loop systems economically viable. As of 2004, there are over a million units installed worldwide, providing 12 GW of thermal capacity with a growth rate of 10% per year. Each year (as of 2011/2004, respectively), about 80,000 units are installed in the US and 27,000 in Sweden. In Finland, a geothermal heat pump was the most common heating system choice for new detached houses between 2006 and 2011 with market share exceeding 40%.


Arrangement


Internal arrangement

A heat pump is the central unit for the building's heating and cooling. It usually comes in two main variants: ''Liquid-to-water'' heat pumps (also called ''water-to-water'') are hydronic systems that carry heating or cooling through the building through pipes to conventional radiators, underfloor heating, baseboard radiators and hot water tanks. These heat pumps are also preferred for pool heating. Heat pumps typically only heat water to about efficiently, whereas boilers typically operate at . The size of radiators designed for the higher temperatures achieved by boilers may be too small for use with heat pumps, requiring replacement with larger radiators when retrofitting a home from boiler to heat pump. When used for cooling, the temperature of the circulating water must normally be kept above the dew point to ensure that atmospheric humidity does not condense on the radiator. ''Liquid-to-air'' heat pumps (also called ''water-to-air'') output forced air, and are most commonly used to replace legacy forced air furnaces and central air conditioning systems. There are variations that allow for split systems, high-velocity systems, and ductless systems. Heat pumps cannot achieve as high a fluid temperature as a conventional furnace, so they require a higher volume flow rate of air to compensate. When retrofitting a residence, the existing ductwork may have to be enlarged to reduce the noise from the higher air flow.


Ground heat exchanger

Ground source heat pumps employ a ground heat exchanger in contact with the ground or groundwater to extract or dissipate heat. Incorrect design can result in the system freezing after a number of years or very inefficient system performance; thus accurate system design is critical to a successful system Pipework for the ground loop is typically made of high-density polyethylene pipe and contains a mixture of water and anti-freeze ( propylene glycol, denatured alcohol or
methanol Methanol (also called methyl alcohol and wood spirit, amongst other names) is an organic chemical and the simplest aliphatic alcohol, with the formula C H3 O H (a methyl group linked to a hydroxyl group, often abbreviated as MeOH). It is a ...
). Monopropylene glycol has the least damaging potential when it might leak into the ground, and is, therefore, the only allowed anti-freeze in ground sources in an increasing number of European countries. ;Horizontal A horizontal closed loop field is composed of pipes that are arrayed in a plane in the ground. A long trench, deeper than the frost line, is dug and U-shaped or slinky coils are spread out inside the same trench. Shallow horizontal heat exchangers experience seasonal temperature cycles due to solar gains and transmission losses to ambient air at ground level. These temperature cycles lag behind the seasons because of thermal inertia, so the heat exchanger will harvest heat deposited by the sun several months earlier, while being weighed down in late winter and spring, due to accumulated winter cold. Systems in wet ground or in water are generally more efficient than drier ground loops since water conducts and stores heat better than solids in sand or soil. If the ground is naturally dry, soaker hoses may be buried with the ground loop to keep it wet. ;Vertical A vertical system consists of a number of boreholes some deep fitted with U-shaped pipes through which a heat-carrying fluid that absorbs (or discharges) heat from (or to) the ground is circulated.Li M, Lai ACK. Review of analytical models for heat transfer by vertical ground heat exchangers (GHEs): A perspective of time and space scales, Applied Energy 2015; 151: 178-191.Hellstrom G. Ground heat storage – thermal analysis of duct storage systems I. Theory. Lund: University of Lund; 1991. Bore holes are spaced at least 5–6 m apart and the depth depends on ground and building characteristics. Alternatively, pipes may be integrated with the
foundation pile A deep foundation is a type of foundation that transfers building loads to the earth farther down from the surface than a shallow foundation does to a subsurface layer or a range of depths. A pile or piling is a vertical structural element ...
s used to support the building. Vertical systems rely on migration of heat from surrounding geology, unless recharged during the summer and at other times when surplus heat is available. Vertical systems are typically used where there is insufficient available land for a horizontal system. Pipe pairs in the hole are joined with a U-shaped cross connector at the bottom of the hole or comprises two small-diameter high-density polyethylene (HDPE) tubes thermally fused to form a U-shaped bend at the bottom. The space between the wall of the borehole and the U-shaped tubes is usually grouted completely with grouting material or, in some cases, partially filled with groundwater. For illustration, a detached house needing 10 kW (3 ton) of heating capacity might need three boreholes deep. ;Radial or directional drilling As an alternative to trenching, loops may be laid by mini
horizontal directional drilling Directional boring, also referred to as horizontal directional drilling (HDD), is a minimal impact trenchless method of installing underground utilities such as pipe, conduit, or cables in a relatively shallow arc or radius along a prescribed und ...
(mini-HDD). This technique can lay piping under yards, driveways, gardens or other structures without disturbing them, with a cost between those of trenching and vertical drilling. This system also differs from horizontal & vertical drilling as the loops are installed from one central chamber, further reducing the ground space needed. Radial drilling is often installed retroactively (after the property has been built) due to the small nature of the equipment used and the ability to bore beneath existing constructions. ;Open loop In an open-loop system (also called a groundwater heat pump), the secondary loop pumps natural water from a well or body of water into a heat exchanger inside the heat pump. Since the water chemistry is not controlled, the appliance may need to be protected from corrosion by using different metals in the heat exchanger and pump. Limescale may foul the system over time and require periodic acid cleaning. This is much more of a problem with cooling systems than heating systems. A standing column well system is a specialized type of open-loop system where water is drawn from the bottom of a deep rock well, passed through a heat pump, and returned to the top of the well. A growing number of jurisdictions have outlawed open-loop systems that drain to the surface because these may drain aquifers or contaminate wells. This forces the use of more environmentally sound injection wells or a closed-loop system. ;Pond A closed pond loop consists of coils of pipe similar to a slinky loop attached to a frame and located at the bottom of an appropriately sized pond or water source. Artificial ponds are used as heat storage (up to 90% efficient) in some central solar heating plants, which later extract the heat (similar to ground storage) via a large heat pump to supply district heating. ;Direct exchange (DX) The
direct exchange geothermal heat pump A direct exchange (DX) geothermal heat pump is a type of ground source heat pump in which refrigerant A refrigerant is a working fluid used in the heat pump and refrigeration cycle, refrigeration cycle of air conditioning systems and heat pump ...
(DX) is the oldest type of geothermal heat pump technology where the refrigerant itself is passed through the ground loop. Developed during the 1980s, this approach faced issues with the
refrigerant A refrigerant is a working fluid used in the heat pump and refrigeration cycle, refrigeration cycle of air conditioning systems and heat pumps where in most cases they undergo a repeated phase transition from a liquid to a gas and back again. Ref ...
and oil management system, especially after the ban of CFC refrigerants in 1989 and DX systems now are infrequently used.


Installation

Because of the technical knowledge and equipment needed to design and size the system properly (and install the piping if heat fusion is required), a GSHP system installation requires a professional's services. Several installers have published real-time views of system performance in an online community of recent residential installations. The
International Ground Source Heat Pump Association Established in 1987, the International Ground Source Heat Pump Association (IGSHPA) is a nonprofit, membership-based organization that promotes geothermal heat pump technology. It was a outreach unit of the College of Engineering, Architecture and T ...
(
IGSHPA Established in 1987, the International Ground Source Heat Pump Association (IGSHPA) is a nonprofit, membership-based organization that promotes geothermal heat pump technology. It was a outreach unit of the College of Engineering, Architecture and T ...
), Geothermal Exchange Organization (GEO), th
Canadian GeoExchange Coalition
and th
Ground Source Heat Pump Association
maintain listings of qualified installers in the US, Canada and the UK. Furthermore, detailed analysis of Soil thermal conductivity for horizontal systems and formation thermal conductivity for vertical systems will generally result in more accurately designed systems with a higher efficiency.


Thermal performance

Cooling performance is typically expressed in units of BTU/hr/watt as the energy efficiency ratio (EER), while heating performance is typically reduced to dimensionless units as the coefficient of performance (COP). The conversion factor is 3.41 BTU/hr/watt. Since a heat pump moves three to five times more heat energy than the electric energy it consumes, the total energy output is much greater than the electrical input. This results in net thermal efficiencies greater than 300% as compared to radiant electric heat being 100% efficient. Traditional combustion furnaces and
electric heater Electric heating is a process in which electrical energy is converted directly to heat energy at around 100% efficiency, using rather cheap devices. Common applications include space heating, cooking, water heating and industrial processes. A ...
s can never exceed 100% efficiency. Ground source heat pumps can reduce energy consumption – and corresponding air pollution emissions – up to 72% compared to electric resistance heating with standard air-conditioning equipment. Efficient compressors, variable speed compressors and larger heat exchangers all contribute to heat pump efficiency. Residential ground source heat pumps on the market today have standard COPs ranging from 2.4 to 5.0 and EERs ranging from 10.6 to 30. To qualify for an Energy Star label, heat pumps must meet certain minimum COP and EER ratings which depend on the ground heat exchanger type. For closed-loop systems, the ISO 13256-1 heating COP must be 3.3 or greater and the cooling EER must be 14.1 or greater. Standards ARI 210 and 240 define Seasonal Energy Efficiency Ratio (SEER) and
Heating Seasonal Performance Factor Heating seasonal performance factor (HSPF) is a term used in the heating and cooling industry. HSPF is specifically used to measure the efficiency of air source heat pumps. HSPF is defined as the ratio of heat output (measured in BTUs) over the ...
s (HSPF) to account for the impact of seasonal variations on air source heat pumps. These numbers are normally not applicable and should not be compared to ground source heat pump ratings. However, Natural Resources Canada has adapted this approach to calculate typical seasonally adjusted HSPFs for ground-source heat pumps in Canada. Note: contrary to air-source conventions, the NRC's HSPF numbers are in units of BTU/hr/watt. Divide these numbers by 3.41 BTU/hr/watt to arrive at non-dimensional units comparable to ground-source COPs and air-source HSPF. The NRC HSPFs ranged from 8.7 to 12.8 BTU/hr/watt (2.6 to 3.8 in nondimensional factors, or 255% to 375% seasonal average electricity utilization efficiency) for the most populated regions of Canada. For the sake of comparing heat pump appliances to each other, independently from other system components, a few standard test conditions have been established by the
American Refrigerant Institute The Air Conditioning, Heating, and Refrigeration Institute (AHRI), formed in 2008 by a merger of the Air-Conditioning and Refrigeration Institute (ARI) and the Gas Appliance Manufacturers Association (GAMA), is a North American trade association of ...
(ARI) and more recently by the International Organization for Standardization. Standard ARI 330 ratings were intended for closed-loop ground-source heat pumps, and assume secondary loop water temperatures of for air conditioning and for heating. These temperatures are typical of installations in the northern US. Standard ARI 325 ratings were intended for open-loop ground-source heat pumps, and include two sets of ratings for groundwater temperatures of and . ARI 325 budgets more electricity for water pumping than ARI 330. Neither of these standards attempts to account for seasonal variations. Standard ARI 870 ratings are intended for direct exchange ground-source heat pumps. ASHRAE transitioned to ISO 13256-1 in 2001, which replaces ARI 320, 325 and 330. The new ISO standard produces slightly higher ratings because it no longer budgets any electricity for water pumps. Soil without artificial heat addition or subtraction and at depths of several metres or more remains at a relatively constant temperature year round. This temperature equates roughly to the average annual air temperature of the chosen location, usually at a depth of in the northern US. Because this temperature remains more constant than the air temperature throughout the seasons, Ground source heat pumps perform with far greater efficiency during extreme air temperatures than air conditioners and air-source heat pumps.


Analysis of heat transfer

A challenge in predicting the thermal response of a ground heat exchanger (GHE) is the diversity of the time and space scales involved. Four space scales and eight time scales are involved in the heat transfer of GHEs. The first space scale having practical importance is the diameter of the borehole (~ 0.1 m) and the associated time is on the order of 1 hr, during which the effect of the heat capacity of the backfilling material is significant. The second important space dimension is the half distance between two adjacent boreholes, which is on the order of several meters. The corresponding time is on the order of a month, during which the thermal interaction between adjacent boreholes is important. The largest space scale can be tens of meters or more, such as the half-length of a borehole and the horizontal scale of a GHE cluster. The time scale involved is as long as the lifetime of a GHE (decades). The short-term hourly temperature response of the ground is vital for analyzing the energy of ground-source heat pump systems and for their optimum control and operation. By contrast, the long-term response determines the overall feasibility of a system from the standpoint of the life cycle. Addressing the complete spectrum of time scales require vast computational resources. The main questions that engineers may ask in the early stages of designing a GHE are (a) what the heat transfer rate of a GHE as a function of time is, given a particular temperature difference between the circulating fluid and the ground, and (b) what the temperature difference as a function of time is, given a required heat exchange rate. In the language of heat transfer, the two questions can probably be expressed as q_l =
_f(t) - T_0 F, or f, is the sixth letter in the Latin alphabet, used in the modern English alphabet, the alphabets of other western European languages and others worldwide. Its name in English is ''ef'' (pronounced ), and the plural is ''efs''. Hist ...
R(t) where ''T''f is the average temperature of the circulating fluid, ''T''0 is the effective, undisturbed temperature of the ground, ''ql'' is the heat transfer rate of the GHE per unit time per unit length (W/m), and ''R'' is the total thermal resistance (m.K/W).''R''(''t'') is often an unknown variable that needs to be determined by heat transfer analysis. Despite ''R''(''t'') being a function of time, analytical models exclusively decompose it into a time-independent part and a time-dependent part to simplify the analysis. Various models for the time-independent and time-dependent R can be found in the references. Further, a
Thermal response test A thermal response test (TRT) is used to determine the thermal properties of the ground. There is no direct way to measure ground thermal conductivity and borehole thermal resistance. The TRT is vital for designing ground source heat pumps and seaso ...
is often performed to make a deterministic analysis of ground thermal conductivity to optimize the loopfield size, especially for larger commercial sites (e.g., over 10 wells).


Seasonal thermal storage

The efficiency of ground source heat pumps can be greatly improved by using seasonal thermal energy storage and interseasonal heat transfer. Heat captured and stored in thermal banks in the summer can be retrieved efficiently in the winter. Heat storage efficiency increases with scale, so this advantage is most significant in commercial or district heating systems.
Geosolar combisystem A solar combisystem provides both solar space heating and cooling as well as hot water from a common array of solar thermal collectors, usually backed up by an auxiliary non-solar heat source. Solar combisystems may range in size from those i ...
s have been used to heat and cool a greenhouse using an aquifer for thermal storage. In summer, the greenhouse is cooled with cold ground water. This heats the water in the aquifer which can become a warm source for heating in winter. The combination of cold and heat storage with heat pumps can be combined with water/humidity regulation. These principles are used to provide renewable heat and renewable cooling to all kinds of buildings. Also the efficiency of existing small heat pump installations can be improved by adding large, cheap, water-filled solar collectors. These may be integrated into a to-be-overhauled parking lot, or in walls or roof constructions by installing one-inch PE pipes into the outer layer.


Environmental impact

The US Environmental Protection Agency (EPA) has called ground source heat pumps the most energy-efficient, environmentally clean, and cost-effective space conditioning systems available. Heat pumps offer significant emission reductions potential, particularly where they are used for both heating and cooling and where the electricity is produced from renewable resources. GSHPs have unsurpassed thermal efficiencies and produce zero emissions locally, but their electricity supply includes components with high greenhouse gas emissions unless the owner has opted for a 100%
renewable energy Renewable energy is energy that is collected from renewable resources that are naturally replenished on a human timescale. It includes sources such as sunlight, wind, the movement of water, and geothermal heat. Although most renewable energy ...
supply. Their environmental impact, therefore, depends on the characteristics of the electricity supply and the available alternatives. The GHG emissions savings from a heat pump over a conventional furnace can be calculated based on the following formula: \text=\mathrm \left( \frac\mathrm-\frac\mathrm\right) *HL = seasonal heat load ≈ 80 GJ/yr for a modern detached house in the northern US *FI = emissions intensity of fuel = 50 kg(CO2)/GJ for natural gas, 73 for heating oil, 0 for 100%
renewable energy Renewable energy is energy that is collected from renewable resources that are naturally replenished on a human timescale. It includes sources such as sunlight, wind, the movement of water, and geothermal heat. Although most renewable energy ...
such as wind, hydro, photovoltaic or solar thermal *
AFUE The annual fuel utilization efficiency (AFUE; pronounced 'A'-'Few' or 'A'-'F'-'U'-'E') is a thermal efficiency measure of space-heating furnaces and boilers. The AFUE differs from the true 'thermal efficiency' in that it is not a steady-state, pea ...
= furnace efficiency ≈ 95% for a modern
condensing furnace Condensing boilers are water heaters typically used for heating systems that are fueled by gas or oil. When operated in the correct circumstances, a heating system can achieve high efficiency (greater than 90% on the higher heating value) by cond ...
*COP = heat pump coefficient of performance ≈ 3.2 seasonally adjusted for northern US heat pump *EI = emissions intensity of electricity ≈ 200–800 ton(CO2)/GWh, depending on the region's mix of electric power plants (Coal vs Natural Gas vs Nuclear, Hydro, Wind & Solar) Ground-source heat pumps always produce fewer greenhouse gases than air conditioners, oil furnaces, and electric heating, but natural gas furnaces may be competitive depending on the greenhouse gas intensity of the local electricity supply. In countries like Canada and Russia with low emitting electricity infrastructure, a residential heat pump may save 5 tons of carbon dioxide per year relative to an oil furnace, or about as much as taking an average passenger car off the road. But in cities like Beijing or Pittsburgh that are highly reliant on coal for electricity production, a heat pump may result in 1 or 2 tons more carbon dioxide emissions than a natural gas furnace. For areas not served by utility natural gas infrastructure, however, no better alternative exists. The fluids used in closed loops may be designed to be biodegradable and non-toxic, but the refrigerant used in the heat pump cabinet and in direct exchange loops was, until recently, chlorodifluoromethane, which is an ozone-depleting substance. The author issued a
updated version
of this article in February 2001.
Although harmless while contained, leaks and improper end-of-life disposal contribute to enlarging the ozone hole. For new construction, this refrigerant is being phased out in favor of the ozone-friendly but potent greenhouse gas
R410A R-410A, sold under the trademarked names AZ-20, EcoFluor R410, Forane 410A, Genetron R410A, Puron, and Suva 410A, is a zeotropic but near-azeotropic mixture of difluoromethane (CH2F2, called R-32) and pentafluoroethane (CHF2CF3, called R-125) th ...
. The EcoCute water heater is an air-source heat pump that uses carbon dioxide as its working fluid instead of chlorofluorocarbons. Open-loop systems (i.e. those that draw ground water as opposed to closed-loop systems using a borehole heat exchanger) need to be balanced by reinjecting the spent water. This prevents aquifer depletion and the contamination of soil or surface water with
brine Brine is a high-concentration solution of salt (NaCl) in water (H2O). In diverse contexts, ''brine'' may refer to the salt solutions ranging from about 3.5% (a typical concentration of seawater, on the lower end of that of solutions used for br ...
or other compounds from underground. Before drilling, the underground geology needs to be understood, and drillers need to be prepared to seal the borehole, including preventing penetration of water between strata. The unfortunate example is a geothermal heating project in
Staufen im Breisgau Staufen im Breisgau (High Alemannic: ''Staufe im Brisgau'') is a German town in the Breisgau-Hochschwarzwald district of Baden-Württemberg. It had a population of approximately 8,300 in 2019. General The city of Staufen im Breisgau lies in the ...
, Germany which seems the cause of considerable damage to historical buildings there. In 2008, the city centre was reported to have risen 12 cm, after initially sinking a few millimeters. The boring tapped a naturally pressurized aquifer, and via the borehole this water entered a layer of anhydrite, which expands when wet as it forms gypsum. The swelling will stop when the anhydrite is fully reacted, and reconstruction of the city center "is not expedient until the uplift ceases". By 2010 sealing of the borehole had not been accomplished. By 2010, some sections of town had risen by 30 cm.badische-zeitung.de, ''Lokales, Breisgau'', 15. Oktober 2010, hcw: ''Keine Entwarnung in der Fauststadt – Risse in Staufen: Pumpen, reparieren und hoffen''
(17. Oktober 2010)


Economics

Ground source heat pumps are characterized by high capital costs and low operational costs compared to other
HVAC Heating, ventilation, and air conditioning (HVAC) is the use of various technologies to control the temperature, humidity, and purity of the air in an enclosed space. Its goal is to provide thermal comfort and acceptable indoor air quality. HV ...
systems. Their overall economic benefit depends primarily on the relative costs of electricity and fuels, which are highly variable over time and across the world. Based on recent prices, ground-source heat pumps currently have lower operational costs than any other conventional heating source almost everywhere in the world. Natural gas is the only fuel with competitive operational costs, and only in a handful of countries where it is exceptionally cheap, or where electricity is exceptionally expensive. In general, a homeowner may save anywhere from 20% to 60% annually on utilities by switching from an ordinary system to a ground-source system. Capital costs and system lifespan have received much less study until recently, and the return on investment is highly variable. The most recent data from an analysis of 2011–2012 incentive payments in the state of Maryland showed an average cost of residential systems of $1.90 per watt, or about $26,700 for a typical (4 ton/14 kW) home system. An older study found the total installed cost for a system with 10 kW (3 ton) thermal capacity for a detached rural residence in the US averaged $8000–$9000 in 1995 US dollars. More recent studies found an average cost of $14,000 in 2008 US dollars for the same size system. The US Department of Energy estimates a price of $7500 on its website, last updated in 2008. One source in Canada placed prices in the range of $30,000–$34,000 Canadian dollars. The rapid escalation in system price has been accompanied by rapid improvements in efficiency and reliability. Capital costs are known to benefit from economies of scale, particularly for open-loop systems, so they are more cost-effective for larger commercial buildings and harsher climates. The initial cost can be two to five times that of a conventional heating system in most residential applications, new construction or existing. In retrofits, the cost of installation is affected by the size of the living area, the home's age, insulation characteristics, the geology of the area, and the location of the property. Proper duct system design and mechanical air exchange should be considered in the initial system cost. Capital costs may be offset by government subsidies; for example, Ontario offered $7000 for residential systems installed in the 2009 fiscal year. Some electric companies offer special rates to customers who install a ground-source heat pump for heating or cooling their building. Where electrical plants have larger loads during summer months and idle capacity in the winter, this increases electrical sales during the winter months. Heat pumps also lower the load peak during the summer due to the increased efficiency of heat pumps, thereby avoiding the costly construction of new power plants. For the same reasons, other utility companies have started to pay for the installation of ground-source heat pumps at customer residences. They lease the systems to their customers for a monthly fee, at a net overall saving to the customer. The lifespan of the system is longer than conventional heating and cooling systems. Good data on system lifespan is not yet available because the technology is too recent, but many early systems are still operational today after 25–30 years with routine maintenance. Most loop fields have warranties for 25 to 50 years and are expected to last at least 50 to 200 years. Ground-source heat pumps use electricity for heating the house. The higher investment above conventional oil, propane or electric systems may be returned in energy savings in 2–10 years for residential systems in the US. If compared to natural gas systems, the payback period can be much longer or non-existent. The payback period for larger commercial systems in the US is 1–5 years, even when compared to natural gas. Additionally, because geothermal heat pumps usually have no outdoor compressors or cooling towers, the risk of vandalism is reduced or eliminated, potentially extending a system's lifespan. Ground source heat pumps are recognized as one of the most efficient heating and cooling systems on the market. They are often the second-most cost-effective solution in extreme climates (after co-generation), despite reductions in thermal efficiency due to ground temperature. (The ground source is warmer in climates that need strong air conditioning, and cooler in climates that need strong heating.) The financial viability of these systems depends on the adequate sizing of ground heat exchangers (GHEs), which generally contribute the most to the overall capital costs of GSHP systems. Commercial systems maintenance costs in the US have historically been between $0.11 to $0.22 per m2 per year in 1996 dollars, much less than the average $0.54 per m2 per year for conventional HVAC systems. Governments that promote renewable energy will likely offer incentives for the consumer (residential), or industrial markets. For example, in the United States, incentives are offered both on the state and federal levels of government.Database of State Incentives for Renewables & Efficiency
. US Department of Energy.
In the United Kingdom the Renewable Heat Incentive provides a financial incentive for the generation of renewable heat based on metered readings on an annual basis for 20 years for commercial buildings. The domestic Renewable Heat Incentive is due to be introduced in Spring 2014 for seven years and be based on deemed heat.


See also

* Ground-coupled heat exchanger * Solar thermal cooling * Renewable heat *
International Ground Source Heat Pump Association Established in 1987, the International Ground Source Heat Pump Association (IGSHPA) is a nonprofit, membership-based organization that promotes geothermal heat pump technology. It was a outreach unit of the College of Engineering, Architecture and T ...
*
Glossary of geothermal heating and cooling The ''Glossary of Geothermal Heating and Cooling'' provides definitions of many terms used within the Geothermal heat pump industry. The terms in this glossary may be used by industry professionals, for education materials, and by the general publ ...
* Uniform Mechanical Code


References


External links


Geothermal Heat Pumps
( EERE/ USDOE).
Cost calculation

Geothermal Heat Pump Consortium

International Ground Source Heat Pump Association

Ground Source Heat Pump Association
(GSHPA) {{Portal box, Renewable energy Energy conversion Building engineering Heat pumps Sustainable technologies